<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 25HEALTH SERVICES
PART 1DEPARTMENT OF STATE HEALTH SERVICES
CHAPTER 133HOSPITAL LICENSING
SUBCHAPTER IPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §133.163Spatial Requirements for New Construction

      (ii) Ceilings in the soiled workroom shall be monolithic type as required by §133.162(d)(2)(B)(vi)(III) of this title.

  (3) Mechanical Requirements. Mechanical requirements shall be in accordance with §133.162(d)(3) of this title and this paragraph. Room recirculating units shall not be used.

  (4) Piping systems and plumbing fixtures. Piping systems and plumbing fixtures shall be in accordance with §133.162(d)(4) of this title.

  (5) Electrical requirements. Electrical requirements shall be in accordance with §133.162(d)(5) of this title and this paragraph.

    (A) General.

      (i) Receptacles at each bed location in a CCU(s) shall be served by two branch circuits, one or more from the critical branch panel of the emergency electrical system and one or more from the normal system. One critical branch circuit shall serve only one bed location. All branch circuits from the normal system shall be from a single panelboard. All branch circuits from the emergency electrical system shall be from a single panelboard.

      (ii) A minimum of seven hospital grade duplex outlets shall be conveniently located at the head of each bed, crib or bassinet. At least three of these duplex outlets shall be on the critical branch of the emergency electrical system.

      (iii) Hospital grade receptacles in the PCCU shall be tamper-resistant or provided with GFCIs.

    (B) Nurses calling systems. The nurse call system shall be in accordance with §133.162(d)(5)(L) and Table 7 of §133.169(g) of this title.

(e) Dietary suite.

  (1) Architectural requirements.

    (A) General. Construction, equipment, and installation shall comply with Chapter 228 of this title (relating to Retail Food).

    (B) Food service facilities. Food services shall be provided by an on-site food preparation system or an off-site food service system or a combination of the two. The following minimum functional elements shall be provided on site regardless of the type of dietary services.

      (i) Dining area. Provide dining space(s) for ambulatory patients, staff, and visitors. These spaces shall be separate from the food preparation and distribution areas.

      (ii) Receiving area. This receiving area shall have direct access to the outside for incoming dietary supplies or off-site food preparation service and shall be separate from the general receiving area. The receiving area shall contain a control station and an area for breakout for loading, unloading, uncrating, and weighing supplies. The entrance area to the receiving area shall be covered from the weather.

      (iii) Storage spaces. Storage spaces shall be convenient to receiving area and food preparation area and shall be located to exclude traffic through the food preparation area. Regardless of the type of food services provided, the facility shall provide storage of food for emergency use for a minimum of four calendar days.

        (I) Storage space(s). Storage space(s) shall be provided for bulk, refrigerated, and frozen foods.

        (II) Cleaning supply storage. This room or closet shall be used to store nonfood items that might contaminate edibles. This storage area may be combined with the housekeeping room.

      (iv) Food preparation area. Counter space shall be provided for food prep work, equipment, and an area to assemble trays for distribution for patient meals.

      (v) Ice-making equipment. Ice-making equipment shall be provided for both drinks and food products (self-dispensing equipment) and for general use (storage-bin type equipment).

      (vi) Hand washing. Hand washing fixtures with hands-free operable controls shall be conveniently located at all food preparation areas and serving areas.

      (vii) Food service carts. When a cart distribution system is provided, space shall be provided for storage, loading, distribution, receiving, and sanitizing of the food service carts. The cart traffic shall be designed to eliminate any danger of cross-circulation between outgoing food carts and incoming soiled carts, and the cleaning and sanitizing process. Cart circulation shall not be through food processing areas.

      (viii) Ware washing room. A ware washing room equipped with commercial type dishwasher equipment shall be located separate from the food preparation and serving areas. Space shall be provided for receiving, scraping, sorting, and stacking soiled tableware and for transferring clean tableware to the using areas. Hand washing facilities with hands-free operable controls shall be located within the soiled dish wash area. A physical separation to prevent cross-traffic between "dirty side" and "clean side" of the dish wash areas shall be provided.

      (ix) Pot washing facilities. A three compartmented sink of adequate size for intended use shall be provided convenient to the food preparation area. Supplemental heat for hot water to clean pots and pans shall be by booster heater or by steam jet.

      (x) Waste storage room. A food waste storage room shall be conveniently located to the food preparation and ware washing areas but not within the food preparation area. It shall have direct access to the hospital's waste collection and disposal facilities.

      (xi) Sanitizing facilities. Storage areas and sanitizing facilities for garbage or refuse cans, carts, and mobile tray conveyors shall be provided. All containers for trash storage shall have tight-fitting lids.

      (xii) Housekeeping room. A housekeeping room shall be provided for the exclusive use of the dietary department. Where hot water or steam is used for general cleaning, additional space within the room shall be provided for the storage of hoses and nozzles.

      (xiii) Office spaces. An office shall be provided for the use of the food service manager or the dietary service manager. In smaller facilities, a designated alcove may be located in an area that is part of the food preparation area.

      (xiv) Toilets and locker spaces. A toilet room(s) with a hand washing fixture(s) with hands-free operable controls shall be provided for the exclusive use of the dietary staff. Toilet room(s) shall not open directly into the food preparation areas, but must be in close proximity to them. For larger facilities, a locker room or space for lockers shall be provided for staff belongings.

    (C) Additional service areas, rooms and facilities. When an on-site food preparation system is used, in addition to the items required in subparagraph (B) of this paragraph, the following service areas, rooms and facilities shall be provided.

      (i) Food preparation facilities. When food preparation systems are provided, there shall be space and equipment for preparing, cooking, and baking.

      (ii) Tray assembly line. A patient tray assembly and distribution area shall be located within close proximity to the food preparation and distribution areas.

      (iii) Food storage. When food is prepared on site, the storage room shall be adequate to accommodate food for a seven calendar day menu cycle.

      (iv) Additional storage room(s). An additional room(s) shall be provided for the storage of cooking wares, extra trays, flatware, plastic and paper products, and portable equipment.

      (v) Drying storage area. Provisions shall be made for drying and storage of pots and pans from the pot washing room.

    (D) Equipment. Equipment for use in the dietary suite shall meet the following requirements.

      (i) Mechanical devices shall be heavy duty, suitable for the use intended, and easily cleaned. Where equipment is movable, provide heavy duty locking casters. Equipment with fixed utility connections shall not be equipped with casters.

      (ii) Floor, wall, and top panels of walk-in coolers, refrigerators, and freezers shall be insulated. Coolers and refrigerators shall be capable of maintaining a temperature down to freezing. Freezers shall be capable of maintaining a temperature of 20 degrees below 0 degrees Fahrenheit. Coolers, refrigerators, and freezers shall be thermostatically controlled to maintain desired temperature settings in increments of two degrees or less. Interior temperatures shall be indicated digitally and visible from the exterior. Controls shall include audible and visible high and low-temperature alarm. The time of alarm shall be automatically recorded.

      (iii) Walk-in units may be lockable from the outside but must have a release mechanism for exit from inside at all times. The interior shall be lighted. All shelving shall be corrosion-resistant, easily cleaned, and constructed and anchored to support a loading of at least 100 pounds per linear foot.