<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 30ENVIRONMENTAL QUALITY
PART 1TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
CHAPTER 217DESIGN CRITERIA FOR DOMESTIC WASTEWATER SYSTEMS
SUBCHAPTER FACTIVATED SLUDGE SYSTEMS
RULE §217.156Sequencing Batch Reactors

(a) System Sizing and Reliability.

  (1) A sequencing batch reactor (SBR) must meet the reliability requirements in §217.155(b) and (c)(3) of this title (relating to Aeration Equipment Sizing), and power source reliability requirements in §217.36 of this title (relating to Emergency Power Requirements).

  (2) An SBR must have a minimum decantable volume that is sufficient to pass the design flow, and must be capable of meeting permitted effluent limits, with the largest basin out of service.

  (3) A two-basin wastewater treatment facility without removable aeration devices is required to have aerated storage of mixed liquor separate from the SBR tank(s).

  (4) An SBR with a fixed level decanter must have more than two basins and additional decantable storage volume.

  (5) An equalization basin is required if an SBR has fixed decant equipment and decant volumes that do not accommodate the peak flow.

  (6) Organic loadings must conform to the values in Table F.1. in Figure: 30 TAC §217.154(b)(2) of this title (relating to Aeration Basin and Clarifier Sizing--Traditional Design). Organic loadings must be below 35 pounds of five-day biochemical oxygen demand per 1,000 cubic feet of tank volume.

  (7) The reactor mixed liquor suspended solids (MLSS) level at the normal operating level must range from at least 3,000 milligrams per liter (mg/l) to not more than 5,000 mg/l.

  (8) The minimum depth of the MLSS during a react phase is 9.0 feet.

  (9) The minimum side water depth of an SBR tank is 12 feet.

  (10) An SBR must include sludge digestion pursuant to the requirements in Subchapter J of this chapter (relating to Sludge Processing).

(b) Decanter Design.

  (1) A decanter must control the velocity at an inlet port or at the edge of submerged weirs to prevent vortexing, disturbance of the settled sludge, and entry of floating materials.

  (2) The entrance velocity to a decanter must not exceed 1.0 foot per second.

  (3) A decanter must draw effluent from below the water surface and include a device that excludes scum.

  (4) A decanter must maintain a zone of separation between the settled sludge and the decanter of no less than 12 inches.

  (5) A decanter must prevent solids from entering the decanter during a react cycle by using one the following methods:

    (A) recycling treated effluent to wash out solids trapped in a decanter;

    (B) mechanically closing a decanter when it is not in use; or

    (C) filling a decanter with air except during a decant period.

  (6) The performance of a decanter and related pipes and valves must not be affected by ambient temperatures below 32 degrees Fahrenheit.

  (7) A fixed decanter is prohibited in a basin where simultaneous fill and decant may occur.

  (8) For any system of tanks that is fed sequentially, the size of the decant system must accommodate the design flow with a constant cycle time with the largest tank out of service.

  (9) An SBR system utilizing more than two basins must allow the decanting of at least two tanks simultaneously.

  (10) If units downstream of an SBR are not capable of accepting the peak flow rate of the decanting cycle, flow equalization must be provided between the decanter and the downstream units.

(c) SBR Tank Details.

  (1) An SBR requires multiple tanks.

  (2) An SBR with two tanks or an SBR system operating with a continuous feed during settling and decanting phases must include influent baffling and physical separation from the decanter.

  (3) An elongated tank must be used for an SBR system if influent baffling is required.

  (4) An SBR tank must have a minimum freeboard of 18 inches at the maximum liquid level.

  (5) An SBR tank must not be buoyant when empty.

  (6) Structures using a common wall must be designed to accommodate the stresses generated when one basin is full and an adjacent basin is empty.

  (7) Each SBR wall must be watertight.

  (8) A sump must be provided in any basin with a flat bottom.

  (9) An SBR system must have a dedicated means of transferring sludge between aeration basins.

  (10) An SBR system must include a means of scum removal in each aeration basin.

  (11) Each SBR tank must include a dewatering system and an emergency overflow to another aeration tank or a storage tank.

  (12) At a wastewater treatment facility that is not staffed 24-hours per day, a manually operated SBR tank must include a high-level alarm that notifies wastewater treatment facility staff in accordance with §217.161 of this title (relating to Electrical and Instrumentation Systems).

  (13) A design must specify the means and frequency for removal of grit and other debris from the SBR tanks.

  (14) All equipment must be accessible for inspection, maintenance, and operation. Walkways shall be provided to allow inspection, maintenance, and process control sampling and to allow access to instrumentation, mechanical equipment, and electrical equipment.

  (15) An SBR may use fine screens pursuant to §217.122 of this title (relating to Fine Screens).

  (16) An SBR preceded by a primary clarifier may use a comminutor.

  (17) An SBR must have a sufficient number of tanks to operate at design flow with the largest tank out of service.

(d) Aeration and Mixing Equipment.

  (1) In addition to the requirements of §217.155 of this title, aeration equipment must handle the cyclical operation in an SBR.

  (2) The aeration and mixing equipment must not interfere with settling.

  (3) A dissolved oxygen concentration of 2.0 mg/l must be maintained in a tank during the fill cycle.

  (4) The design must specify the blower discharge pressure at the maximum water depth.

  (5) An SBR used for biological nutrient removal or reduction must meet the design requirements of §217.163 of this title (relating to Advanced Nutrient Removal).

  (6) The design of an SBR must allow for the removal of air diffusers or mechanical aeration devices without dewatering the tank.

(e) Control Systems.

  (1) The motor control center must include programmable logic controllers (PLC) that are able to operate with limited operator adjustment and be programmed to meet the effluent limitations in the wastewater permit at the design loadings. An SBR must have the ability to run in full manual mode.

  (2) A hard-wired backup means of operating the SBR is required.

  (3) The PLC must include battery backup. A duplicate set of all circuit boards must be kept at the wastewater treatment facility.

  (4) Adequate controls for the separate operation of each tank must be provided.

  (5) A tank level system must include floats or pressure transducers.

    (A) A float system must be protected from prevailing winds and freezing.

    (B) A bubbler system in a tank level system is prohibited.

  (6) The control panel switches must include the following switches:

    (A) pumps - hand/off/automatic;

    (B) valves - open/closed/automatic;

    (C) blowers or aerators - hand/off/automatic; and

    (D) selector switch for tank(s) - in operation/standby.

  (7) The control panel visual displays must include:

    (A) a mimic diagram of the process that shows the status and position of all pumps, valves, blowers, aerators, and mixers;

    (B) process cycle and time remaining;

    (C) instantaneous and totalized influent flow to the wastewater treatment facility and effluent flow of the final discharge;

    (D) tank level gauges or levels;

    (E) sludge pumping rate and duration; and

    (F) airflow rate and totalizer.

  (8) The annunciator panel must include the following alarm condition indicators:

    (A) high and low water levels in each tank;

    (B) failure of all automatically operated valves;

    (C) decanter failure;

    (D) blowers, if used - low pressure, high temperature, and failure;

    (E) mechanical aerator, if used - high temperature and failure;

    (F) pump - high pressure and failure; and

    (G) mixers, if used - failure.


Source Note: The provisions of this §217.156 adopted to be effective August 28, 2008, 33 TexReg 6843; amended to be effective December 4, 2015, 40 TexReg 8254

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page