<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 25HEALTH SERVICES
PART 1DEPARTMENT OF STATE HEALTH SERVICES
CHAPTER 131FREESTANDING EMERGENCY MEDICAL CARE FACILITIES
SUBCHAPTER FFIRE PREVENTION AND SAFETY REQUIREMENTS
RULE §131.121Fire Prevention, Protection, and Emergency Contingency Plan

(a) A facility shall comply with the provisions of this section with respect to fire prevention and protection.

  (1) A facility shall comply with local fire codes.

  (2) All incidents of fire shall be reported to the local fire authority and shall be reported in writing to the Department of State Health Services, Facility Licensing Group, Mail Code 1979, P.O. Box 149347 Austin, Texas 78714-9347, as soon as possible, but not later than 10 calendar days following the incident. Any fire incident causing injury to a person shall be reported no later than the next business day.

  (3) A facility shall adopt, implement, and enforce a written smoking policy.

(b) A facility shall adopt, implement, and enforce a written policy for periodic inspection, testing, and maintenance of fire fighting equipment, portable fire extinguishers, and when installed sprinkler systems. If installed, fire sprinkler systems shall comply with National Fire Protection Association 13, Standard for the Installation of Sprinkler Systems, 2002 Edition (NFPA 13). All documents published by National Fire Protection Association (NFPA) as referenced in this section may be obtained by writing or calling the NFPA at the following address or telephone number: National Fire Protection Association, 1 Batterymarch Park, Quincy, Massachusetts 02269-9101 or (800) 344-3555. NFPA documents are also available for public inspection during regular working hours at the offices of Architectural Review Group, Texas Department of State Health Services, 1100 West 49th Street, Austin, Texas 78756-3199.

  (1) All fire sprinkler systems, fire pumps, fire standpipe and hose systems, water storage tanks, and valves and fire department connections shall be inspected, tested, and maintained in accordance with National Fire Protection Association 25, Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems, 2002 Edition.

  (2) Every portable fire extinguisher located in a facility or upon facility property shall be installed, tagged, and maintained in accordance with National Fire Protection Association 10, Standard for Portable Fire Extinguishers, 2002 Edition.

(c) A plan for the protection of patients in the event of fire and their evacuation from the building when necessary shall be formulated according to NFPA 101, §21.7.1.1 Copies of the plan shall be available to all staff.

  (1) An evacuation floor plan shall be prominently and conspicuously posted for display throughout the facility in public areas that are readily visible to patients, employees, and visitors.

  (2) Each facility shall conduct an annual training program for instruction of all personnel in the location and use of fire fighting equipment. All employees shall be instructed regarding their duties under the fire protection and evacuation plan.

  (3) The facility shall conduct one fire drill per shift per quarter. The governing body of the facility shall define working shifts for the facility. Fire drills shall include the transmission of the fire alarm signal and simulation of the emergency fire condition, simulation of evacuation of patients and other occupants, and use of fire-fighting equipment. Written reports shall be maintained to include evidence of patient and staff participation. Fire exit drills shall incorporate the minimum requirements of NFPA 101, §§21.7.1.2 through 21.7.2.3.

  (4) All staff shall be familiar with the locations of fire fighting equipment. Fire fighting equipment shall be located so that a person shall not have to travel more than 75 feet from any point to reach the equipment.

(d) A fire alarm system shall be installed, maintained, and tested, in accordance with National Fire Protection Association 72, National Fire Alarm Code, 2002 Edition (NFPA 72) and NFPA 101, §21.3.4.

(e) A reliable communication system shall be provided as a means of reporting a fire to the fire department. This is in addition to the automatic alarm transmission to the fire department required by NFPA 101, §21.3.4.4.

(f) As an aid to fire department services, every facility shall provide the following:

  (1) The facility shall maintain driveways, free from all obstructions, to main buildings for fire department apparatus use.

  (2) Upon request, the facility shall submit a copy of the floor plans of the building to the local fire department officials.

  (3) The facility shall place proper identification on the outside of the main building showing the locations of siamese connections and standpipes as required by the local fire department services.

(g) When a facility is located outside of the service area or range of the public fire protection, arrangements shall be made to have the nearest fire department respond in case of a fire.

(h) The facility shall provide an emergency contingency plan for the continuity of emergency essential building systems. The emergency contingency plan shall consist of one of the two options as described in paragraphs (1) and (2) of this subsection.

  (1) An onsite emergency generator shall be provided with a Type II essential electrical distribution system in accordance with requirements of NFPA 99, §4.5, and National Fire Protection Association 110, Standard for Emergency and Standby Power Systems, 2002 Edition.

    (A) The minimum electrical load connection shall be in accordance with NFPA 99 §4.5.2.

    (B) An emergency generator standby power system(s) shall require an onsite fuel source and enough fuel capacity in the tank for a period of twenty-four hours or more. The facility shall execute contract(s) with the supplier/vendor(s) for fuel on demand. When a vapor liquefied petroleum gas (LPG) (natural gas) system is used, the twenty-four hour fuel capacity onsite is not required. The vapor withdrawal LPG system shall require a dedicated fuel supply.

    (C) The emergency generator shall be installed, tested and maintained in accordance with the National Fire Protection Association 99, §4.5.4, and National Fire Protection Association 110, Standard for Emergency and Standby Power Systems, 2002 Edition.

  (2) An executed contract(s) with an outside supplier/vendor that will provide a portable emergency generator(s) and fuel.

    (A) An electrical transfer switch with plug-in device sized to provide emergency power for the patient care areas and the provisions in NFPA 99, §4.5.2.2.2.

    (B) An alternate source of power (battery power lighting) shall be provided separate and independent from the normal electrical power source that will be effective for a minimum of one and one half hours after loss of the electrical power. The emergency lighting system shall be capable of providing sufficient illumination to allow safe evacuation from the building. The battery pack systems shall be maintained and tested quarterly.

    (C) The facility shall implement the emergency contingency plan upon the loss of electrical power following a natural weather or man-made event when the electrical power may not be restored within 24 hours. The facility shall exercise the contract(s) with the supplier/vendor(s) in order to have portable emergency generator(s) and potable water available within 36 hours after the loss of electrical power.

(i) The facility premises shall be kept free from accumulations of combustible materials not necessary for immediate operation of the facility.


Source Note: The provisions of this §131.121 adopted to be effective June 1, 2010, 35 TexReg 4400

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page