TITLE 25HEALTH SERVICES
PART 1DEPARTMENT OF STATE HEALTH SERVICES
CHAPTER 133HOSPITAL LICENSING
SUBCHAPTER IPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §133.163Spatial Requirements for New Construction

      (iv) All cooking equipment shall be equipped with automatic shutoff devices to prevent excessive heat buildup.

    (E) Vending services. When vending machines are provided, a dedicated room or an alcove shall be located so that access is available at all times.

  (2) Details and finishes. Details and finishes shall be in accordance with §133.162(d)(2) of this title and this paragraph.

    (A) Details.

      (i) Food storage shelves shall not be less than four inches above the finished floor and the space below the bottom shelf shall be closed in and sealed tight for ease of cleaning.

      (ii) Operable windows and doors not equipped with automatic closing devices shall be equipped with insect screens.

      (iii) Food processing areas in the central dietary kitchen shall have ceiling heights not less than nine feet. Ceiling-mounted equipment shall be supported from rigid structures located above the finished ceiling.

      (iv) Mirrors shall not be installed at hand washing fixtures in the food preparation areas.

    (B) Finishes.

      (i) Floors in areas used for food preparation, food assembly, soiled and clean ware cleaning shall be water-resistant and grease-proof. Floor surfaces, including tile joints, shall be resistant to food acids.

      (ii) Wall bases in food preparation, food assembly, soiled and clean ware cleaning and other areas which are frequently subject to wet cleaning methods shall be made integral and coved with the floor, tightly sealed to the wall, constructed without voids that can harbor insects, retain dirt particles, and be impervious to water.

      (iii) In the dietary and food preparation areas, the wall construction, finishes, and trim, including the joints between the walls and the floors, shall be free of voids, cracks, and crevices.

      (iv) The ceiling in food preparation and food assembly areas shall be washable as required by §133.162(d)(2)(B)(vi)(II) of this title.

      (v) The ceiling in the soiled and clean ware cleaning area shall be of the monolithic type as required by §133.162(d)(2)(B)(vi)(III) of this title.

  (3) Mechanical Requirements. Mechanical requirements shall be in accordance with §133.162(d)(3) of this title and this paragraph.

    (A) Exhaust hoods handling grease-laden vapors in food preparation centers shall comply with National Fire Protection Association 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, 2001 edition. All hoods over cooking ranges shall be equipped with grease filters, fire extinguishing systems, and heat-actuated fan controls. Clean out openings shall be provided every 20 feet and at any changes in direction in the horizontal exhaust duct systems serving these hoods. (Horizontal runs of ducts serving range hoods should be kept to a minimum.)

    (B) When air change standards in Table 3 of §133.169(c) of this title do not provide sufficient air for proper operation of exhaust hoods (when in use), supplementary filtered make-up air shall be provided in these rooms to maintain the required airflow direction and exhaust velocity. Make-up systems for hoods shall be arranged to minimize "short circuiting" of air and to avoid reduction in air velocity at the point of contaminant capture.

    (C) Air handling units serving the dietary suite shall be equipped with filters having efficiencies equal to, or greater than specified in Table 4 of §133.169(d) of this title.

  (4) Piping systems and plumbing fixtures. Piping systems and plumbing fixtures shall be in accordance with §133.162(d)(4) of this title and this paragraph.

    (A) The kitchen grease traps shall be located and arranged to permit easy access without the need to enter food preparation or storage areas. Grease traps shall be of capacity required and shall be accessible from outside of the building without need to interrupt any services.

    (B) Grease traps or grease interceptors shall be located outside the food preparation area and shall comply with the requirements in the National Association of Plumbing-Heating-Cooling Contractors (PHCC), National Standard Plumbing Code, 2000 edition. This publication may be obtained from the National Association of Plumbing-Heating-Cooling Contractors, 180 South Washington Street, Falls Church, VA 22046; telephone (703) 237-8100.

    (C) The material used for plumbing fixtures shall be nonabsorptive and acid-resistant.

    (D) Water spouts used at lavatories and sinks shall have clearances adequate to avoid contaminating utensils and containers.

    (E) Hand washing fixtures used by food handlers shall be trimmed with valves that can be operated without hands. Single lever or wrist blade devices may be used. Blade handles used for this purpose shall not be less than four inches in length.

    (F) Drainage and waste piping shall not be installed within the ceiling or installed in an exposed location in food preparation centers, food serving facilities and food storage areas unless precautions are taken to protect the space below from leakage and condensation from necessary overhead piping. Any required secondary protection shall be labeled, "code required secondary drain system" every 20 feet in a highly visible print or label.

    (G) No plumbing lines may be exposed overhead or on walls where possible leaks would create a potential for food contamination.

  (5) Electrical requirements. Electrical requirements shall be in accordance with §133.162(d)(5) of this title and this paragraph.

    (A) Exhaust hoods shall have an indicator light indicating that the exhaust fan is in operation.

    (B) The electrical circuit(s) to equipment in wet areas shall be provided with five milliampere GFCI.

(f) Emergency suite. This subsection applies to all hospitals (general or special) included under the hospital license, including those licensed as a multiple-location hospital.

  (1) Architectural requirements.

    (A) Emergency treatment area.

      (i) Emergency treatment room. As a minimum requirement, all hospitals shall provide at least one emergency treatment room and facilities to handle emergencies. The room(s) and facilities shall meet the following requirements.

        (I) The emergency treatment room for a single patient shall have a minimum clear area of 120 square feet clear floor area exclusive of fixed and movable cabinets and shelves. The minimum clear room dimension exclusive of fixed cabinets and built-in shelves shall be 10 feet. The emergency treatment room shall contain cabinets, medication storage, work counter, examination light, and a hand washing fixture with hands-free operable controls.

        (II) When a multiple-bed emergency treatment room is provided, the clearance between the side of a bed/gurney and a wall/partition shall be a minimum of four feet. The clearance between the sides of beds/gurneys shall be a minimum of six feet. The minimum distance at the foot of the bed/gurney shall not be less than seven feet for single load area/room or ten feet for double load area/room. Four feet of the passage space at the foot of the bed may be shared between two beds/gurneys. The multiple-bed emergency treatment room shall contain cabinets, medication storage, work counter, examination light, and a hand washing fixture with hands-free operable controls. The fixed and movable cabinets and shelves shall not encroach upon the bed/gurney clear floor space/area. The requirements of this subclause are illustrated in Table 8, Diagram C of §133.169(h) of this title.

        (III) One hand washing fixture with hands-free operable controls shall be provided for each bed/gurney location. One hand washing fixture may serve two beds/gurneys if distributed appropriately between the two.

        (IV) Storage space shall be provided within the room or suite and be under staff control for general medical-surgical emergency supplies and medications. Adequate space shall be provided for emergency equipment such as emergency treatment trays, ventilator, defibrillator, splints, cardiac monitor, etc.

        (V) Locked storage space shall be provided for drugs and an area for preparation of medication with a work counter, refrigerator, and hand washing fixture with hands-free operable controls.

        (VI) An alcove shall be provided for stretcher and wheelchair storage. The storage shall be located out of the line of traffic.

        (VII) Patient toilet room(s) shall be provided and shall be convenient to treatment rooms, examination rooms, and holding rooms, and a hand washing fixture with hands-free operable controls.