<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 30ENVIRONMENTAL QUALITY
PART 1TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
CHAPTER 290PUBLIC DRINKING WATER
SUBCHAPTER DRULES AND REGULATIONS FOR PUBLIC WATER SYSTEMS
RULE §290.42Water Treatment

  (6) Where anhydrous ammonia feed equipment is utilized, it must be housed in a separate enclosure equipped with both high and low level ventilation to the outside atmosphere. The enclosure must be provided with forced air ventilation which includes: screened and louvered floor level and high level vents; a fan which is located at and draws air in through the floor vent and discharges through the top vent; and a fan switch located outside the enclosure. Alternately, systems may install negative pressure ventilation as long as the facilities also have gas containment and treatment as prescribed by the current IFC.

  (7) Chloramine disinfection shall be performed in a manner which assures that the proper chlorine to ammonia (as nitrogen) ratio is achieved in order to maintain a monochloramine residual and limit nitrification.

    (A) The order of chlorine and ammonia injection must be accomplished in a manner which allows inactivation of viruses and oxidation of cyanide.

      (i) When chlorine is injected upstream of any other disinfectant, the ammonia injection point must be downstream of the chlorine injection point.

      (ii) When chlorine and ammonia are added to distribution water that has a chloramine residual, ammonia should be added first.

      (iii) When chlorine and ammonia are added to distribution water that has a free chlorine residual, chlorine should be added first.

    (B) Mixing shall be provided to disperse chemicals.

    (C) Sampling taps must be provided at locations that allow for chlorine and ammonia to be added to the water to form monochloramine as the primary chloramine species. These locations must be listed in the system's monitoring plan as described in §290.121 of this title (relating to Monitoring Plans). Sample taps must be provided as follows:

      (i) upstream of the chlorine or ammonia chemical injection point, whichever is furthest upstream;

      (ii) between the addition of the chloramine chemicals at chloramination facilities submitted for plan review after December 31, 2015. For these facilities, an installation without this sample tap may be approved if an acceptable technical reason is described in the plan review documents. Technical reasons, such as disinfection byproduct control, must be supported by bench scale sampling results. Other technical reasons, such as membrane integrity, must be supported by documentation; and

      (iii) at a point after mixing to be able to measure fully-formed monochloramine levels.

    (D) When using chloramines, the feed and storage must be designed as described in subsection (f) of this section, regardless of water source.

    (E) When using chloramines, the public water systems shall provide equipment for making at least the following determinations for purposes of complying with the requirements in §290.110 of this title:

      (i) free ammonia (as nitrogen);

      (ii) monochloramine;

      (iii) total chlorine;

      (iv) free chlorine; and

      (v) nitrite and nitrate (both as nitrogen). The public water systems must either obtain equipment for measuring nitrite and nitrate or identify an accredited laboratory that can perform nitrite and nitrate analysis and can provide results to the public water systems within 48 hours of sample delivery.

(f) Water treatment plant chemical storage and feed facilities.

  (1) Chemical storage facilities shall be designed to ensure a reliable supply of chemicals to the feeders, minimize the possibility and impact of accidental spills, and facilitate good housekeeping.

    (A) Bulk storage facilities at the plant shall be adequate to store at least a 15-day supply of all chemicals needed to comply with minimum treatment technique and maximum contaminant level (MCL) requirements. The capacity of these bulk storage facilities shall be based on the design capacity of the treatment plant. However, the executive director may require a larger stock of chemicals based on local resupply ability.

    (B) Day tanks shall be provided to minimize the possibility of severely overfeeding liquid chemicals from bulk storage facilities. Day tanks will not be required if adequate process control instrumentation and procedures are employed to prevent chemical overfeed incidents.

    (C) Every chemical bulk storage facility and day tank shall have a label that identifies the facility's or tank's contents and a device that indicates the amount of chemical remaining in the facility or tank.

    (D) Dry chemicals shall be stored off the floor in a dry room that is located above ground and protected against flooding or wetting from floors, walls, and ceilings.

    (E) Bulk storage facilities and day tanks must be designed to minimize the possibility of leaks and spills.

      (i) The materials used to construct bulk storage and day tanks must be compatible with the chemicals being stored and resistant to corrosion.

      (ii) Except as provided in this clause, adequate containment facilities shall be provided for all liquid chemical storage tanks.

        (I) Containment facilities for a single container or for multiple interconnected containers must be large enough to hold the maximum amount of chemical that can be stored with a minimum freeboard of six vertical inches or to hold 110% of the total volume of the container(s), whichever is less.

        (II) Common containment for multiple containers that are not interconnected must be large enough to hold the volume of the largest container with a minimum freeboard of six vertical inches or to hold 110% of the total volume of the container(s), whichever is less.

        (III) The materials used to construct containment structures must be compatible with the chemicals stored in the tanks.

        (IV) Incompatible chemicals shall not be stored within the same containment structure.

        (V) No containment facilities are required for hypochlorite solution containers that have a capacity of 55 gallons or less.

        (VI) On a site-specific basis, the executive director may approve the use of double-walled tanks in lieu of separate containment facilities.

    (F) Chemical transfer pumps and control systems must be designed to minimize the possibility of leaks and spills.

    (G) Piping, pumps, and valves used for chemical storage and transfer must be compatible with the chemical being fed.

  (2) Chemical feed and metering facilities shall be designed so that chemicals shall be applied in a manner which will maximize reliability, facilitate maintenance, and ensure optimal finished water quality.

    (A) Each chemical feeder that is needed to comply with a treatment technique or MCL requirement shall have a standby or reserve unit. Common standby feeders are permissible, but generally, more than one standby feeder must be provided due to the incompatibility of chemicals or the state in which they are being fed (solid, liquid, or gas).

    (B) Chemical feed equipment shall be sized to provide proper dosage under all operating conditions.

      (i) Devices designed for determining the chemical feed rate shall be provided for all chemical feeders.

      (ii) The capacity of the chemical feeders shall be such that accurate control of the dosage can be achieved at the full range of feed rates expected to occur at the facility.

      (iii) Chemical feeders shall be provided with tanks for chemical dissolution when applicable.

    (C) Chemical feeders, valves, and piping must be compatible with the chemical being fed.

    (D) Chemical feed systems shall be designed to minimize the possibility of leaks and spills and provide protection against backpressure and siphoning.

    (E) If enclosed feed lines are used, they shall be designed and installed so as to prevent clogging and be easily maintained.

    (F) Dry chemical feeders shall be located in a separate room that is provided with facilities for dust control.

    (G) Coagulant feed systems shall be designed so that coagulants are applied to the water prior to or within the mixing basins or chambers so as to permit their complete mixing with the water.

      (i) Coagulant feed points shall be located downstream of the raw water sampling tap.

      (ii) Coagulants shall be applied continuously during treatment plant operation.

    (H) Chlorine feed units, ammonia feed units, and storage facilities shall be separated by solid, sealed walls.

Cont'd...

Next Page Previous Page

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page