RULE §510.122New Construction Requirements

      (i) Equipment required for safe operation of the facility shall be powered from the equipment system in accordance with the requirements contained in NFPA 99, §3-4.2.2.3.

      (ii) Boiler accessories including feed pumps, heat-circulating pumps, condensate return pumps, fuel oil pumps, and waste heat boilers shall be connected and installed to provide both normal and standby service.

    (J) Ground fault circuit interrupters (GFCI). GFCIs shall comply with NFPA 70. When GFCIs are used in critical areas, provisions shall be made to ensure that other essential equipment is not affected by activation of one interrupter.

    (K) Nurses calling systems. Three different types of nurses calling systems are required to be installed in a facility: a nurses regular calling system; a nurses emergency calling system; and a staff emergency assistance calling system. The facility shall comply with the requirements of this paragraph and any specific requirements for nurses calling systems for the particular unit of the facility in accordance with §134.123 of this title.

      (i) A nurses regular calling system is intended for routine communication between each patient and the nursing staff. Activation of the system at a patient's regular calling station will sound a repeating (every 20 seconds) audible signal at the nurse station, indicate type and location of call on the system monitor, and activate a distinct visible signal in the corridor at the patient suites door. In multi-corridor nursing units, additional visible signals shall be installed at corridor intersections. The audible signal shall be canceled and two-way voice communication between the patient room and the nursing staff shall be established at the unit's nursing station when the call is answered by the nursing staff. The visible signal(s) in the corridor shall be canceled upon termination of the call. An alarm shall activate at the nurses station when the call cable is unplugged.

      (ii) A nurses emergency calling system shall be installed in all toilets used by all patients to summon nursing staff in an emergency. Activation of the system shall sound a repeating (every 5 seconds) audible signal at the nurse station, indicate type and location of call on the system monitor, and activate a distinct visible signal in the corridor at the patient suites door. In multi-corridor nursing units, additional visible signals shall be installed at corridor intersections. The visible and audible signals shall be cancelable only at the patient calling station. Activation of the system shall also activate distinct visible signals in the clean workroom, in the soiled workroom, medication, charting, clean linen storage, nourishment, nurse lounge and equipment storage. When conveniently located and accessible from both the bathing and toilet fixtures, one emergency call station may serve one bathroom. A nurses emergency call system shall be accessible to a collapsed patient lying on the floor.

      (iii) A staff emergency assistance calling system (code blue) is intended to be used by staff to summon additional help in an emergency. In open suites, an emergency assistant call system device shall be located at the head of each bed and in each individual room. The emergency assistance calling device can be shared between two beds if conveniently located. Activation of the system will sound an audible signal at the nursing unit's nurses station, indicate type and location of call on the system monitor and activate a distinct visible signal in the corridor at the patient suites door. In multi-corridor nursing units, additional visible signals shall be installed at corridor intersections. Activation of the system shall also activate visible and audible signals in the clean workroom, in the soiled workroom, medication, charting, clean linen storage, nourishment, equipment storage, and examination/treatment room(s) with back up to a continuously staffed area (other than the nurse station or an administrative center) from which assistance can be summoned. The system shall have voice communication capabilities so that the type of emergency or help required may be specified.

    (L) Emergency electric service. A Type I essential electrical system shall be provided in each facility in accordance with requirements of NFPA 99; NFPA 101, and National Fire Protection Association 110, Standard for Emergency and Standby Power Systems, 1999 edition. Exception: Crisis stabilization units have the option of providing a Type II essential electrical system in accordance with the requirements of NFPA 99 and NFPA 101.

      (i) The number of transfer switches to be used shall be based on reliability, design and load considerations.

      (ii) All wiring installation of the emergency system of the essential electrical system shall be mechanically protected in nonflexible metal raceways in compliance with NFPA 70, §517-30(c)(3).

      (iii) The stored fuel capacity for emergency generators shall be sufficient to permit continuous operation for at least 24 hours at full load.

    (M) Fire alarm system. A fire alarm system which complies with NFPA 101, §18-3.4, and with NFPA 72, Chapter 3 requirements, shall be provided in each facility. The required fire alarm system components are as follows:

      (i) A fire alarm control panel (FACP) shall be installed at a continuously attended (24 hour) location. A remote fire alarm annunciator listed for fire alarm service and installed at a continuously attended location and is capable of indicating both visual and audible alarm, trouble and supervisory signals in accordance with the requirements of NFPA 72 may be substituted for the FACP.

      (ii) Manual fire alarm pull stations shall be installed in accordance with NFPA 101, §18-3.4.

      (iii) Smoke detectors for door release service shall be installed on the ceiling at each door opening in the smoke partition in accordance with NFPA 72, §2-10.6, where the doors are held open with electromagnetic devices conforming with NFPA 101, §18-2.2.6.

      (iv) Ceiling mounted smoke detector(s) shall be installed in room containing the FACP when this room is not attended continuously by staff as required by NFPA 72, §1-5.6.

      (v) Smoke detectors shall be installed in supply air ducts in accordance with NFPA 72, §2-10.4.2 and §2-10.5, and with NFPA 90A §4-4.2.

      (vi) Smoke detectors shall be installed in return air ducts in accordance with requirements of NFPA 72, §2-10.4.2.2 and §2-10.5, and NFPA 90A, §4-4.2(2).

      (vii) Fire sprinkler system water flow switches shall be installed in accordance with requirements of NFPA 101, §9-6.2; NFPA 13, §3-10; and NFPA 72, §3-8.5.

      (viii) Sprinkler system valve supervisory switches shall be installed in accordance with the requirements of NFPA 72, §3-8.6.

      (ix) Audible alarm indicating devices shall be installed in accordance with the requirements of NFPA 101, §18-3.4., and NFPA 72, §6-3.

      (x) Visual fire alarm indicating devices which comply with the requirements of §134.122(d)(1)(F) of this title (relating to New Construction Requirements) and NFPA 72, §6-4, shall be provided.

      (xi) Devices for transmitting alarm for alerting the local fire brigade or municipal fire department of fire or other emergency shall be provided. The devices shall be listed for the fire alarm service by a nationally recognized laboratory, and be installed in accordance with such listing and the requirements of NFPA 72.

      (xii) A smoke detection system for spaces open to corridor(s) shall be provided when required by NFPA 101, §18-3.6.1.

      (xiii) A fire alarm signal notification which complies with NFPA 101, §9-6.3, shall be provided to alert occupants of fire or other emergency.

      (xiv) Wiring for fire alarm detection circuits and fire alarm notification circuits shall comply with requirements of NFPA 70, Article 760.

      (xv) A smoke detection system for elevator recall shall be located in elevator lobbies, elevator machine rooms and at the top of elevator hoist ways as required by NFPA 72, §3-9.3.7.

        (I) The elevator recall smoke detection system in new construction shall comply with requirements of American Society of Mechanical Engineers/American National Standards Institute (ASME/ANSI) A17.1, Safety Code for Elevators and Escalators, 1996 edition. The publications of the ASME/ANSI referenced in this section may be obtained by writing ASME/ANSI, United Engineering Center, 345 East 47th Street, New York, N.Y. 10017.

        (II) The elevator recall smoke detection system in existing facilities shall comply with requirements of ASME/ANSI A17.3, Safety Code for Existing Elevators and Escalators, 1995 edition.