<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 30ENVIRONMENTAL QUALITY
PART 1TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
CHAPTER 117CONTROL OF AIR POLLUTION FROM NITROGEN COMPOUNDS
SUBCHAPTER DCOMBUSTION CONTROL AT MINOR SOURCES IN OZONE NONATTAINMENT AREAS
DIVISION 1HOUSTON-GALVESTON-BRAZORIA OZONE NONATTAINMENT AREA MINOR SOURCES
RULE §117.2035Monitoring and Testing Requirements

  (5) For units equipped with CEMS or PEMS, the CEMS or PEMS must be installed and operational before testing under this subsection. Verification of operational status must, at a minimum, include completion of the initial monitor certification and the manufacturer's written requirements or recommendations for installation, operation, and calibration of the device.

  (6) Initial compliance with §117.2010 of this title for units operating with CEMS or PEMS must be demonstrated after monitor certification testing using the NOX CEMS or PEMS.

  (7) For units not operating with CEMS or PEMS, the following apply.

    (A) Retesting as specified in paragraphs (1) - (4) of this subsection is required within 60 days after any modification that could reasonably be expected to increase the NOX emission rate.

    (B) Retesting as specified in paragraphs (1) - (4) of this subsection may be conducted at the discretion of the owner or operator after any modification that could reasonably be expected to decrease the NOX emission rate, including, but not limited to, installation of post-combustion controls, low-NOX burners, low excess air operation, staged combustion (for example, overfire air), flue gas recirculation, and fuel-lean and conventional (fuel-rich) reburn.

    (C) The NOX emission rate determined by the retesting must establish a new emission factor to be used to calculate actual emissions from the date of the retesting forward. Until the date of the retesting, the previously determined emission factor must be used to calculate actual emissions for compliance with Chapter 101, Subchapter H, Division 3 of this title.

  (8) Testing must be performed in accordance with the schedule specified in §117.9200 of this title.

  (9) All test reports must be submitted to the executive director for review and approval within 60 days after completion of the testing.

(f) Emission allowances.

  (1) For sources that are subject to Chapter 101, Subchapter H, Division 3 of this title, the NOX testing and monitoring data of subsections (a) - (e) of this section, together with the level of activity, as defined in §101.350 of this title (relating to Definitions), must be used to establish the emission factor calculating actual emissions for compliance with Chapter 101, Subchapter H, Division 3 of this title.

  (2) The emission factor in subsection (e)(7) of this section or paragraph (1) of this subsection is multiplied by the unit's level of activity to determine the unit's actual emissions for compliance with Chapter 101, Subchapter H, Division 3 of this title.

(g) Run time meters. The owner or operator of any stationary diesel engine claimed exempt using the exemption of §117.2003(a)(2)(E), (H), or (I) of this title shall record the operating time with an elapsed run time meter. Any run time meter installed on or after October 1, 2001, must be non-resettable.


Source Note: The provisions of this §117.2035 adopted to be effective June 14, 2007, 32 TexReg 3206; amended to be effective March 4, 2009, 34 TexReg 1445; amended to be effective May 16, 2024, 49 TexReg 3347

Previous Page

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page