Figure: 30 TAC §290.45(d)(1)

Table A
Type of Establishment Gallons/Person/Day
Restaurants. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Schools without cafeterias, gymnasiums, or showers. . . . . . . . . . . 18
Schools with cafeterias, but no gymnasiums or showers. . . . . . . . . 24
Schools with cafeterias, gymnasiums, and showers. . . . . . . . . . . . 30
Youth camps without flush toilets, showers, or dining halls. . . . . . 6
Youth camps with flush toilets, but no showers or dining halls. . . 24
Youth camps with flush toilets, showers, and dining halls. . . . . . .. 42
Office buildings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Hospitals (based on number of beds). . . . . . . . . . . . . . . . . . . . . . . . 720
Institutions, other than hospitals. . . . . . . . . . . . . . . . . . . . . . . . . . . 240
Factories (exclusive of industrial processes). . . . . . . . . . . . . . . . . . 24
Parks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Swimming pools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Country clubs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Airports (per passenger). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Self-service laundries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Service stations/stores. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

It should be noted that this table is used to determine minimum capacities only and that the overriding

criteria will be the ability of the system to maintain a minimum pressure of 35 psi under normal operating

conditions. Minimum distribution pressure shall not be less than 20 psi at any time.