Figure:16 TAC §65.615(7)
Exhibit 7
Firetube Boilers | Watertube Boilers | |
---|---|---|
Boiler Heating Surface | ||
Hand fired | 5 (24) | 6 (29) |
Stoker fired | 7 (34) | 8 (39) |
Oil, gas or pulverized fuel fired |
8 (39) | 10 (49) |
Waterwall Heating Surface | ||
Hand fired | 8 (39) | 8 (39) |
Stoker fired | 10 (49) | 12 (59) |
Oil, gas, or pulverized fuel fired |
14 (68) | 16 (78) |
Note: The minimum safety valve or safety relief valve relieving capacity for electric boilers
shall be 3 ½ lb/hr/kw (1.6 kg/hr/kw) input.
Minimum Required Safety Valve Capacity lb. (kg) of Steam/Hr. |
Blowoff Piping Valves, and Cocks Size, min. in. (mm) |
---|---|
(Note) | |
Up to 500 (226) | ¾ (20) |
501 to 1,250 (227 to 567) | 1 (25) |
1,251 to 2,500 (568 to 1184) | 1 ¼ (32) |
2,501 to 6,000 (1185 to 2721) | 1 ½ (40) |
6,001 (2722) and Larger | 2 (50) |
Note: To determine the discharge capacity of safety
relief valves in terms of Btu, the relieving
capacity in lbs. of steam/hr. is
multiplied by 1,000.