TITLE 25HEALTH SERVICES
PART 1DEPARTMENT OF STATE HEALTH SERVICES
CHAPTER 133HOSPITAL LICENSING
SUBCHAPTER IPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §133.163Spatial Requirements for New Construction

        (VIII) In a special hospital, comprehensive medical rehabilitation hospital, or pediatric and adolescent hospital, the emergency treatment room and facilities may be located anywhere in the hospital.

      (ii) Additional requirements for a general hospital. Except for comprehensive medical rehabilitation hospitals and pediatric and adolescent hospitals that generally provide care that is not administered for or in expectation of compensation, a general hospital shall also meet the following requirements.

        (I) Emergency entry signage. An emergency sign shall be provided at the entry from the public road(s) or street(s) serving the site. The emergency sign at the entry to the site shall be illuminated and connected to the emergency essential electrical system. Additional sign(s) on-site may be required to direct patients to the emergency treatment area entrance when the emergency treatment area is not visible from the site entry. The letters on the entry sign shall be red with a contrasting background, all capitalized, at least eight inches in height, and an arrow indicating direction.

        (II) Entrances. Separate ambulance and pedestrian entrances at grade level shall be well-illuminated, identified by signs, and protected from inclement weather. The ambulance entry shall have a drive under canopy for protection from inclement weather. The emergency access to permit discharge of patients from automobile and ambulances shall be paved. Parking shall be provided near and convenient to the pedestrian entrance.

        (III) Control station. A registration, reception, discharge or control station shall be located to permit staff observation and control of access to treatment room(s), pedestrian and ambulance entrances, and public waiting area(s). When a dedicated triage space is provided, it shall include a counter with a hand washing fixture with hands-free operable controls.

        (IV) Public waiting room. A public waiting room shall be provided.

        (V) Public facilities. Toilet facilities, public telephone(s), and drinking fountain(s) shall be provided for the exclusive use of the waiting room.

        (VI) Diagnostic radiographic (X-ray) room. Imaging facilities for diagnostic services shall be readily available to the emergency suite. If a separate radiographic (X-ray) room is installed within the emergency suite, it shall comply with the requirements in subsection (l)(1)(A) of this section. When the diagnostic X-ray room is exclusively used for the emergency treatment area, the dressing rooms may be omitted.

        (VII) Laboratory unit. Laboratory services shall be made available to the emergency suite. If a separate laboratory workroom is installed within the emergency suite, it shall comply with the requirements in subsection (n)(1)(C)(i) of this section. All laboratory services provided on site or by contractual arrangement shall comply with §133.41(h) of this title (relating to Hospital Functions and Services).

        (VIII) Medical staff work area and charting area(s). A medical staff work area and charting area(s) shall be provided. The area may be combined with the reception and control area.

        (IX) Clean storage room. A clean storage room shall be provided for clean supplies, linens and medications as needed. A hand washing fixture shall be provided with hands-free operable controls.

        (X) Soiled workroom. The workroom shall contain a work counter, a clinical sink or equivalent flushing type fixture, hand washing fixture with hands-free operable controls, waste receptacles, and soiled linen receptacles.

        (XI) Housekeeping room. The housekeeping room shall contain a floor receptor or service sink, storage space for housekeeping supplies and equipment, and be located within the suite. When automatic film processors are used, a receptacle of adequate size with hot and cold water for cleaning the processor racks shall be provided.

        (XII) Staff toilets. Toilets may be outside the suite but shall be convenient for staff use and include hand washing fixtures with hands-free operable controls. When a department has four or more treatment or examination rooms, toilet facilities shall be in the suite.

      (iii) Other rooms. If a hospital provides the following rooms, the rooms shall meet these requirements.

        (I) Examination room. When provided, the examination room for a single patient shall have a minimum clear area of 100 square feet clear floor area exclusive of fixed and movable cabinets and shelves. The minimum clear room dimension exclusive of fixed cabinets and built-in shelves shall be 9 feet. The examination room shall contain cabinets, medication storage, work counter, examination light, and a hand washing fixture with hands-free operable controls.

        (II) Multi-bed examination room. In a multiple-bed examination room the clearance between the side of the bed/gurney and a wall/partition shall be a minimum of three feet. The clearance between sides of the beds/gurneys shall be a minimum of six feet. The minimum distance at the foot of the bed/gurney shall not be less than seven feet for single load area/room or ten feet for double load area/room. Four feet of the passage space at the foot of the bed may be shared between two beds/gurneys. The multiple-bed examination room shall contain cabinets, work counters, and a hand washing fixture with hands-free operable controls. One hand washing fixture shall be provided for every four beds/gurneys or fraction thereof. Fixtures shall be uniformly distributed. The fixed and moveable cabinets and shelves shall not encroach upon the bed/gurney clear floor space/area.

        (III) Isolation room. The need for an airborne infection isolation room in the emergency suite shall be determined by the hospital and the infection risk assessment. When the hospital provides treatment rooms to perform procedures on persons who are known or suspected of having an airborne infectious disease, these procedures shall be performed in a designated treatment room meeting airborne infection isolation ventilation requirements. The isolation room shall have functional space in accordance with clause (i)(I) of this subparagraph, and meet the ventilation requirements contained in Table 3 of §133.169(c) of this title.

        (IV) Secured holding room. When provided, this room shall be constructed to allow for security, patient and staff safety, patient observation, and sound mitigation. The secure holding room shall have a minimum clear area of 100 square feet clear floor area exclusive of fixed cabinets. The minimum clear room dimension exclusive of fixed cabinets shall be 10 feet.

        (V) Orthopedic and cast room. The room(s) may be in separate room(s) or in the trauma room. The room(s) shall contain a work counter, storage for splints and orthopedic supplies, traction hooks, medication storage, examination light, and a hand washing fixture with hands-free operable controls. When a cast room is provided it shall be equipped with hand washing facilities, plaster sink, storage, and other provisions required for cast procedures.

        (VI) Film processing room. When a radiographic (X-ray) room is provided, a darkroom for processing film shall be provided unless the processing equipment does not require a darkroom for loading and transfer. When daylight processing is used, the darkroom may be minimal for emergency and special uses. Film processing shall be located convenient to the darkroom.

        (VII) Decontamination room. A decontamination room shall have an exterior entry point and as far as practical from any other entry point to the emergency treatment area. The internal door from the decontamination room shall open directly to the corridor into the emergency treatment area. The door shall swing into the room and be lockable against ingress from the corridor. The room shall be a minimum of 80 square feet of clear floor area with a hand washing fixture with hands-free operable controls.

    (B) Holding or observation room/area.

      (i) When a holding or observation room/area is provided within or adjacent to the emergency suite, it shall comply with the following.

        (I) A single holding/observation room shall have a minimum clear area of 100 square feet exclusive of fixed and movable cabinets and shelves. The holding/observation room shall contain a work counter and hand washing fixture with hands-free operable controls.

        (II) The single holding/observation room shall be near the nurses station and near a patient toilet room which contains a hand washing fixture with hands-free operable controls.

        (III) In a multiple-bed holding/observation room/area, the clearance between the side of the bed/gurney and a wall/partition shall be a minimum of three feet. The clearance between sides of the beds/gurneys shall be a minimum of six feet. The minimum distance at the foot of the bed/gurney shall not be less than seven feet for single load area/room or ten feet for double load area/room. Four feet of the passage space at the foot of the bed may be shared between two beds/gurneys. The multiple-bed holding/observation room/area shall contain cabinets, work counters, and a hand washing fixture with hands-free operable controls. One hand washing fixture shall be provided Cont'd...