<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 25HEALTH SERVICES
PART 1DEPARTMENT OF STATE HEALTH SERVICES
CHAPTER 117END STAGE RENAL DISEASE FACILITIES
SUBCHAPTER HPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §117.102Construction Requirements for a New End Stage Renal Disease Facility

    (B) Air handling fans and smoke damper controls may be interconnected so that closing of smoke dampers will not damage the ducts.

    (C) Use of frangible devices for shutting smoke dampers is not permitted.

  (18) Only fire damper and smoke damper assemblies integral with sleeves and listed for the intended purpose shall be acceptable.

  (19) Unobstructed access to duct openings in accordance with NFPA 90A, §4.3.4, shall be provided in ducts within reach and sight of every fire damper, smoke damper and smoke detector. Each opening shall be protected by an internally insulated door which shall be labeled externally to indicate the fire protection device located within.

  (20) Controls for restarting fans may be installed for convenient fire department use to assist in evacuation of smoke after a fire is controlled, provided that provisions are made to avoid possible damage to the system because of closed dampers. To accomplish this, smoke dampers shall be equipped with remote control devices.

(h) All piping systems and plumbing fixtures shall be designed and installed in accordance with the requirements of the National Standard Plumbing Code Illustrated published by the National Association of Plumbing-Heating-Cooling Contractors (PHCC), 2003 edition, and this paragraph. The National Standard Plumbing Code may be obtained by writing or calling the PHCC at the following address or telephone number: Plumbing-Heating-Cooling Contractors, Post Office Box 6808, Falls Church, Virginia 22046; telephone (800) 533-7694.

  (1) Piping systems.

    (A) Water service pipe to point of entrance to the building shall be brass pipe, copper tube (not less than type M when buried directly), copper pipe, cast iron water pipe, galvanized steel pipe, or approved plastic pipe. Domestic water distribution system piping within buildings shall be brass pipe, copper pipe, copper tube, or galvanized steel pipe. Piping systems shall be designed to supply water at sufficient pressure to operate all fixtures and equipment during maximum demand.

      (i) Each water service main, branch main, riser, and branch to a group of fixtures shall be equipped with accessible and readily identifiable shutoff valves. Stop valves shall be provided at each fixture.

      (ii) Backflow preventers (vacuum breakers) shall be installed on hose bibbs, laboratory sinks, janitor sinks, and on all other fixtures to which hoses or tubing can be attached. Backflow preventers are not required for hoses that are directly connected to the dialysis machines.

      (iii) Flush valves installed on plumbing fixtures shall be of a quiet operating type, equipped with silencers.

      (iv) Hot water distribution systems for patient care areas shall be under constant recirculation to provide continuous hot water at each hot water outlet. Nonrecirculated fixtures branch piping shall not exceed 25 feet in length. Tankless water system may be used at point of use.

      (v) Water heating equipment shall have sufficient capacity to supply water for clinical, use.

      (vi) Water temperatures shall be measured at hot water point of use, and shall be between 105 - 120 degrees Fahrenheit.

      (vii) The domestic hot water system shall make provisions to limit the amount of Legionella bacteria and opportunistic waterborne pathogens.

      (viii) Domestic water storage tank(s) shall be fabricated of corrosion-resistant metal or lined with noncorrosive material. When potable water storage tanks (hot and cold) are used, the water shall be used and replenished. Water shall not be stored in tanks for future use unless the water is tested weekly for contaminates/bacteria.

      (ix) Purified water distribution system piping shall be task specific and include, but not necessarily be limited to, polypropylene (PP), polyvinylidene fluoride (PVDF) or polyvinyl chloride (PVC) pipe. Final installed purified water system piping assemblies shall be UL approved and fully comply with applicable American Society for Testing and Materials (ASTM) Fire Resistant/Smoke Density requirements. The applicable documents are available from ASTM International, 100 Barr Harbor Drive, Post Office Box C700, West Conshohocken, Pennsylvania 19428-2959.

    (B) When fire sprinkler systems are required and provided in an ESRD facility, the fire sprinkler systems shall be designed, installed, and maintained in accordance with the requirements of NFPA 13, and shall be certified as required by §117.105(c)(1)(C) of this title (relating to Construction, Inspections, and Approval of Project).

    (C) Main storage of medical gases may be outside or inside the ESRD facility in accordance with NFPA 99, §5.1.

    (D) Steam and hot water systems.

      (i) When boilers are used the boilers shall have the capacity, based upon the net ratings as published in The I-B-R Ratings Book for Boilers, Baseboard Radiation and Finned Tube (commercial) by the Hydronics Institute Division of GAMA, to supply the normal requirements of all systems and equipment. The document published by the Hydronics Institute Division of GAMA as referenced in this rule may be obtained by writing or calling the Hydronics Institute Division of GAMA at 35 Russo Place, P.O. Box 218, Berkeley Heights, New Jersey 07922, telephone (908) 464-8200.

      (ii) Boiler feed pumps, heating circulating pumps, condensate return pumps, and fuel oil pumps shall be connected and installed to provide normal and standby service.

      (iii) Supply and return mains and risers of cooling, heating, and process steam systems shall be valved to isolate the various sections of each system. Each piece of equipment shall be valved at the supply and return ends except that vacuum condensate returns need not be valved at each piece of equipment.

    (E) Drainage systems.

      (i) All underground building drains shall be: cast iron soil pipe, hard temper copper tube (drain-waste-vent (DWV) or heavier), acrylonitrile-butodiene-styrene (ABS) plastic pipe (DWV Schedule 40 or heavier), polyvinyl chloride (PVC) plastic pipe (DWV Schedule 40 or heavier), or extra strength vitrified clay pipe (VCP) with compression joints or couplings with at least 12 inches of earth cover.

      (ii) Soil stacks, drains, vents, waste lines, and leaders installed above ground within buildings shall be DWV weight or heavier and shall be: copper pipe, copper tube, plastic pipe (DWV scheduled 40 or heavier) cast iron pipe, or galvanized iron pipe.

      (iii) Drainage systems for chemical wastes (acids and other corrosive materials) shall be provided. Materials acceptable for chemical waste drainage systems shall include chemically resistant glass pipe, high silicone content cast iron pipe, VCP, CPVC plastic pipe, or plastic lined pipe.

      (iv) Thermal insulation for piping systems and equipment shall be provided for the following:

        (I) boilers, smoke breeching, and stacks;

        (II) steam supply and condensate return piping;

        (III) hot water piping and all hot water heaters, generators, converters, and storage tanks;

        (IV) chilled water, refrigerant, other process piping, equipment operating with fluid temperatures below ambient dew point, and water supply and drainage piping on which condensation may occur. Insulation on cold surfaces shall include an exterior vapor barrier; and

        (V) other piping, ducts, and equipment as necessary to maintain the efficiency of the system.

      (v) Flame spread shall not exceed 25 and smoke development rating shall not exceed 50 for pipe insulation as determined by an independent testing laboratory in accordance with National Fire Protection Association 255, Standard Method of Test of Surface Burning Characteristics of Building Materials, 2000 Edition. Smoke development rating for pipe insulation located in environmental air areas shall not exceed 50.

      (vi) Asbestos insulation shall not be used.

  (2) Plumbing fixtures shall be made of nonabsorptive acid-resistant materials and shall comply with the recommendations of the National Standard Plumbing Code and this paragraph.

    (A) All sinks used by medical and nursing staff and all lavatories used by patients shall be trimmed with valves which can be operated without the use of hands. Blade handles used for this purpose shall not be less than four inches in length. Single lever or wrist blade devices may be used.

    (B) Clinical sinks shall have an integral trap in which the upper portion of a visible trap seal provides a water surface.

    (C) All plumbing fixtures and equipment shall be designed and installed to prevent the back-flow or back-siphonage of any material into the water supply. The over-the-rim type water inlet shall be used wherever possible. Vacuum-breaking devices shall be properly installed when an over-the-rim type water inlet cannot be utilized.

    (D) Each drinking fountain shall be designed so that the water issues at an angle from the vertical, the end of the water orifice is above the rim of the bowl, and a guard is located over the orifice to protect it from lip contamination.

Cont'd...

Next Page Previous Page

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page