<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 25HEALTH SERVICES
PART 1DEPARTMENT OF STATE HEALTH SERVICES
CHAPTER 133HOSPITAL LICENSING
SUBCHAPTER IPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §133.165Building with Multiple Occupancies

  (1) Before a hospital is licensed in a building containing other licensed health care facilities, all the requirements of this chapter and the following requirements shall be met.

    (A) Construction of the building shall conform to the requirements of NFPA 101, Chapter 18, and the building shall be fully sprinklered.

    (B) The hospital shall be in one identifiable contiguous location and shall be separated (vertically and horizontally) with two-hour fire rated noncombustible construction from the other licensed health care facility and comply with the requirements of this chapter.

      (i) In no case may a person leave the hospital, traverse other licensed healthcare facilities, and then reenter the hospital to access the remaining portion of the hospital.

      (ii) A connecting stair(s) and elevator(s) within the building shall be provided to connect the vertical contiguous areas of the hospital.

      (iii) A hospital may not occupy two or more noncontiguous areas of other licensed healthcare facilities which contain intervening space of the other licensed healthcare facilities even if on the same floor.

      (iv) Access to the hospital shall be directly from a main lobby or an elevator lobby, if on an upper floor. The required means of egress from the hospital may be through the other licensed health care facility except not through a psychiatric hospital or a crisis stabilization unit or other area subject to locking.

        (I) Each licensed facility shall be identified with external signage at the building entrance.

        (II) Internal signage shall provide direction to the hospital.

      (v) The hospital shall have services and facilities separate from the other licensed health care facility. The required facilities shall be located within the proposed hospital proper.

      (vi) Common use of facilities using time-sharing concepts may be permitted on a case by case basis when the other health care facilities comply with the requirements contained in NFPA 101, Chapter 18, and §133.163 of this title, and provided this chapter and the other health care facility licensing regulations allow.

    (C) The equipment and systems required in each new hospital may be provided exclusively for the hospital or by contractual agreement with a licensed health care facility. The equipment and systems shall be in accordance with §133.162 of this title.

      (i) The following equipment and systems shall be provided for the exclusive use of the hospital, except where noted otherwise:

        (I) breaker serving the hospital. Where the hospital is served by the building's normal electrical system, the breaker serving the hospital shall originate in the main switchboard and shall be labeled, "Hospital Service - Contact Hospital Representative Prior to Opening Breaker";

        (II) electrical service for power and lighting. The hospital distribution panel board(s) shall be within the hospital;

        (III) type I essential electrical system. An electrical room for the distribution of type I essential electrical system shall be provided separate from the building electrical room. The hospital staff shall have access at all times to the essential electrical system room and the building's electrical room(s). The hospital shall be responsible for maintenance, testing and upkeep of the essential electrical system. When the existing essential electrical system owned and operated by the other licensed health care facility is nonconforming, the following options are available:

          (-a-) a separate conforming essential electrical system shall be provided in the new hospital; or

          (-b-) separate transfer switches connected to the existing on-site generator(s) shall be provided when adequate capacity is available and the other health care facility existing nonconforming system shall be corrected. Corrections shall be made in accordance with a plan of correction approved by the department;

        (IV) an emergency generator. An emergency generator may be shared when adequate capacity is available. Separate transfer switches shall be provided to serve the hospital and other licensed health care facilities. The hospital shall be the owner of the generator, have access to the generator at all times, and shall be responsible for maintenance, testing and upkeep of the generator;

        (V) emergency water storage requirement of §133.162(d)(4)(A)(i)(VIII) of this title shall be located within the hospital;

        (VI) a fire alarm system. When the other licensed health care facilities have a fire alarm control center or a main building alarm panel at the main lobby entrance, the hospital shall have an annunciator panel at a 24-hour staffed location. The hospital staff shall have access at all times to the main building fire alarm system panels and shall be responsible for verifying the maintenance and upkeep of such system;

        (VII) fireman's test valve for the fire sprinkler system;

        (VIII) air conditioning, heating and ventilating systems;

        (IX) medical piping systems with alarm. The medical gas supply sources may be shared provided the hospital is owner of the medical gas system source and is responsible for maintenance, testing and upkeep of the supply sources. The hospital and other occupancies shall have separate main supply shutoff valves. The hospital shall be provided with an alarm panel within the hospital that monitors the medical gas system supply source serving the other licensed health care facilities;

        (X) medical vacuum and medical air; and

        (XI) nurses calling systems.

      (ii) Where applicable, the following systems may be a part or extension of those in the existing licensed health care facility, provided the existing systems meet the requirements of this chapter for new construction:

        (I) drainage systems;

        (II) elevators. The hospital shall be served by the number and size of elevators cabs in accordance with §133.164 of this title (relating to Elevators, Escalators, and Conveyors). The elevators cab lighting, control, communication, and signal systems shall be connected to the life safety panel of the essential electrical system;

        (III) fire sprinkler systems. The new hospital may not be constructed in the other health care facility when the other health care facility is not fully sprinklered. The new hospital and the other health care facility shall be fully sprinklered;

        (IV) stand pipe systems;

        (V) steam systems. The hospital is responsible for providing all backup systems (such as boilers) as required in this chapter;

        (VI) domestic water supply systems, hot and cold; and

        (VII) mechanical chilled and hot water systems.

  (2) When hospitals and psychiatric hospitals share one building, the building systems and equipment may be shared in accordance with subsection (a)(5)(B) of this section, or be provided separately.

(c) Hospitals in buildings with nonhealth care occupancies.

  (1) General. Before a hospital is licensed in a building also containing occupancies other than health care occupancies, all requirements of this chapter and the following requirements shall be met.

    (A) Construction of the building shall conform to the requirements of NFPA 101, Chapter 18, and the building shall be fully sprinklered.

    (B) The hospital shall be in one identifiable contiguous location and shall be separated (vertically and horizontally) with two-hour fire rated noncombustible construction from the other occupancies.

      (i) In no case may a person leave the hospital, traverse other occupancies, and then reenter the hospital to access the remaining portion of the hospital.

      (ii) A connecting stair(s) and elevator(s) within the building shall be provided to connect the vertical contiguous areas of the hospital.

      (iii) A hospital may not occupy two or more noncontiguous areas of other occupancies which contain intervening space of the other occupancies even if on the same floor.

    (C) Access to the hospital shall be through a dedicated hospital lobby or from the building's main lobby. The building's main lobby shall be part of the hospital and shall comply with the requirements of §133.162 of this title.

      (i) External signage shall be provided at the building entrance which identifies the hospital.

      (ii) Internal signage shall be provided to give directions to the hospital.

    (D) The required means of egress from the hospital shall be independent of and shall not traverse through the other occupancies.

Cont'd...

Next Page Previous Page

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page