<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 30ENVIRONMENTAL QUALITY
PART 1TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
CHAPTER 217DESIGN CRITERIA FOR DOMESTIC WASTEWATER SYSTEMS
SUBCHAPTER LULTRAVIOLET LIGHT DISINFECTION
RULE §217.298Ultraviolet Light Disinfection System Cleaning and Maintenance

(a) An ultraviolet (UV) disinfection system must include provisions for draining each UV disinfection channel to another treatment unit within the wastewater treatment facility and for routine cleaning of the UV lamps and modules.

(b) A UV system must include the following replacement parts, as a percentage of the total system, equal to at least:

  (1) 5% of the lamps;

  (2) 2% of the ballasts; and

  (3) 5% of the quartz sleeves.

(c) The UV system must ensure continuous disinfection during maintenance.


Source Note: The provisions of this §217.298 adopted to be effective August 28, 2008, 33 TexReg 6843; amended to be effective December 4, 2015, 40 TexReg 8254