<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 26HEALTH AND HUMAN SERVICES
PART 1HEALTH AND HUMAN SERVICES COMMISSION
CHAPTER 553LICENSING STANDARDS FOR ASSISTED LIVING FACILITIES
SUBCHAPTER DFACILITY CONSTRUCTION
DIVISION 5EXISTING SMALL TYPE B ASSISTED LIVING FACILITIES
RULE §553.125Fire Protection Systems Requirements for an Existing Small Type B Assisted Living Facility

(a) Fire alarm and smoke detection system. An existing small Type B assisted living facility must provide a manual fire alarm system meeting the requirements of section 9.6, Fire Detection, Alarm, and Communication Systems, in NFPA 101, Chapter 9, Building Service and Fire Protection Equipment, as modified by this section.

  (1) General. An existing small Type B assisted living facility must ensure the operation of any alarm initiating device automatically activates an audible or a visual alarm at the site.

  (2) Smoke detectors.

    (A) An existing small Type B assisted living facility must install smoke detectors in resident bedrooms, corridors, hallways, living rooms, dining rooms, offices, kitchens, laundries, attached garages used for car parking, and public or common areas, except as permitted in subparagraphs (B) and (C) of this paragraph.

    (B) An existing small Type B assisted living facility may install heat detectors in lieu of smoke detectors in kitchens, laundries, and attached garages used for car parking.

    (C) An existing small Type B assisted living facility located in a building constructed to meet the requirements of NFPA 101, Chapter 19, Existing Health Care Occupancies, may install a smoke detection system meeting the requirements of 19.3.4.5.1, Corridors, in NFPA 101, Chapter 19, Existing Health Care Occupancies, in lieu of the requirements in subparagraph (A) of this paragraph.

  (3) Alarm control panel.

    (A) An existing small Type B assisted living facility must provide a fire alarm control unit, or a fire alarm annunciator providing annunciation of all fire alarm, supervisory, and trouble signals by audible and visible indicators, in a location visible to staff at or near the staff area that is attended 24 hours a day.

    (B) An existing small Type B assisted living facility is not required to ensure a fire alarm control unit or fire alarm annunciator is visible to staff if the fire alarm is monitored by devices carried by all staff.

  (4) Fire alarm power source.

    (A) An existing small Type B assisted living facility must ensure a fire alarm system is powered by a permanently-wired, dedicated branch circuit that is powered from a commercial power source in accordance with NFPA 70.

    (B) An existing small Type B assisted living facility must provide a secondary, emergency power source meeting the requirements of NFPA 72.

(b) Fire sprinkler system.

  (1) An existing small Type B assisted living facility must provide one of the following fire sprinkler systems according to the requirements of 33.2.3.5, Extinguishment Requirements, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies.

    (A) A fire sprinkler system meeting the requirements of NFPA 13 in accordance with 33.2.3.5.3.3;

    (B) A fire sprinkler system meeting the requirements of NFPA 13R in accordance with 33.2.3.5.3.4; or

    (C) A fire sprinkler system meeting the requirements of NFPA 13D in accordance with 33.2.3.5.3.2.

  (2) An existing small Type B assisted living facility must ensure a fire sprinkler system is supervised according to 9.7.2, Supervision, in NFPA 101, Chapter 9, Building Service and Fire Protection Equipment.

(c) Protection of attics. An existing small Type B assisted living facility equipped with a fire sprinkler system must ensure an attic is protected according to the requirements of 33.2.3.5.7, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies, not later than August 31, 2024.

(d) Portable fire extinguishers. An existing small Type B assisted living facility must provide and maintain portable fire extinguishers according to the requirements of NFPA 10.

  (1) An existing small Type B assisted living facility must ensure all requirements of NFPA 10 are followed for all extinguisher types, including requirements for location, spacing, mounting heights, monthly inspections by staff, yearly inspections by a licensed agent, any necessary servicing, and hydrostatic testing as recommended by the manufacturer.

  (2) An existing small Type B assisted living facility must ensure portable fire extinguishers are located so the travel distance from any point in the facility to an extinguisher is no more than 75 feet.

  (3) An existing small Type B assisted living facility must ensure the actual size of any portable fire extinguisher meets the requirements of NFPA 10 for maximum floor area per unit covered, but an extinguisher must be no smaller than the following.

    (A) A water-type portable fire extinguisher must have a rating of at least 1-A according to NFPA 10; or

    (B) Other portable fire extinguishers must have a rating of at least 2-A:5-B:C according to NFPA 10.

  (4) An existing small Type B assisted living facility must ensure portable fire extinguishers are installed on hangers or brackets supplied with the extinguisher or mounted in an approved cabinet.

  (5) An existing small Type B assisted living facility must ensure a portable fire extinguisher is protected from impact or dislodgement.

  (6) An existing small Type B assisted living facility must ensure a portable fire extinguisher is installed at an appropriate height.

    (A) A portable fire extinguisher having a gross weight of up to 40 pounds must be installed so the top of the extinguisher is not more than five feet above the floor.

    (B) A portable fire extinguisher having a gross weight greater than 40 pounds must be installed so the top of the extinguisher is not more than three and a half feet above the floor.

    (C) A portable fire extinguisher must be installed so the clearance between the bottom of the extinguisher and the floor is at least four inches.

  (7) A portable extinguisher provided in a hazardous room must be located as close as possible to the door leading from the room and on the latch or knob side of the door.


Source Note: The provisions of this §553.125 adopted to be effective August 31, 2021, 46 TexReg 5189

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page