<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 26HEALTH AND HUMAN SERVICES
PART 1HEALTH AND HUMAN SERVICES COMMISSION
CHAPTER 554NURSING FACILITY REQUIREMENTS FOR LICENSURE AND MEDICAID CERTIFICATION
SUBCHAPTER DFACILITY CONSTRUCTION
DIVISION 5FACILITIES LICENSED ON OR AFTER SEPTEMBER 11, 2003 AND BEFORE APRIL 2, 2018
RULE §554.338Hazardous Areas

(a) Protection from hazardous areas must be as required in NFPA 101, except as required or modified in this section. Gas-fired equipment must not be located in attic spaces, except under the following conditions:

  (1) the area around the units must be constructed to be one-hour fire rated;

  (2) the enclosure must have sprinkler protection; and

  (3) combustion and venting air must be ducted from the exterior in properly sized metal ducts.

(b) Laboratories must be protected according to NFPA 99.

(c) Cooking equipment must be protected according to NFPA 101.

(d) Doors to hazardous areas must have closers and be kept closed unless provided with an approved hold-open device such as an alarm activated magnetic hold-open device, as permitted by NFPA 101. Doors must be single-swing type with positive latching hardware. View panels at laundry entrances must be provided and be of materials adequate to maintain the integrity of the door as allowed by NFPA 101.


Source Note: The provisions of this §554.338 adopted to be effective July 1, 1996, 21 TexReg 4408; amended to be effective March 22, 2018, 43 TexReg 1646; transferred effective January 15, 2021, as published in the Texas Register December 11, 2020, 45 TexReg 8871

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page