(xvi) A smoke detection system for initiating smoke
removal from atriums shall be located above the highest floor level
of the atrium and at return intakes from the atrium in accordance
with National Fire Protection Association 92B, Guide for Smoke Management
Systems in Malls, Atria, and Large Areas, 1995 edition.
(xvii) Smoke detector(s) for shut-down of air handling
units shall be provided. The detectors shall be installed in accordance
with NFPA 90A, §4-4.2.
(xviii) New or modified fire alarm systems shall be
certified as meeting pplicable NFPA standards such as NFPA 101, 72A,
72E, etc. on form FML-009 040392 of the Office of the State Fire Marshal.
A copy of the fire alarm system certification shall be submitted to
the department.
(N) Telecommunications and information systems. Telecommunications
and information systems central equipment shall be installed in a
separate location designed for the intended purpose. Special air
conditioning and voltage regulation shall be provided as recommended
by the manufacturer.
(O) Lightning protection systems. When installed, lightning
protection systems shall comply with National Fire Protection Association
780, Standard for the Installation of Lightning Protection Systems,
1997 edition.
|
Source Note: The provisions of this §510.122 adopted to be effective January 1, 2004, 28 TexReg 5154; transferred effective June 1, 2019, as published in the Texas Register May 17, 2019, 44 TexReg 2469 |