TITLE 30ENVIRONMENTAL QUALITY
PART 1TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
CHAPTER 290PUBLIC DRINKING WATER
SUBCHAPTER FDRINKING WATER STANDARDS GOVERNING DRINKING WATER QUALITY AND REPORTING REQUIREMENTS FOR PUBLIC WATER SYSTEMS
RULE §290.111Surface Water Treatment

  (2) A public water system that fails to submit a report required by subsection (h) of this section commits a reporting violation.

  (3) A public water system that has one or more of the following conditions as specified in subparagraphs (A) - (E) of this paragraph commits an acute treatment technique violation and is required to issue a public notice and a boil water notice within 24 hours in accordance with §290.122(a) of this title (relating to Public Notification).

    (A) A public water system using conventional filters that has a turbidity level exceeding 5.0 NTU in the combined filter effluent.

    (B) A public water system using conventional filters that has a combine filter effluent (CFE) turbidity level exceeding 2.0 NTU at plants that are required to have individual filter effluent (IFE) turbidimeters and failed to properly monitor or record IFE turbidity data during the period when the CFE turbidity level was above 2.0 NTU.

    (C) A public water system using conventional filters that has a CFE turbidity level exceeding 2.0 NTU at a plant that has only two filters, is not required to continuously monitor the IFE turbidity level at the effluent of each filter, and did not collect IFE turbidity grab samples during the period when CFE levels were above 2.0 NTU.

    (D) A public water system that fails to submit a report required by subsection (h) of this section for two consecutive months.

    (E) A public water system using membrane or cartridge filters that has a turbidity level exceeding 1.0 NTU in the combined filter effluent.

  (4) A public water system using conventional filters that has one or more of the following conditions as specified in subparagraphs (A) - (D) of this paragraph, and has not met the conditions as specified in paragraph (3) of this subsection, commits an acute treatment technique violation and is required to issue a public notice within 24 hours in accordance with §290.122(a) of this title.

    (A) A CFE turbidity level exceeding 1.0 NTU during a period when the disinfection protocol did not achieve an inactivation ratio of at least 2.0 for both Giardia and viruses.

    (B) A CFE turbidity level exceeding 1.0 NTU during a period that IFE turbidity levels were above 2.0 NTU at one or more filters.

    (C) A CFE turbidity level exceeding 1.0 NTU occurring at a plant that is required to have IFE turbidimeters and fails to properly monitor or record IFE turbidity data during the period when the CFE turbidity level was above 1.0 NTU.

    (D) A CFE turbidity level exceeding 1.0 NTU occurred at a plant that has only two filters, is not required to continuously monitor the IFE turbidity level at the effluent of each filter, and did not collect IFE turbidity grab samples during the period when CFE levels were above 1.0 NTU.

  (5) Except as provided in paragraphs (3) and (4) of this subsection, a public water system that violates the requirements of subsections (c), (d)(1), (e)(1), and (f)(1) of this section commits a nonacute treatment technique violation.

  (6) A system that fails to request a bin classification within six months of completing a round of source water monitoring commits a treatment technique violation.

  (7) A system that fails to correct the performance-limiting factors identified in a comprehensive performance evaluation conducted under the requirements of subsection (e)(4)(A)(iii) or (B)(iii) of this section commits a violation.

  (8) A system that fails to properly issue a public notice required by subsection (j) of this section commits a violation.

(j) Public notification. The owner or operator of a public water system that violates the requirements of this section must notify the executive director and the people served by the system.

  (1) A public water system that commits an acute treatment technique violation must notify the executive director and the water system customers of the acute violation within 24 hours in accordance with the requirements of §290.46(q) of this title and §290.122(a) of this title (relating to Public Notification).

  (2) A public water system that has a turbidity level exceeding 1.0 NTU in the combined filter effluent must consult with the executive director within 24 hours of the violation.

    (A) Based on the results of the consultation, the executive director will determine whether the water system must notify its customers in accordance with the requirements of §290.122(a) or (b) of this title.

    (B) A water system that fails to consult with the executive director as required by this paragraph must notify its customers in accordance with the requirements of §290.122(a) of this title.

  (3) Except as provided in paragraphs (1) and (2) of this subsection, a public water system that fails to meet the treatment technique requirements of subsections (c), (d)(1), (e)(1), or (f)(1) of this section must notify the executive director by the end of the next business day and the water system customers in accordance with the requirements of §290.122(b) of this title.

  (4) A public water system that fails to conduct the monitoring required by this section must notify its customers of the violation in accordance with the requirements of §290.122(c) of this title.


Source Note: The provisions of this §290.111 adopted to be effective September 13, 2000, 25 TexReg 8880; amended to be effective May 16, 2002, 27 TexReg 4127; amended to be effective February 19, 2004, 29 TexReg 1373; amended to be effective December 23, 2004, 29 TexReg 11729; amended to be effective January 9, 2008, 33 TexReg 198; amended to be effective May 15, 2011, 36 TexReg 2860; amended to be effective November 8, 2012, 37 TexReg 8849; amended to be effective July 30, 2015, 40 TexReg 4769; amended to be effective March 30, 2017, 42 TexReg 1466