RULE §510.127Preparation, Submittal, Review and Approval of Plans

(a) General.

  (1) Facility owners or operators may not begin construction of a new building or additions to or renovations or conversions of existing buildings until final construction documents are reviewed and approved by the Texas Health and Human Services Commission (HHSC).

  (2) Plans and specifications describing the construction of new buildings and additions to or renovations and conversions of existing buildings shall be prepared by registered architects, licensed professional engineers, or both.

  (3) Preliminary plans shall be prepared and submitted in accordance with subsection (b) of this section.

  (4) Final plans and specifications shall be prepared and submitted in accordance with subsection (c) of this section.

(b) Preliminary documents. Preliminary documents shall consist of a functional program narrative, preliminary plans, and outline specifications. These documents shall contain sufficient information to establish the project scope, description of functions to be performed, project location, required fire safety and exiting requirements, building construction type, compartmentation showing fire and smoke barriers, bed count and services, and the usage of all spaces, areas, and rooms on every floor level.

  (1) Preparation of preliminary plans. Preliminary plans shall be of a sufficiently large scale to clearly illustrate the proposed design but not less than one-eighth inch equals one foot. Preliminary plans shall provide the following information.

    (A) Floor area and bed distribution. The total floor area on each level involved in construction, together with the proposed bed distribution, shall be shown on the drawings.

    (B) Floor plan. Each floor plan shall indicate and identify all individual spaces, doors, windows and means of egress.

    (C) Existing floor plan. An overall floor plan showing existing spaces, smoke partitions, smoke compartments, and exits and their relationship to the new construction shall be submitted on all renovations or additions to an existing facility. Plans for remodeling of spaces above or below the level of discharge shall include the level of discharge floor plan, showing all exits at that level. When there are two different levels of discharge, plans for both levels shall be submitted.

    (D) Construction type and fire rating. Building sections shall be provided to illustrate construction type and fire protection rating. Sections shall be drawn at a scale sufficiently large to clearly present the proposed construction system.

    (E) Area map. A map of the area within a two-mile radius of the facility site shall be provided and any hazardous and undesirable location noted in §510.122(a) of this subchapter (relating to New Construction Requirements) shall be identified.

    (F) Site plan. A site plan shall be submitted and shall indicate the location of the proposed buildings in relation to property lines, existing buildings or structures, access and approach roads, and parking areas and drives. Any overhead or underground utilities or service lines shall also be indicated.

    (G) Outline specifications. Outline specifications shall provide a general description of the construction, materials, and finishes that are not shown on the drawings.

  (2) Functional program narrative. The facility shall provide a functional program narrative presented on facility letterhead and signed by facility administration. The narrative program shall be submitted to HHSC at the preliminary plan (stage 1) review and be approved by HHSC. The narrative shall include the functional description of each space and the following:

    (A) departmental relationships, number of patient beds in each category, and other basic information relating to the fulfillment of the facility's objectives;

    (B) a description of each function to be performed, approximate space needed for these functions, occupants of the various spaces, types of equipment required, interrelationship of various functions and spaces;

    (C) energy conservation measures, included in building, mechanical, and electrical designs; and

    (D) the type of construction (existing or proposed) as stated in Table 18-1.6.2 of National Fire Protection Association 101, Code for Safety to Life from Fire in Buildings and Structures, 2000 edition (NFPA 101), published by the National Fire Protection Association.

  (3) Submission of preliminary plans. One set of preliminary plans, outline specifications covering the construction of new buildings or alterations, additions, conversions, modernizations, or renovations to existing buildings, a functional program narrative, a completed and signed Application for Plan Review, and the applicable plan review fee in accordance with §510.26(c) of this chapter (relating to Fees) shall be submitted to HHSC for review and approval. For convenience, preliminary plans may be reduced for preliminary submittal. The cost of submitting plans and specifications shall be borne by the sender.

  (4) Preliminary plan review. All deficiencies noted in the preliminary plan review shall be satisfactorily resolved. Written HHSC approval of preliminary plans must be obtained prior to proceeding with final plans and specifications. This requirement also applies to fast-track projects.

(c) Construction documents. Construction documents or final plans and specifications shall be submitted to HHSC for review and approval prior to start of construction. All final plans and specifications shall be appropriately sealed and signed by a registered architect and a professional engineer licensed by the State of Texas.

  (1) Preparation of construction documents. Construction documents shall be well prepared so that clear and distinct prints may be obtained, shall be accurately and adequately dimensioned, and shall include all necessary explanatory notes, schedules, and legends and shall be adequate for contract purposes. Compliance with model building codes and this chapter shall be indicated. The type of construction, as classified by National Fire Protection Association 220, Standard on Types of Building Construction, 1999 edition, shall be provided for existing and new facilities. Final plans shall be drawn to a sufficiently large scale to clearly illustrate the proposed design but not less than one-eighth inch equals one foot. All rooms shall be identified by usage on all plans (architectural, fire safety, mechanical, electrical, etc.) submitted. Separate drawings shall be prepared for each of the following branches of work.

    (A) Architectural plans. Architectural drawings shall include the following:

      (i) site plan showing all new topography, newly established levels and grades, existing structures on the site (if any), new buildings and structures, roadways, walks, and the extent of the areas to be landscaped. All structures which are to be removed under the construction contract and improvements shall be shown. A general description of the immediate area surrounding the site shall be provided, which includes a:

      (ii) plan of each floor and roof to include fire and smoke separation, means of egress, and identification of all spaces;

      (iii) schedules of doors, windows, and finishes;

      (iv) elevations of each facade;

      (v) sections through building; and

      (vi) scaled details as necessary.

    (B) Fire safety plans. These drawings shall be provided for all newly constructed buildings, conversions of existing buildings for facilities, additions to existing licensed facilities, and remodeled portions of existing buildings containing licensed facilities. Fire safety plans shall be of a sufficiently large scale to clearly illustrate the proposed design but not less than one-sixteenth inch equals one foot and shall include the following information:

      (i) separate fire safety plans (preferably one floor plan per sheet) shall indicate location of fire protection rated walls and partitions, location and fire resistance rating of each fire damper, and the required means of egress (corridors, stairs, exits, exit passageways);

        (I) when a new building is to contain a proposed facility, when an existing building is converted to a facility, or when an addition is made to an existing facility building, plans of each floor and roof shall be provided; and

        (II) when a portion of a building is remodeled or when a new service is added, only the plan of the floor where the remodeling will take place or new service will be introduced and the plan of the floor of discharge shall be provided;

      (ii) designated smoke compartments with floor areas of each compartment, location and fire resistance rating (one or two hour) of each smoke partition, location, type and fire resistance rating of each smoke damper;

Cont'd...