TITLE 25HEALTH SERVICES
PART 1DEPARTMENT OF STATE HEALTH SERVICES
CHAPTER 133HOSPITAL LICENSING
SUBCHAPTER IPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §133.163Spatial Requirements for New Construction

moveable cabinets and shelves shall not encroach upon the bassinet/crib clear floor space/area. The requirements of this clause are illustrated in Table 8, Diagram K of §133.169(h) of this title.

      (viii) A minimum of one isolation room shall be provided with a minimum clear floor area of 120 square feet per bassinet/crib exclusive of work counter, vestibule, sink and aisle. A minimum of 12 feet width shall be provided for the head wall for each bed. A toilet room is not required.

      (ix) A lavatory equipped for hand washing with hands-free operable controls shall be provided in each single-bed room. In rooms with multiple beds, one lavatory with hands-free operable controls for each four patient stations or fraction thereof shall be provided. These lavatories shall be located convenient to infant stations.

      (x) Each NCCU shall be served by a connecting workroom containing gowning facilities at the entrance for staff and housekeeping personnel, a work space with counter, storage facilities, a lavatory or sink equipped for hand washing with hands-free operable controls, and individual closet or lockers for personal effects of nursing personnel. One workroom may serve not more than two NCCUs.

      (xi) A storage space for infant formula shall be provided. This functional space may be outside the NCCU but shall be available for use at all times.

      (xii) A breast feeding or pump room shall be provided convenient to the unit. Provision shall be made, either within the room or conveniently located nearby, for a sink with hands-free operable controls, counter, refrigeration and freezer, storage for pump and attachments, and educational materials.

      (xiii) A room(s) shall be provided within the NCCU for parents and infants for extended private time together and the room is not considered a patient room. The room(s) shall have direct access to toilet facilities and a hand washing fixture with hands-free operable controls. The room(s) shall have a sleeping area for at least one parent, and sufficient space for the infant's bassinet/crib and equipment. The room(s) shall have electrical and medical gas outlets as specified for NCCU bassinet/cribs. This room(s) shall have direct communication with the NCCU staff.

      (xiv) Twenty square feet of equipment storage shall be provided for each patient station. The storage areas shall be out of the way of the corridor traffic.

      (xv) Charting and dictation space shall be provided for physicians and nurses.

      (xvi) A respiratory therapy work area and storage room shall be provided.

      (xvii) Blood gas lab facilities shall be immediately accessible to the NCCU.

      (xviii) A staff lounge shall include toilet facilities with a hand washing fixture with hands-free operable controls. The lounge(s) shall be located so that staff may be recalled quickly to the patient area in emergencies. Toilet facilities may be shared as long as privacy is maintained for changing areas.

      (xix) Physicians and other staff on 24-hour on-call work schedules shall be provided with sleeping rooms with access to a shower(s), toilet(s), and lavatory(ies). If on-call room(s) are not within the NCCU served, a dedicated telephone or intercom system shall connect the on-call room(s) to the NCCU.

      (xx) A waiting room/area shall be provided and contain toilet room(s) with hand washing facilities. Waiting room/area maybe shared with other waiting room/areas if conveniently located.

      (xxi) A consultation room shall be provided, if not provided elsewhere in the suite.

      (xxii) A housekeeping room shall be provided exclusively within or immediately adjacent to the NCCU. It shall not be shared with other nursing units or departments.

    (P) Infant formula facilities. Infant formula facilities shall meet the following requirements.

      (i) When infant formula is prepared on site, the infant formula preparation room shall contain a lavatory equipped for hand washing with hands-free operable controls, warming facilities, refrigerator, work counter, formula sterilizer, and storage facilities. The formula room may be located near the nurseries or at another appropriate place within the hospital. Direct access from the formula preparation room to any nursery room is prohibited.

      (ii) An infant formula clean-up room shall be provided and include a hand washing fixture with hands-free operable controls, facilities for bottle washing, a work counter, and sterilization equipment.

      (iii) When commercial infant formula is used, the separate clean-up and formula preparation rooms may be omitted. The storage and handling may be done in the nursery workroom or in another appropriate room in the hospital that is conveniently accessible at all hours.

      (iv) A refrigerated storage and warming facilities for infant formula shall be provided and be accessible for use by nursery personnel at all times.

    (Q) Service areas. The following service areas shall be provided to support an obstetrical suite unless otherwise noted.

      (i) Control station. The control station shall be located to permit direct visual surveillance of all traffic which enters the obstetrical suite.

      (ii) Office. A supervisor's office shall be provided.

      (iii) Waiting room/area. A waiting room/area shall be provided and contain toilet room(s) with hand washing facilities, public telephone(s), and drinking fountain(s).

      (iv) Scrub facilities. Two scrub stations shall be within 5 feet of the entrance to each c-section operating room and delivery room. Two scrub stations may serve two c-section operating rooms or delivery rooms if the scrub stations are located adjacent to the entrance of each c-section operating room or delivery room. Scrub facilities shall be arranged to minimize any incidental splatter on nearby personnel or supply carts. Viewing panels shall be provided for observation of c-section operating rooms and delivery rooms from the scrub area.

      (v) Sterilizing facilities. Sterilizing facilities with high speed sterilizers shall be conveniently located to serve all c-section operating rooms and delivery rooms. A work space and a hand washing fixture with hands-free operable controls shall be included. High speed autoclaves should only be used in an emergency situation (e.g. replacements unavailable for dropped instruments). Sterilization facilities would not be necessary when spare instruments are available.

      (vi) Anesthesia workroom. An anesthesia workroom shall be provided with work counter, sink with hands-free operable controls, and storage space for small style D or E medical gas cylinders and other anesthesia equipment.

      (vii) Medication station. Storage and distribution of medication may be done from a medicine preparation room, medicine alcove area or from a self-contained medicine dispensing unit but must be under visual control of nursing staff. A work counter, hand washing fixture with hands-free operable controls, refrigerator, and double-locked storage for controlled substances shall be provided. Standard cup-sinks provided in many self-contained units are not adequate for hand washing. The medication station may be shared with the clean work room.

      (viii) Nourishment station. The nourishment station shall contain sink with hands-free operable controls, work counter, self-dispensing ice machine, refrigerator, cabinets, and not located in the clean work room. Space shall be included for temporary holding of unused or soiled dietary trays. A nourishment station is not required in the nursery suite.

      (ix) General storage room(s). A minimum of 50 square feet per operating room is required for general storage space(s). The storage space is exclusive of soiled holding, sterile supplies, clean storage, drug storage, locker rooms. In addition to general storage, equipment storage shall be provided for labor, LDR and LDRP rooms.

      (x) Emergency storage. Equipment used for emergencies shall be stored in a room or alcove under direct visual control of the nursing staff.

      (xi) Storage alcove. The alcove provided for stretcher storage, portable X-ray equipment, warming devices, auxiliary lamps, etc. shall be located out of direct line of traffic.

      (xii) Obstetrical suite staff clothing change rooms. Appropriately sized areas shall be provided for male and female personnel working within the obstetrical suite. These areas shall contain lockers, showers, toilets, hand washing fixtures with hands-free operable controls, and space to change into scrub suits and boots. Separate locker/changing rooms shall be provided for male and female staff. The shower and toilet room(s) may be unisex. These areas shall be arranged to provide a traffic pattern so that personnel entering from outside the obstetrical suite can shower, change, and move directly into the restricted areas of the obstetrical suite.

Cont'd...