<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 26HEALTH AND HUMAN SERVICES
PART 1HEALTH AND HUMAN SERVICES COMMISSION
CHAPTER 510PRIVATE PSYCHIATRIC HOSPITALS AND CRISIS STABILIZATION UNITS
SUBCHAPTER GPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §510.122New Construction Requirements

      (v) Sterilizing equipment. All sterilizing equipment shall be designed and installed to prevent not only the contamination of the water supply but also the entrance of contaminating materials into the sterilizing units.

      (vi) Hose attachment. No hose shall be affixed to any faucet if the end of the hose can become submerged in contaminated liquid unless the faucet is equipped with an approved, properly installed vacuum-breaker.

      (vii) Bedpan washers and sterilizers. Bedpan washers and sterilizers shall be designed and installed so that both hot and cold water inlets shall be protected against back-siphonage at maximum water level.

      (viii) Flood level rim clearance. The water supply spout for lavatories and sinks required in patient care areas shall be mounted so that its discharge point is a minimum of five inches above the rim of the fixture.

      (ix) Floor drains or floor sinks. Where floor drains or floor sinks are installed, they shall be of a type that can be easily cleaned by removal of the cover. Removable stainless steel mesh shall be provided in addition to grilled drain cover to prevent entry of large particles of waste which might cause stoppages.

      (x) Under counter piping. Under counter piping and above floor drains shall be arranged (raised) so as not to interfere with cleaning of floor below the equipment.

      (xi) Ice machines. All ice making machines shall be of the self-dispensing type, unless otherwise specified.

  (5) General electrical requirements. This paragraph contains common electrical requirements. The facility shall comply with the requirements of this paragraph and with any specific electrical requirements for the particular unit or suite of the facility in accordance with §134.123 of this title. Electrical systems shall comply with NFPA 99, Chapter 3.

    (A) Electrical installations. All new electrical material and equipment, including conductors, controls, and signaling devices, shall be installed in compliance with applicable sections of the National Fire Protection Association 70, National Electrical Code, 1999 edition (NFPA 70), and NFPA 99 and as necessary to provide a complete electrical system. Electrical systems and components shall be listed by nationally recognized listing agencies as complying with available standards and shall be installed in accordance with the listings and manufacturers' instructions.

      (i) All fixtures, switches, sockets, and other pieces of apparatus shall be maintained in a safe and working condition.

      (ii) Extension cords and cables shall not be used for permanent wiring.

      (iii) All electrical heating devices shall be equipped with a pilot light to indicate when the device is in service, unless equipped with a temperature limiting device integral with the heater.

      (iv) All equipment, fixtures, and appliances shall be properly grounded in accordance with NFPA 70.

      (v) Under-counter receptacles and conduits shall be arranged (raised) to not interfere with cleaning of floor below the equipment.

    (B) Installation testing and certification.

      (i) Installation testing. The electrical installations, including alarm, nurses calling system and communication systems, shall be tested to demonstrate that equipment installation and operation is appropriate and functional.

        (I) Grounding continuity shall be tested as described in NFPA 99 for new or existing work.

        (II) A written record of performance tests on special electrical systems and equipment shall show compliance with applicable codes and standards.

      (ii) Installation certification. Certifications in affidavit form signed by a registered electrical engineer attesting that the electrical service, electrical equipment, and electrical appliances have been installed in compliance with the approved plans and/or applicable standards, shall be submitted to the department when requested.

    (C) Electrical safeguards. Shielded isolation transformers, voltage regulators, filters, surge suppressors, and other safeguards shall be provided as required where power line disturbances are likely to affect fire alarm components, data processing, equipment used for treatment, and automated laboratory diagnostic equipment.

    (D) Services and switchboards. Main switchboards shall be located in separate rooms, separated from adjacent areas with one-hour fire rated enclosures containing only electrical switchgear and distribution panels and shall be accessible to authorized persons only. These rooms shall be ventilated to provide an environment free of corrosive or explosive fumes and gases, or any flammable and combustible materials. Switchboards shall be located convenient for use and readily accessible for maintenance as required by NFPA 70, Article 384. Overload protective devices shall operate properly in ambient temperatures.

    (E) Panelboards. Panelboards serving normal lighting and appliance circuits shall be located on the same floor as the circuits they serve. Panelboards serving critical branch emergency circuits may serve three floors, the floor where the panelboard is located, the floor above and the floor below. Panelboards serving life safety branch circuits may serve three floors, the floor where the panelboard is located, and the floors above and below.

      (i) Circuiting shall minimize the number of receptacles on a single branch circuit, in order to limit the effects of a branch circuit outage, caused by one faulted device. Any life-support equipment on that circuit would be lost.

      (ii) Loading of branch circuits is limited by NFPA 70, Articles 210, 220, and 384.

    (F) Wiring. All conductors for controls, equipment, lighting and power operating at 100 volts or higher shall be installed in accordance with the requirements of NFPA 70, Article 517. All surface mounted wiring operating at less than 100 volts shall be protected from mechanical injury with metal raceways to a height of seven feet above the floor. Conduits and cables shall be supported in accordance with NFPA 70, Article 300.

    (G) Lighting.

      (i) Lighting intensity for staff and patient needs shall comply with Chapter 17, Institution and Public Building Lighting, Health Care Facilities, of the Illuminating Engineering Society of North America (IES) Lighting Handbook, published by the IES, 345 East 47th Street, N.Y., N.Y. 10017.

        (I) Consideration should be given to controlling intensity and wavelength to prevent harm to the patient's eyes (i.e., cataracts due to ultraviolet light).

        (II) Approaches to buildings and parking lots, and all spaces within buildings shall have fixtures that can be illuminated as necessary. All rooms including storerooms, electrical and mechanical equipment rooms, and all attics shall have sufficient artificial lighting so that all parts of these spaces shall be clearly visible.

        (III) Consideration should be given to the special needs of the elderly. Excessive contrast in lighting levels that makes effective sight adaptation difficult shall be minimized.

      (ii) Means of egress and exit sign lighting intensity shall comply with NFPA 101, §§7-8, 7-9 and 7-10.

      (iii) Electric lamps which may be subject to breakage or which are installed in fixtures in confined locations when near woodwork, paper, clothing, or other combustible materials, shall be protected by wire guards, or plastic shields.

      (iv) Ceiling mounted examination light fixtures shall be suspended from rigid support structures mounted above the ceiling.

    (H) Receptacles. Only listed "hospital" grade single-grounding or duplex-grounding receptacles shall be used in all patient care areas. This does not apply to special purpose receptacles.

      (i) Installations of multiple ganged receptacles shall be permitted in patient care areas.

      (ii) Electrical outlets powered from the critical branch shall be provided in all patient care, procedure and treatment locations in accordance with NFPA 99, §3-4.2.2.2(c). At least one receptacle at each patient treatment or procedure location shall be powered from the normal power panel.

      (iii) Replacement of malfunctioning receptacles and installation of new receptacles powered from the critical branch in existing facilities shall be accomplished with receptacles of the same distinct color as the existing receptacles.

      (iv) In locations where mobile X-ray or other equipment requiring special electrical configuration is used, the additional receptacles shall be distinctively marked for the special use.

      (v) Each receptacle shall be grounded to the reference grounding point by means of a green insulated copper equipment grounding conductor.

    (I) Equipment.

Cont'd...

Next Page Previous Page

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page