Figure: 30 TAC 113.2075(a)(3)(A)
Table 6. Operating Parameters to be Monitored, and Minimum Measurement and Recording Frequencies.
Operating Parameters to be Monitored
(3-hour rolling averages) |
Minimum Frequency | Control System | |||
Data Measurement | Data Recording | Dry Scrubber followed by Fabric Filter |
Wet Scrubber | Dry Scrubber followed by Fabric Filter and Wet Scrubber |
|
Maximum Operating Parameters | |||||
Charge Rate | continuous | 1 per hour | |||
Fabric Filter Inlet Temperature | continuous | 1 per minute | |||
Flue Gas Temperature | continuous | 1 per minute | |||
Minimum Operating Parameters | |||||
Secondary Chamber Temperature | continuous | 1 per minute | |||
Dioxin/furan Sorbent Flow Rate | hourly | 1 per hour | |||
HCl Sorbent Flow Rate | hourly | 1 per hour | |||
Mercury (Hg) Sorbent Flow Rate | hourly | 1 per hour | |||
Pressure Drop Across the Wet Scrubber or Horsepower or Amperage to Wet Scrubber |
continuous | 1 per minute | |||
Wet Scrubber Liquor Flow Rate | continuous | 1 per minute | |||
Wet Scrubber Liquor pH | continuous | 1 per minute |