Figure: 30 TAC §113.2075(a)(1)
Table 4. Test Methods.
EMISSION LIMIT | TEST METHODS (EPA Reference Methods are as specified in Title 40 Code of Federal Regulations, Appendix A, dated 1999, unless otherwise specified) |
|
Small-Remote HMIWI | Small, Medium, and Large HMIWI | |
Opacity | Method 9 | Method 9 |
Particulate Matter (PM) | Method 5 or Method 29 |
Method 5 or Method 29 |
Carbon Monoxide (CO) | Method 10 or 10B | Method 10, or 10B |
Dioxins/furans | Method 231 for total dioxins/furans or TEQ Method specified in §113.2075(a)(2)(I)(ii) |
Method 231 for total dioxins/furans or TEQ Method specified in §113.2075(a)(2)(I)(ii) |
Hydrogen Chloride (HCl) | Testing not required | Method 26 |
Sulfur Dioxide (SO2) | Testing not required | Testing not required |
Nitrogen Oxides (NOx) | Testing not required | Testing not required |
Lead (Pb) | Testing not required | Reference Method 29 |
Cadmium (Cd) | Testing not required | Reference Method 29 |
Mercury (Hg) | Reference Method 29 | Reference Method 29 |
Footnotes:
1 Minimum sample time is 4 hours per test run.