Figure: 30 TAC §113.2074(a)
Table 3. Initial and Annual Inspection Requirements.
Items to be Inspected | Requirements |
Burners, pilot assemblies, and pilot sensing devices | Inspect for proper operation; clean pilot flame sensor, as necessary. |
Combustion air | Ensure proper adjustment of primary and secondary chamber combustion air, and adjust as necessary. |
Hinges and door latches | Inspect and lubricate as necessary. |
Dampers, fans, and blowers | Inspect for proper operation. |
Incinerator door and door gaskets | Inspect for proper sealing. |
Motors | Inspect for proper operation. |
Primary chamber refractory lining | Inspect lining; clean and repair/replace as necessary. |
Incinerator shell | Inspect for corrosion and/or hot spots. |
Secondary/tertiary chamber and stack | Inspect and clean as necessary. |
Mechanical loader, including limit switches | Inspect for proper operation, if applicable. |
Waste bed (grates) | visually inspect and repair/seal, as appropriate. |
Air pollution control device(s) | Inspect device(s) for proper operation, if applicable. |
Waste heat boiler systems | Inspect to ensure proper operation, if applicable. |
Bypass stack components | Inspect components. |
Thermocouples, sorbent feed systems, and any other monitoring equipment | Ensure proper calibration of equipment. |
General equipment | Generally observe that the equipment is maintained in good operating condition. |
Incinerator operation | For the burn cycle that follows the inspection, document that the incinerator is operating properly and make any necessary adjustments. |