Figure: 25 TAC §134.131(d)
TABLE (4)
FILTER EFFICIENCIES FOR CENTRAL VENTILATION AND AIR CONDITIONING SYSTEMS
Area Designation |
Number of Filter Beds |
Filter Efficiencies (%) |
|
|
|
Filter Bed |
Filter Bed |
Patient care and treatment, diagnostic and related areas |
2 |
25 |
90 |
Laboratories and sterile storage |
1 |
80 |
|
Administrative, bulk storage, soiled holding areas, food preparation areas, and laundries |
1 |
30 |
|
NOTES: Additional roughing or prefilters should be considered to reduce maintenance required for filters with efficiency higher than 75%. The filtration efficiency ratings are based on American Society of Heating Refrigeration and Air-conditioning Engineers, Standard 52-92, 1992 edition.