TITLE 25HEALTH SERVICES
PART 1DEPARTMENT OF STATE HEALTH SERVICES
CHAPTER 133HOSPITAL LICENSING
SUBCHAPTER IPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §133.162New Construction Requirements

signal in the corridor at the patient suites door. In multi-corridor nursing units, additional visible signals shall be installed at corridor intersections. Calls shall activate audible and visible signals in accordance with Table 7 of §133.169(g) of this title. A visible system shall clearly define the alarm location to a continuously staffed back up area (other than the nurse station or an administrative center) from which assistance can be summoned. Alternatively, back up may be provided via automatic annunciation from the staff emergency assistance calling system through wireless phones or pagers. The system shall have voice communication capability so that the type of emergency or help required may be specified between the point of alarm and the unit's nurse station.

    (M) Emergency electric service. A type I essential electrical system shall be provided in each hospital in accordance with requirements of NFPA 99; NFPA 101, and National Fire Protection Association 110, Standard for Emergency and Standby Power Systems, 2002 edition.

      (i) When the emergency and standby power systems require a fuel source with tank, the fuel storage capacity tank shall have enough fuel for a period of 24 hours.

      (ii) When a vapor liquefied petroleum gas (LPG) systems (natural gas) system is used, the 24-hour fuel capacity on-site is not required. The vapor withdrawal LPG system shall require a dedicated fuel supply.

      (iii) When the emergency generator(s) and electrical transformer(s) are located within the same area, they shall be located at least 10 feet apart.

    (N) Fire alarm system. A fire alarm system which complies with NFPA 101, §18.3.4, and with NFPA 72, Chapter 6 requirements, shall be provided in each facility. The required fire alarm system components are as follows:

      (i) A fire alarm control panel (FACP) shall be installed at a continuously attended (24 hour) location. A remote fire alarm annunciator listed for fire alarm service and installed at a continuously attended location and is capable of indicating both visual and audible alarm, trouble and supervisory signals in accordance with the requirements of NFPA 72 may be substituted for the FACP.

      (ii) Manual fire alarm pull stations shall be installed in accordance with NFPA 101, §18.3.4.

      (iii) Smoke detectors for door release service shall be installed on the ceiling at each door opening in the smoke partition in accordance with NFPA 72, §6.15.6, where the doors are held open with electromagnetic devices conforming with NFPA 101, §18.2.2.6.

      (iv) Ceiling-mounted smoke detector(s) shall be installed in room containing the FACP when this room is not attended continuously by staff as required by NFPA 72, §4.4.5.

      (v) Smoke detectors shall be installed in air ducts in accordance with NFPA 72, §5.14.4.2 and §5.14.5 and NFPA 90A, §6.4.2.

      (vi) Smoke detectors shall be installed in return air ducts in accordance with requirements of NFPA 72 §5.14.4.2.2 and §5.14.5 and NFPA 90A, §6.4.2.2.

      (vii) Fire sprinkler system water flow switches shall be installed in accordance with requirements of NFPA 101, §9.6.2; NFPA 13, §6.9; and NFPA 72, §8.5.3.3.3.4.

      (viii) Sprinkler system valve supervisory switches shall be installed in accordance with the requirements of NFPA 72, §6.8.5.5.

      (ix) Audible alarm indicating devices shall be installed in accordance with the requirements of NFPA 101, §18.3.4, and NFPA 72, §7.4.

      (x) Visual fire alarm indicating devices which comply with the requirements of paragraph (1)(D) of this subsection and NFPA 72, §7.5, shall be provided.

      (xi) Devices for transmitting alarm for alerting the local fire brigade or municipal fire department of fire or other emergency shall be provided. The devices shall be listed for the fire alarm service by a nationally recognized laboratory, and be installed in accordance with such listing and the requirements of NFPA 72.

      (xii) A smoke detection system for spaces open to corridor(s) shall be provided when required by NFPA 101, §18.3.6.1.

      (xiii) A fire alarm signal notification which complies with NFPA 101, §9.6.3, shall be provided to alert occupants of fire or other emergency.

      (xiv) Wiring for fire alarm detection circuits and fire alarm notification circuits shall comply with requirements of NFPA 70, Article 760.

      (xv) A smoke detection system for elevator recall shall be located in elevator lobbies, elevator machine rooms and at the top of elevator hoist ways as required by NFPA 72, §6.15.3.10.

        (I) The elevator recall smoke detection system in new construction shall comply with requirements of American Society of Mechanical Engineers/American National Standards Institute (ASME/ANSI) A17.1, Safety Code for Elevators and Escalators, 2000 edition. The publications of the ASME/ANSI referenced in this section may be obtained by writing ASME/ANSI, United Engineering Center, 345 East 47th Street, New York, N.Y. 10017.

        (II) The elevator recall smoke detection system in existing hospitals shall comply with requirements of ASME/ANSI A17.3, Safety Code for Existing Elevators and Escalators, 2002 edition.

      (xvi) Smoke detectors for initiating smoke removal from windowless anesthetizing areas shall be provided in accordance with NFPA 99, §6.4.1.2.

      (xvii) Smoke detectors for initiating smoke removal from surgical suites shall be provided in accordance with NFPA 99, §6.4.1.3.

      (xviii) A smoke detection system for initiating smoke removal from atriums shall be located above the highest floor level of the atrium and at return intakes from the atrium in accordance with National Fire Protection Association 92B, Guide for Smoke Management Systems in Malls, Atria, and Large Areas, 2000 edition.

      (xix) Smoke detector(s) for shutdown of air handling units shall be provided. The detectors shall be installed in accordance with NFPA 90A, §6.4.3.

    (O) Telecommunications and information systems. Telecommunications and information systems central equipment shall be installed in a separate location designed for the intended purpose. Special air conditioning and voltage regulation shall be provided as recommended by the manufacturer.

    (P) Lightning protection systems. When installed, lightning protection systems shall comply with National Fire Protection Association 780, Standard for the Installation of Lightning Protection Systems, 2000 edition.


Source Note: The provisions of this §133.162 adopted to be effective June 21, 2007, 32 TexReg 3587