<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 26HEALTH AND HUMAN SERVICES
PART 1HEALTH AND HUMAN SERVICES COMMISSION
CHAPTER 510PRIVATE PSYCHIATRIC HOSPITALS AND CRISIS STABILIZATION UNITS
SUBCHAPTER GPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §510.122New Construction Requirements

      (iii) The stored fuel capacity for emergency generators shall be sufficient to permit continuous operation for at least 24 hours at full load.

    (M) Fire alarm system. A fire alarm system which complies with NFPA 101, §18-3.4, and with NFPA 72, Chapter 3 requirements, shall be provided in each facility. The required fire alarm system components are as follows:

      (i) A fire alarm control panel (FACP) shall be installed at a continuously attended (24 hour) location. A remote fire alarm annunciator listed for fire alarm service and installed at a continuously attended location and is capable of indicating both visual and audible alarm, trouble and supervisory signals in accordance with the requirements of NFPA 72 may be substituted for the FACP.

      (ii) Manual fire alarm pull stations shall be installed in accordance with NFPA 101, §18-3.4.

      (iii) Smoke detectors for door release service shall be installed on the ceiling at each door opening in the smoke partition in accordance with NFPA 72, §2-10.6, where the doors are held open with electromagnetic devices conforming with NFPA 101, §18-2.2.6.

      (iv) Ceiling mounted smoke detector(s) shall be installed in room containing the FACP when this room is not attended continuously by staff as required by NFPA 72, §1-5.6.

      (v) Smoke detectors shall be installed in supply air ducts in accordance with NFPA 72, §2-10.4.2 and §2-10.5, and with NFPA 90A §4-4.2.

      (vi) Smoke detectors shall be installed in return air ducts in accordance with requirements of NFPA 72, §2-10.4.2.2 and §2-10.5, and NFPA 90A, §4-4.2(2).

      (vii) Fire sprinkler system water flow switches shall be installed in accordance with requirements of NFPA 101, §9-6.2; NFPA 13, §3-10; and NFPA 72, §3-8.5.

      (viii) Sprinkler system valve supervisory switches shall be installed in accordance with the requirements of NFPA 72, §3-8.6.

      (ix) Audible alarm indicating devices shall be installed in accordance with the requirements of NFPA 101, §18-3.4., and NFPA 72, §6-3.

      (x) Visual fire alarm indicating devices which comply with the requirements of §134.122(d)(1)(F) of this title (relating to New Construction Requirements) and NFPA 72, §6-4, shall be provided.

      (xi) Devices for transmitting alarm for alerting the local fire brigade or municipal fire department of fire or other emergency shall be provided. The devices shall be listed for the fire alarm service by a nationally recognized laboratory, and be installed in accordance with such listing and the requirements of NFPA 72.

      (xii) A smoke detection system for spaces open to corridor(s) shall be provided when required by NFPA 101, §18-3.6.1.

      (xiii) A fire alarm signal notification which complies with NFPA 101, §9-6.3, shall be provided to alert occupants of fire or other emergency.

      (xiv) Wiring for fire alarm detection circuits and fire alarm notification circuits shall comply with requirements of NFPA 70, Article 760.

      (xv) A smoke detection system for elevator recall shall be located in elevator lobbies, elevator machine rooms and at the top of elevator hoist ways as required by NFPA 72, §3-9.3.7.

        (I) The elevator recall smoke detection system in new construction shall comply with requirements of American Society of Mechanical Engineers/American National Standards Institute (ASME/ANSI) A17.1, Safety Code for Elevators and Escalators, 1996 edition. The publications of the ASME/ANSI referenced in this section may be obtained by writing ASME/ANSI, United Engineering Center, 345 East 47th Street, New York, N.Y. 10017.

        (II) The elevator recall smoke detection system in existing facilities shall comply with requirements of ASME/ANSI A17.3, Safety Code for Existing Elevators and Escalators, 1995 edition.

      (xvi) A smoke detection system for initiating smoke removal from atriums shall be located above the highest floor level of the atrium and at return intakes from the atrium in accordance with National Fire Protection Association 92B, Guide for Smoke Management Systems in Malls, Atria, and Large Areas, 1995 edition.

      (xvii) Smoke detector(s) for shut-down of air handling units shall be provided. The detectors shall be installed in accordance with NFPA 90A, §4-4.2.

      (xviii) New or modified fire alarm systems shall be certified as meeting pplicable NFPA standards such as NFPA 101, 72A, 72E, etc. on form FML-009 040392 of the Office of the State Fire Marshal. A copy of the fire alarm system certification shall be submitted to the department.

    (N) Telecommunications and information systems. Telecommunications and information systems central equipment shall be installed in a separate location designed for the intended purpose. Special air conditioning and voltage regulation shall be provided as recommended by the manufacturer.

    (O) Lightning protection systems. When installed, lightning protection systems shall comply with National Fire Protection Association 780, Standard for the Installation of Lightning Protection Systems, 1997 edition.


Source Note: The provisions of this §510.122 adopted to be effective January 1, 2004, 28 TexReg 5154; transferred effective June 1, 2019, as published in the Texas Register May 17, 2019, 44 TexReg 2469

Previous Page

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page