RULE §112.112Control Requirements

(a) Production Units 1 and 2 together are prohibited from operating with only one furnace on-line and Production Unit 3 is prohibited from operating with only one furnace on-line. Affected sources in §112.110 of this title (relating to Applicably) may not exceed the following pounds per hour (lb/hr) sulfur dioxide (SO2) limits based on the number of furnaces on-line in Production Units 1 and 2 and in Production Unit 3:

Attached Graphic

(b) If during any block one-hour period the number of furnaces on-line changes, the emission limit must be determined by one of the following methods:

  (1) the fewest number of furnaces on-line in each production unit during any fraction of the hour; or

  (2) the time-weighted average of all limits applying during any fraction of the hour, calculated using the following equation:

Attached Graphic

(c) The maximum emission rate of SO2 allowed under this section during any block one-hour period must be determined on a block one-hour average.

(d) The emission cap identified in §112.112(a) of this section is the maximum emission limit that applies to the sum of the emissions from the Incinerator + HRSG (EPN 13A), Flare 4 (EPN Flare 4), Dryer Stack Units Nos. 1 & 2 (EPN 7A), and Dryer Stack Unit No. 1 (EPN 12A), and the subcap identified in §112.112(a) of this section is the maximum emission limit that applies to the sum of the emissions from Dryer Stack Units Nos. 1 & 2 (EPN 7A) and Dryer Stack Units No. 3 (EPN 12A).

(e) Tail gas may only be combusted in sources whose emissions are routed to the Incinerator + HRSG (EPN 13A), Flare 4 (EPN Flare 4), Dryer Stack Units Nos. 1 & 2 (EPN 7A), and Dryer Stack Unit No. 1 (EPN 12A ).

(f) Simultaneous operation of the Incinerator + HRSG (EPN 13A) and Flare 4 (EPN FLARE 4) during any block one-hour period is prohibited.

(g) Sulfur or sulfur containing compounds may not be routed to Flare 1 (EPN Flare-1), Flare 2 (EPN Flare-2), or Flare 3 (EPN Flare-3) on or after the compliance date in §112.118 of this title (relating to Compliance Schedule).

(h) After construction and commencement of operation, if authorized, Flare 4 (EPN FLARE 4) must have a stack height of 60.35 meters and must be located at Universal Transverse Mercator (UTM) coordinates UTM East Meters 273185 and UTM North Meters 3573987 in UTM Zone 14.

(i) Incinerator + HRSG (EPN 13A) must have a stack height of 65.00 meters no later than the compliance date in §112.118 of this title (relating to Compliance Schedules).

(j) The owner or operator may request an alternate means of control under the provisions of §112.102(i) of this title (relating to Control Requirements).


Source Note: The provisions of this §112.112 adopted to be effective October 27, 2022, 47 TexReg 6985