<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 30ENVIRONMENTAL QUALITY
PART 1TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
CHAPTER 115CONTROL OF AIR POLLUTION FROM VOLATILE ORGANIC COMPOUNDS
SUBCHAPTER BGENERAL VOLATILE ORGANIC COMPOUND SOURCES
DIVISION 1STORAGE OF VOLATILE ORGANIC COMPOUNDS
RULE §115.112Control Requirements

(a) The following requirements apply in the Beaumont-Port Arthur, Dallas-Fort Worth, and El Paso areas, as defined in §115.10 of this title (relating to Definitions). The control requirements in this subsection no longer apply in the Dallas-Fort Worth area beginning March 1, 2013.

  (1) No person shall place, store, or hold in any storage tank any volatile organic compounds (VOC) unless the storage tank is capable of maintaining working pressure sufficient at all times to prevent any vapor or gas loss to the atmosphere or is in compliance with the control requirements specified in Table I(a) of this paragraph for VOC other than crude oil and condensate or Table II(a) of this paragraph for crude oil and condensate.

Attached Graphic

  (2) For an external floating roof or internal floating roof storage tank subject to the provisions of paragraph (1) of this subsection, the following requirements apply.

    (A) All openings in an internal floating roof or external floating roof except for automatic bleeder vents (vacuum breaker vents) and rim space vents must provide a projection below the liquid surface or be equipped with a cover, seal, or lid. Any cover, seal, or lid must be in a closed (i.e., no visible gap) position at all times except when the device is in actual use.

    (B) Automatic bleeder vents (vacuum breaker vents) must be closed at all times except when the roof is being floated off or landed on the roof leg supports.

    (C) Rim vents, if provided, must be set to open only when the roof is being floated off the roof leg supports or at the manufacturer's recommended setting.

    (D) Any roof drain that empties into the stored liquid must be equipped with a slotted membrane fabric cover that covers at least 90% of the area of the opening.

    (E) There must be no visible holes, tears, or other openings in any seal or seal fabric.

    (F) For an external floating roof storage tank, secondary seals must be the rim-mounted type (the seal must be continuous from the floating roof to the tank wall). The accumulated area of gaps that exceed 1/8 inch in width between the secondary seal and storage tank wall may not be greater than 1.0 square inch per foot of tank diameter.

  (3) Vapor control systems, as defined in §115.10 of this title, used as a control device on any storage tank must maintain a minimum control efficiency of 90%. If a flare is used, it must be designed and operated in accordance with 40 Code of Federal Regulations §60.18(b) - (f) (as amended through December 22, 2008 (73 FR 78209)) and be lit at all times when VOC vapors are routed to the flare.

(b) The following requirements apply in Gregg, Nueces, and Victoria Counties.

  (1) No person shall place, store, or hold in any storage tank any VOC, unless the storage tank is capable of maintaining working pressure sufficient at all times to prevent any vapor or gas loss to the atmosphere or is in compliance with the control requirements specified in Table I(a) in subsection (a)(1) of this section for VOC other than crude oil and condensate or Table II(a) in subsection (a)(1) of this section for crude oil and condensate. If a flare is used as a vapor recovery system, as defined in §115.10 of this title, it must be designed and operated in accordance with 40 Code of Federal Regulations §60.18(b) - (f) (as amended through December 22, 2008 (73 FR 78209)) and be lit at all times when VOC vapors are routed to the flare.

  (2) For an external floating roof or internal floating roof storage tank subject to the provisions of paragraph (1) of this subsection, the following requirements apply.

    (A) All openings in an internal floating roof or external floating roof, except for automatic bleeder vents (vacuum breaker vents) and rim space vents, must provide a projection below the liquid surface or be equipped with a cover, seal, or lid. Any cover, seal, or lid must be in a closed (i.e., no visible gap) position at all times, except when the device is in actual use.

    (B) Automatic bleeder vents (vacuum breaker vents) must be closed at all times except when the roof is being floated off or landed on the roof leg supports.

    (C) Rim vents, if provided, must be set to open only when the roof is being floated off the roof leg supports or at the manufacturer's recommended setting.

    (D) Any roof drain that empties into the stored liquid must be equipped with a slotted membrane fabric cover that covers at least 90% of the area of the opening.

    (E) There must be no visible holes, tears, or other openings in any seal or seal fabric.

    (F) For an external floating roof storage tank, secondary seals must be the rim-mounted type (the seal shall be continuous from the floating roof to the tank wall). The accumulated area of gaps that exceed 1/8 inch in width between the secondary seal and tank wall may not be greater than 1.0 square inch per foot of tank diameter.

(c) The following requirements apply in Aransas, Bexar, Calhoun, Matagorda, San Patricio, and Travis Counties.

  (1) No person may place, store, or hold in any storage tank any VOC, other than crude oil or condensate, unless the storage tank is capable of maintaining working pressure sufficient at all times to prevent any vapor or gas loss to the atmosphere or is in compliance with the control requirements specified in Table I(b) of this paragraph for VOC other than crude oil and condensate.

Attached Graphic

  (2) For an external floating roof or internal floating roof storage tank subject to the provisions of paragraph (1) of this subsection, the following requirements apply.

    (A) There must be no visible holes, tears, or other openings in any seal or seal fabric.

    (B) All tank gauging and sampling devices must be vapor-tight except when gauging and sampling is taking place.

  (3) No person in Matagorda or San Patricio Counties shall place, store, or hold crude oil or condensate in any storage tank unless the storage tank is a pressure tank capable of maintaining working pressures sufficient at all times to prevent vapor or gas loss to the atmosphere or is equipped with one of the following control devices, properly maintained and operated:

    (A) an internal floating roof or external floating roof, as defined in §115.10 of this title. These control devices will not be allowed if the VOC has a true vapor pressure of 11.0 pounds per square inch absolute (psia) or greater. All tank-gauging and tank-sampling devices must be vapor-tight, except when gauging or sampling is taking place; or

    (B) a vapor control system as defined in §115.10 of this title.

(d) The following requirements apply in the Houston-Galveston-Brazoria area, as defined in §115.10 of this title. The requirements in this subsection no longer apply beginning March 1, 2013.

  (1) No person shall place, store, or hold in any storage tank any VOC unless the storage tank is capable of maintaining working pressure sufficient at all times to prevent any vapor or gas loss to the atmosphere or is in compliance with the control requirements specified in either Table I(a) of subsection (a)(1) of this section for VOC other than crude oil and condensate or Table II(a) of subsection (a)(1) of this section for crude oil and condensate.

  (2) For an external floating roof or internal floating roof storage tank subject to the provisions of paragraph (1) of this subsection, the following requirements apply.

    (A) All openings in an internal floating roof or external floating roof as defined in §115.10 of this title except for automatic bleeder vents (vacuum breaker vents), and rim space vents must provide a projection below the liquid surface. All openings in an internal floating roof or external floating roof except for automatic bleeder vents (vacuum breaker vents), rim space vents, leg sleeves, and roof drains must be equipped with a deck cover. The deck cover must be equipped with a gasket in good operating condition between the cover and the deck. The deck cover must be closed (i.e., no gap of more than 1/8 inch) at all times, except when the cover must be open for access.

    (B) Automatic bleeder vents (vacuum breaker vents) and rim space vents must be equipped with a gasketed lid, pallet, flapper, or other closure device and must be closed (i.e., no gap of more than 1/8 inch) at all times except when required to be open to relieve excess pressure or vacuum in accordance with the manufacturer's design.

    (C) Each opening into the internal floating roof for a fixed roof support column may be equipped with a flexible fabric sleeve seal instead of a deck cover.

Cont'd...

Next Page

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page