(G) Sprinkler system valve supervisory switches shall be installed in accordance with the requirements of NFPA 72, §6.8.5.5. (H) A fire alarm signal notification which complies with NFPA 101, §9.6.3, shall be provided to alert occupants of fire or other emergency. (I) Audible alarm indicating devices shall be installed in accordance with the requirements of NFPA 101, §20.3.4, and NFPA 72, §7.4. (J) Visual fire alarm indicating devices which comply in accordance with the requirements of NFPA 72, §7.5, shall be provided. (K) Devices for transmitting alarm for alerting the local fire brigade or municipal fire department of fire or other emergency shall be provided. The devices shall be listed for the fire alarm service by a nationally recognized laboratory, and be installed in accordance with such listing and the requirements of NFPA 72. (L) Wiring for fire alarm detection circuits and fire alarm notification circuits shall comply with requirements of NFPA 70, Article 760. |