Figure: 30 TAC §113.2174(e)
Municipal Waste Combustion Unit |
Carbon Monoxide Limitsa | Averaging Timesb |
---|---|---|
1. Fluidized bed | 100 parts per million by dry volume |
4-hour |
2. Fluidized bed, mixed fuel, (wood/refuse-derived fuel) |
200 parts per million by dry volume |
24-hourc |
3. Mass burn rotary refractory | 100 parts per million by dry volume |
4-hour |
4. Mass burn rotary waterwall | 250 parts per million by dry volume |
24-hour |
5. Mass burn waterwall and refractory |
100 parts per million by dry volume |
4-hour |
6. Mixed fuel-fired, (pulverized coal/refuse- derived fuel) |
150 parts per million by dry volume |
4-hour |
7. Modular starved-air and excess air |
50 parts per million by dry volume |
4-hour |
8. Spreader stoker, mixed fuel- fired (coal/refuse-derived fuel) |
200 parts per million by dry volume |
24-hour daily |
9. Stoker, refuse-derived fuel | 200 parts per million by dry volume |
24-hour daily |
aAll emission limits (except for opacity) are measured at 7 percent oxygen. Compliance is determined by continuous emission monitoring systems.
bBlock averages, arithmetic mean. See §113.2100 of this title for definitions.
c24-hour block average, geometric mean.