RULE §117.140Continuous Demonstration of Compliance

(a) Totalizing fuel flow meters. The owner or operator of units listed in this subsection shall install, calibrate, maintain, and operate a totalizing fuel flow meter, with an accuracy of ± 5%, to individually and continuously measure the gas and liquid fuel usage. A computer that collects, sums, and stores electronic data from continuous fuel flow meters is an acceptable totalizer. The owner or operator of units with totalizing fuel flow meters installed prior to March 31, 2005, that do not meet the accuracy requirements of this subsection shall either recertify or replace existing meters to meet the ± 5% accuracy required as soon as practicable but no later than March 31, 2007. For the purpose of compliance with this subsection for units having pilot fuel supplied by a separate fuel system or from an unmonitored portion of the same fuel system, the fuel flow to pilots may be calculated using the manufacturer's design flow rates rather than measured with a fuel flow meter. The calculated pilot fuel flow rate must be added to the monitored fuel flow when fuel flow is totaled.

  (1) Totalizing fuel flow meters are required for the following units that are subject to §117.105 or §117.110 of this title (relating to Emission Specifications for Reasonably Available Control Technology (RACT); and Emission Specifications for Attainment Demonstration) and for stationary gas turbines that are exempt under §117.103(b)(6) of this title (relating to Exemptions):

    (A) if individually rated more than 40 million British thermal units per hour (MMBtu/hr):

      (i) boilers;

      (ii) process heaters; and

      (iii) gas turbine supplemental-fired waste heat recovery units;

    (B) stationary, reciprocating internal combustion engines not exempt by §117.103(a)(6), (a)(8), (b)(8), or (b)(9) of this title; and

    (C) stationary gas turbines with a megawatt (MW) rating greater than or equal to 1.0 MW operated more than 850 hours per year.

  (2) The following are alternatives to the fuel flow monitoring requirements of paragraph (1) of this subsection.

    (A) Units operating with a nitrogen oxides (NOX ) and diluent continuous emissions monitoring system (CEMS) under subsection (e) of this section may monitor stack exhaust flow using the flow monitoring specifications of 40 Code of Federal Regulations (CFR) Part 60, Appendix B, Performance Specification 6 or 40 CFR Part 75, Appendix A.

    (B) Units that vent to a common stack with a NOX and diluent CEMS under subsection (e) of this section may use a single totalizing fuel flow meter.

    (C) Diesel engines operating with run time meters may meet the fuel flow monitoring requirements of this subsection through monthly fuel use records maintained for each engine.

    (D) Stationary reciprocating internal combustion engines and stationary gas turbines equipped with a continuous monitoring system that continuously monitors horsepower and hours of operation are not required to install totalizing fuel flow meters. The continuous monitoring system must be installed, calibrated, maintained, and operated according to manufacturers' recommended procedures.

(b) Oxygen (O2) monitors.

  (1) The owner or operator shall install, calibrate, maintain, and operate an O2 monitor to measure exhaust O2 concentration on the following units operated with an annual heat input greater than 2.2(1011 ) British thermal units per year (Btu/yr):

    (A) boilers with a rated heat input greater than or equal to 100 MMBtu/hr; and

    (B) process heaters with a rated heat input greater than or equal to 100 MMBtu/hr, except as provided in subsection (f) of this section.

  (2) The following are not subject to this subsection:

    (A) units listed in §117.103(b)(3) - (5) and (7) - (9) of this title;

    (B) process heaters operating with a carbon dioxide CEMS for diluent monitoring under subsection (e) of this section; and

    (C) wood-fired boilers.

  (3) The O2 monitors required by this subsection are for process monitoring (predictive monitoring inputs, boiler trim, or process control) and are only required to meet the location specifications and quality assurance procedures referenced in subsection (e) of this section if O2 is the monitored diluent under that subsection. However, if new O2 monitors are required as a result of this subsection, the criteria in subsection (e) of this section should be considered the appropriate guidance for the location and calibration of the monitors.

(c) NOX monitors.

  (1) The owner or operator of units listed in this paragraph shall install, calibrate, maintain, and operate a CEMS or predictive emissions monitoring system (PEMS) to monitor exhaust NOX . The units are:

    (A) boilers with a rated heat input greater than or equal to 250 MMBtu/hr and an annual heat input greater than 2.2(1011 ) Btu/yr;

    (B) process heaters with a rated heat input greater than or equal to 200 MMBtu/hr and an annual heat input greater than 2.2(1011 ) Btu/yr;

    (C) boilers and process heaters that are vented through a common stack and the total rated heat input from the units combined is greater than or equal to 250 MMBtu/hr and the annual heat input combined is greater than 2.2(1011 ) Btu/yr;

    (D) stationary gas turbines with an MW rating greater than or equal to 30 MW operated more than 850 hours per year;

    (E) units that use a chemical reagent for reduction of NOX ; and

    (F) units that the owner or operator elects to comply with the NOX emission specifications of §117.105 or §117.110(a) of this title using a pounds per million British thermal unit (lb/MMBtu) limit on a 30-day rolling average.

  (2) The following are not required to install CEMS or PEMS under this subsection:

    (A) for purposes of §117.105 or §117.110(a) of this title, units listed §117.103(b)(3) - (5) and (7) - (9) of this title; and

    (B) units subject to the NOX CEMS requirements of 40 CFR Part 75.

  (3) The owner or operator shall use one of the following methods to provide substitute emissions compliance data during periods when the NOX monitor is off-line:

    (A) if the NOX monitor is a CEMS:

      (i) subject to 40 CFR Part 75, use the missing data procedures specified in 40 CFR Part 75, Subpart D (Missing Data Substitution Procedures); or

      (ii) subject to 40 CFR Part 75, Appendix E, use the missing data procedures specified in 40 CFR Part 75, Appendix E, §2.5 (Missing Data Procedures);

    (B) use 40 CFR Part 75, Appendix E monitoring in accordance with §117.1040(d) of this title (relating to Continuous Demonstration of Compliance);

    (C) if the NOX monitor is a PEMS:

      (i) use the methods specified in 40 CFR Part 75, Subpart D; or

      (ii) use calculations in accordance with §117.8110(b) of this title (relating to Emission Monitoring System Requirements for Utility Electric Generation Sources); or

    (D) if the methods specified in subparagraphs (A) - (C) of this paragraph are not used, the owner or operator shall use the maximum block one-hour emission rate as measured during the initial demonstration of compliance required in §117.135(f) of this title (relating to Initial Demonstration of Compliance).

(d) Carbon monoxide (CO) monitoring. The owner or operator shall monitor CO exhaust emissions from each unit listed in subsection (c)(1) of this section using one or more of the methods specified in §117.8120 of this title (relating to Carbon Monoxide (CO) Monitoring).

(e) CEMS requirements. The owner or operator of any CEMS used to meet a pollutant monitoring requirement of this section shall comply with the requirements of §117.8100(a) of this title (relating to Emission Monitoring System Requirements for Industrial, Commercial, and Institutional Sources).

(f) PEMS requirements. The owner or operator of any PEMS used to meet a pollutant monitoring requirement of this section shall comply with the following.

  (1) The PEMS must predict the pollutant emissions in the units of the applicable emission specifications of this division (relating to Beaumont-Port Arthur Ozone Nonattainment Area Major Sources).

  (2) The PEMS must meet the requirements of §117.8100(b) of this title.

(g) Engine monitoring. The owner or operator of any stationary gas engine subject to the emission specifications of this division shall stack test engine NOX and CO emissions as specified in §117.8140(a) of this title (relating to Emission Monitoring for Engines).