TITLE 16ECONOMIC REGULATION
PART 1RAILROAD COMMISSION OF TEXAS
CHAPTER 14REGULATIONS FOR LIQUEFIED NATURAL GAS (LNG)
SUBCHAPTER EPIPING SYSTEMS AND COMPONENTS FOR ALL STATIONARY LNG INSTALLATIONS
RULE §14.2410Valves

(a) Cast iron, malleable iron, and ductile iron shall not be used in valves in piping.

(b) Extended bonnet valves with or without bellows seals should be used for service temperatures below -50 degrees Fahrenheit.


Source Note: The provisions of this §14.2410 adopted to be effective May 26, 2003, 28 TexReg 4100