TITLE 30ENVIRONMENTAL QUALITY
PART 1TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
CHAPTER 115CONTROL OF AIR POLLUTION FROM VOLATILE ORGANIC COMPOUNDS
SUBCHAPTER HHIGHLY-REACTIVE VOLATILE ORGANIC COMPOUNDS
DIVISION 2COOLING TOWER HEAT EXCHANGE SYSTEMS
RULE §115.764Monitoring and Testing Requirements

(a) The owner or operator of a cooling tower heat exchange system with a design capacity to circulate 8,000 gallons per minute (gpm) or greater of cooling water shall:

  (1) install, calibrate, operate, and maintain a continuous flow monitor on each inlet of each cooling tower. Each monitor shall be calibrated on an annual basis to within ±5.0% accuracy. When the cooling tower flow monitor is down, flow measurements shall be used for the most recent 24-hour period in which the flow measurements are representative of cooling tower operations during monitor downtime;

  (2) install, calibrate, operate, and maintain a system to continuously determine the total strippable volatile organic compound (VOC) concentration at each inlet of each cooling tower. The continuous monitoring system must have a minimum detection limit capability of no more than 25 parts per billion by weight (ppbw) of strippable VOC in the cooling water. The continuous monitor must be calibrated with methane or a VOC that best represents potential leakage into the cooling tower system and the emissions from the system. Calibration must be checked weekly or more frequently, as necessary, to maintain a monitor drift of less than 5.0%. During out-of-order periods of the VOC monitor(s) of 24 hours or greater, a sample must be collected for total VOC analysis according to the air-stripping method in Appendix P of the Texas Commission on Environmental Quality Sampling Procedures Manual (January 2003). This sample must be collected at least three times per calendar week, with an interval of no less than 36 hours between samples;

  (3) continuously operate each monitoring system as required by this section at least 95% of the time when the cooling tower is operational, averaged over a calendar year. The percent measurement data availability must be calculated as the total operating hours of the cooling tower heat exchange system for which valid quality-assured data was recorded divided by the total operating hours of the cooling tower heat exchange system. Time required for normal calibration checks required under this subsection is not considered downtime for purposes of this calculation;

  (4) determine the speciated strippable highly-reactive volatile organic compound (HRVOC) concentration by collecting samples from each inlet of each cooling tower at least once per month in accordance with the air-stripping method in Appendix P;

  (5) if the concentration of total strippable VOC is equal to or greater than 50 ppbw in the cooling tower water for more than a one-hour block of time, collect an additional sample to determine speciated and total HRVOC in accordance with the air-stripping method in Appendix P from each inlet of the affected cooling tower at least once daily, beginning on the next calendar day. The additional sampling to determine speciated and total HRVOC shall continue on a daily basis until the concentration of total strippable VOC drops below 50 ppbw; and

  (6) in lieu of the monitoring in paragraph (2) of this subsection and the sampling for speciation of strippable HRVOC in paragraphs (4) and (5) of this subsection, a continuous on-line monitor capable of providing total HRVOC and speciated HRVOCs in ppbw may be installed. The sampling system for the continuous on-line monitoring system must be demonstrated equivalent to the air-stripping apparatus used in Appendix P for determining strippable HRVOC concentrations in the water as specified in subsection (f) of this section. The continuous on-line monitor system must satisfy the requirements of Sections 8.3, 10, 13.1, and 13.2 of 40 Code of Federal Regulations (CFR) Part 60, Appendix B, Performance Specification 9, as amended through October 17, 2000 (65 FR 61744). The multi-point calibration procedure in Section 10.1 of Performance Specification 9 must be performed at least once every calendar quarter instead of once every month. During out-of-order periods of the on-line HRVOC monitor(s) of 24 hours or greater, sampling must be performed for total and speciated HRVOC analysis according to the air-stripping method in Appendix P. Sampling must be performed at least three times per calendar week, with an interval of no less than 36 hours between sampling times, until the continuous on-line monitor is properly operating and within the required performance specifications.

    (A) During out-of-order periods of the monitoring system, data should be handled as follows for purposes of recordkeeping and demonstrating compliance:

      (i) For each out-of-order period less than 24 hours, the maximum one-hour average HRVOC concentrations from the 24-hour period immediately prior to the out-of-order period must be used; and

      (ii) For each out-of-order period of 24 hours or greater, the maximum one-hour average HRVOC concentrations from the 24-hour period immediately prior to the out-of-order period must be used for the time period from the initial outage of the monitoring system to time of collection of the first manual sample required by this paragraph. The results of each manual sample must be used for the time period from collection of that sample to the collection of the subsequent sample, or to the time that the continuous monitoring system is on-line and within the required performance specifications.

    (B) For periods that only the analyzer system is out of order and the sampling system (i.e., HRVOC sparging or stripping system) is still functioning within normal specifications, the owner or operator may elect to collect the manual samples required by this paragraph using the sampling system of the continuous HRVOC monitoring system.

(b) The owner or operator of a cooling tower heat exchange system with a design capacity to circulate less than 8,000 gpm of cooling water or a cooling tower heat exchange system in dedicated service to a jacketed reactor, as defined in §115.760(b) of this title (relating to Applicability and Cooling Tower Heat Exchange System Definitions), shall:

  (1) install, calibrate, operate, and maintain a continuous flow monitor on each inlet of each cooling tower. Each monitor must be calibrated on an annual basis to within ±5.0% accuracy. When the cooling tower flow monitor is down, flow measurements must be used for the most recent 24-hour period in which the flow measurements are representative of cooling tower operations during monitor downtime;

  (2) determine the total strippable VOC concentration by collecting samples from each inlet of each cooling tower at least twice per week in accordance with the air-stripping method in Appendix P with an interval of not less than 48 hours between samples;

  (3) operate each monitoring system as required by this section at least 95% of the time when the cooling tower is operational, averaged over a calendar year. The percent measurement data availability must be calculated as the total operating hours of the cooling tower heat exchange system for which valid quality-assured data was recorded divided by the total operating hours of the cooling tower heat exchange system. Time required for normal calibration checks required under this subsection is not considered downtime for purposes of this calculation;

  (4) determine the speciated strippable HRVOC concentration by collecting samples from each inlet of each cooling tower at least once per month in accordance with the air-stripping method in Appendix P;

  (5) if the concentration of total strippable VOC is equal to or greater than 50 ppbw in the cooling tower water, collect an additional sample to determine total strippable VOC, speciated HRVOC, and total HRVOC from each inlet of the affected cooling tower at least once daily, beginning on the next calendar day, in accordance with the air-stripping method in Appendix P. The additional sampling to determine total strippable VOC, speciated HRVOC, and total HRVOC must continue on a daily basis until the concentration of total strippable VOC drops below 50 ppbw; and

  (6) in lieu of the monitoring in paragraph (2) of this subsection and the sampling for speciation of strippable HRVOC in paragraphs (4) and (5) of this subsection, a continuous on-line monitor capable of providing total HRVOC and speciated HRVOCs in ppbw may be installed. The sampling system for the continuous on-line monitoring system must be demonstrated equivalent to the air-stripping apparatus used in Appendix P for determining strippable HRVOC concentrations in the water as specified in subsection (f) of this section. The continuous on-line monitor system must satisfy the requirements of Sections 8.3, 10, 13.1, and 13.2 of 40 CFR Part 60, Appendix B, Performance Specification 9. The multi-point calibration procedure in Section 10.1 of Performance Specification 9 must be performed at least once every calendar quarter instead of once every month. During out-of-order periods of the on-line HRVOC monitor(s) of 24 hours or greater, sampling must be performed for total and speciated HRVOC analysis according to the air-stripping method in Appendix P. Sampling must be performed at least twice per calendar week, with an interval of no less than 72 hours between sampling times, until the continuous on-line monitor is properly operating and within the required performance specifications.

    (A) During out-of-order periods of the monitoring system, data should be handled as follows for purposes of recordkeeping and demonstrating compliance.

Cont'd...