Figure: 30 TAC §113.2072(a)

Table 2. Emission Limits for Small, Medium, and Large HMIWI.

Pollutant Units

(Corrected to 7% oxygen, dry basis

according to the formula in §113.2075)

Emission Limits
HMIWI Size
Small Small

Remote

Medium Large
Particulate Matter milligrams per dscm1

(grains per dscf2)

115

(0.05)

197

(0.086)

69

(0.03)

34

(0.015)

Carbon Monoxide parts per million by volume 40 40 40 40
Dioxins/furans nanograms per dscm total dioxins/furans

(grains per billion dscf)

or

nanograms per dscm on a TEQ basis 3

(grains per billion dscf)

125

(55)

or

2.3

(1.0)

800

(350)

or

15

(6.6)

125

(55)

or

2.3

(1.0)

125

(55)

or

2.3

(1.0)

Hydrogen Chloride parts per million by volume

or

percent reduction

100

or

95%

3100 100

or

95%

100

or

95%

Sulfur Dioxide parts per million by volume 55 55 55 55
Nitrogen Oxides parts per million by volume 250 250 250 250
Lead milligrams per dscm

(grains per thousand dscf)

or

percent reduction

1.2

(0.52)

or

70%

10

(4.4)

1.2

(0.52)

or

70%

1.2

(0.52)

or

70%

Cadmium milligrams per dscm

(grains per thousand dscf)

or

percent reduction

0.16

(0.07)

or

65%

4

(1.7)

0.16

(0.07)

or

65%

0.16

(0.07)

or

65%

Mercury milligrams per dscm

(grains per thousand dscf)

or

percent reduction

0.55

(0.24)

or

85%

7.5

(3.3)

0.55

(0.24)

or

85%

0.55

(0.24)

or

85%

Footnotes:

1 dscm = dry standard cubic meter

2 dscf = dry standard cubic foot

3 TEQ basis=2,3,7,8-tetrachlorinated dibenzo-p-dioxin toxic equivalent based on the 1989 international toxic equivalency factors. Dioxins/furans and oxygen content shall be measured at the same location.