Figure: 25 TAC §135.56(b)

TABLE 2
FILTER EFFICIENCIES FOR CENTRAL VENTILATION
AND AIR CONDITIONING SYSTEMS

Area Designation Number
of Filter
Beds
Filter Bed No. 1
(Percent, MERV*)
Filter Bed No. 2
(Percent, MERV*)
General procedure operating rooms,
patient care areas, treatment,
diagnostic, those areas providing
direct service or clean supplies such
as sterile and clean processing, and
related areas.
2 30, 8 90, 14
Laboratories 1 80, 13 ----
Administrative, bulk storage, soiled
holding areas, and laundries
1 30, 8 ----

* MERV - Minimum efficiency rating value (American Society of Heating Refrigeration and Air-Conditioning Engineers (ASHRAE) Standard 52.2, 1999 edition.

NOTES:

•               Additional roughing or prefilters should be considered to reduce maintenance
 required for filters with efficiency higher than 75%.

•               The filtration efficiency ratings are based on ASHRAE Standard 52.1, 1992 edition.