(a) Service entrance and panels. The inspector shall:
(1) inspect service entrance cables and report as in need of
repair deficiencies in the integrity of insulation, drip loop, separation
of conductors at weatherheads and clearances;
(2) report as in need of repair a drop, weatherhead or
mast that is not securely fastened;
(3) report as in need of repair the lack of a grounding
electrode conductor in the service where visible, or the lack of secure connection
to the grounding electrode or grounding system;
(4) report as in need of repair accessible main or subpanels
that are not secured to the structure or appropriate for their location (weather-tight
if exposed to weather, appropriate clearances and accessibility), do not have
inside covers (dead fronts) in place, do not have conductors protected from
the edges of metal panel boxes, do not have trip ties installed on labeled
240 volt circuits, do not have proper fasteners or do not have knockouts filled;
(5) inspect and report as in need of repair deficiencies
in the type and condition of the wiring in the panels, in the compatibility
of overcurrent protectors for the size of conductor being used and in sizing
of listed equipment of overcurrent protection and conductors, when power requirements
for listed equipment are readily available and breakers are labeled;
(6) report as in need of repair a panel that is installed
in a hazardous location, such as a clothes closet;
(7) report as in need of repair the absence of appropriate
connections, such as copper/aluminum approved devices, pig-tailed connections
or crimp connections; and the absence of anti-oxidants on aluminum conductor
terminations; and
(8) report as in need of repair the lack of main disconnect(s).
(b) Specific limitations for service entrance and panels. The
inspector is not required to do the following:
(1) determine service capacity amperage or voltage or the capacity
of the electrical system relative to present or future use;
(2) determine the insurability of the property;
(3) conduct voltage drop calculations; or
(4) determine the accuracy of breaker labeling.
(c) Branch circuits, connected devices and fixtures. The inspector
shall:
(1) report the type of branch circuit wiring;
(2) inspect all accessible receptacles and report as in
need of repair a receptacle in which:
(A) power is not present;
(B) polarity is incorrect;
(C) the unit is not grounded, if applicable;
(D) there is evidence of arcing or excessive heat;
(E) the unit is not secured to the wall;
(F) the cover is not in place; or
(G) ground fault circuit interrupter devices are not properly
installed as set forth by the current edition of the National Electric Code,
publication 70A of the National Fire Protection Association, or do not operate
properly as shown by use of a separate testing device;
(3) operate all accessible wall and appliance switches
and report as in need of repair a switch that:
(A) does not operate or is damaged;
(B) displays evidence of arcing or excessive heat; or
(C) is not fastened securely with cover in place.
(4) inspect installed fixtures including lighting
devices and ceiling fans;
(5) report as in need of repair an inoperable or missing
fixture;
(6) report as in need of repair deficiencies in exposed
wiring, wiring terminations, junctions and junction boxes;
(7) report as in need of repair deficiencies or absences
of conduit in appropriate locations or conduit that is not terminated securely;
(8) report as in need of repair appliances and electrical
gutters that do not have proper bonding;
(9) report as in need of repair subpanels that are not
properly bonded and grounded;
(10) report as in need of repair the lack of disconnects
in appropriate locations;
(11) inspect (if branch circuit aluminum wiring is discovered
in the main or subpanels) a random sampling of accessible receptacles and
switches and report as in need of repair the absence of appropriate connections,
such as copper/aluminum approved devices, pig-tailed connections or crimp
connections;
(12) report as in need of repair the improper use of extension
cords; and
(13) report as in need of repair the absence of, or deficiencies
in, the installation and operation of smoke or fire detectors not connected
to a central alarm system.
|