(d) Other tank system repairs and ancillary equipment
repairs.
(1) Repairs to secondary containment areas of tanks
and piping used for interstitial monitoring and to containment sumps
used for interstitial monitoring of piping must have the secondary
containment tested for tightness according to the manufacturer's instructions,
a code of practice developed by a nationally recognized association,
or independent testing laboratory within 30 days following the date
of completion of the repair. All other repairs to tanks and piping
must be tightness tested in accordance with §334.50(b)(2)(A)(ii)(I)
and (d)(1)(A) of this title within 30 days following the date of completion
of the repair.
(2) Within 30 days following any repair to spill or
overfill prevention equipment, the repaired spill or overfill prevention
equipment must be tested or inspected, as appropriate, in accordance
with §334.48(g) of this title (relating to General Operating
and Management Requirements) to ensure it is operating properly.
(e) Records for repairs and relining.
(1) Owners and operators shall maintain the repair
and relining records required in this subsection in accordance with
the requirements in §334.10(b) of this title (relating to Reporting
and Recordkeeping).
(2) Owners and operators shall maintain records adequate
to demonstrate compliance with the applicable repairs and relining
requirements in this section, and in accordance with the following
minimum requirements.
(A) General information related to the repairs or relining
shall be maintained for the remaining operational life of the UST
system, including:
(i) date and description of the repairs or relining;
(ii) names, addresses, and telephone numbers of the
persons who conducted the repairs or relining; and
(iii) copies of all related construction notification,
registration, and certification documents filed with the agency.
(B) Results of all inspections, tests, and maintenance
activities required in this section shall be maintained for at least
five years.
(C) Materials specifications, warranty information,
recommended test procedures, and inspection and maintenance schedules
applicable to the relining of any tank shall be maintained for the
remaining operational life of the UST system.
|
Source Note: The provisions of this §334.52 adopted to be effective September 29, 1989, 14 TexReg 4714; amended to be effective November 23, 2000, 25 TexReg 11442; amended to be effective May 31, 2018, 43 TexReg 3390 |