<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 30ENVIRONMENTAL QUALITY
PART 1TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
CHAPTER 317DESIGN CRITERIA PRIOR TO 2008
RULE §317.4Wastewater Treatment Facilities

properly. For facilities with a design capacity greater than or equal to 0.5 mgd and in which recirculation is included in design computations for BOD5 removal, recirculation shall be provided by variable speed pumps and a method of conveniently measuring the recycle flow rate shall be provided.

    (F) Surface loading. The engineering report shall include calculations of the maximum, design, and minimum surface loadings on the filter(s) in terms of mgd/acre of filter area per day (for the initial year and design year). Hydraulic loadings of filters with crushed rock, slag, or similar media shall not exceed 40 mgd/acre based on design flow. The minimum surface loading shall not be less than 1.0 mgd/acre. Loadings on synthetic (manufactured or prefabricated) filter media shall be within the ranges specified by the manufacturer.

  (6) Underdrain system.

    (A) Underdrains. Underdrains with semicircular inverts or equivalent shall be provided and the underdrainage system shall cover the entire floor of the trickling filter. Inlet openings into the underdrains shall provide an unsubmerged gross combined area of at least 15% of the surface area of the filter.

    (B) Hydraulics. Underdrains and the filter effluent channel floor shall have a minimum slope of 1.0%. Effluent channels shall be designed to produce a minimum velocity of two feet per second at average daily flow rate of application to the trickling filter.

    (C) Drain tile. Underdrains for rock media trickling filters shall be either vitrified clay or precast reinforced concrete. The use of half tile for underdrain systems is unacceptable.

    (D) Corrosion. Underdrain systems for synthetic media trickling filters shall be resistant to corrosion.

    (E) Ventilation. The underdrain system, effluent channels, and effluent pipe shall be designed to permit free passage of air. Drains, channels, and effluent pipes shall have a cross-sectional area such that not more than 50% of the cross-sectional area will be submerged at peak flow plus recirculation. Provision shall be made in the design of the effluent channels to allow the possibility of increased hydraulic loading. The underdrain system shall provide at least one square foot of ventilating area (vent stacks, ventilating holes, ventilating ports) for every 250 square feet of rock media filter plan area. Ventilating area for synthetic media underdrains will be provided as recommended by the manufacturer, but shall be at least one square foot for every 175 square feet of synthetic media trickling filter plan area.

    (F) Maintenance. All flow distribution devices, underdrains, channels, and pipes shall be designed so they may be maintained, flushed, and properly drained. The units shall be designed to facilitate cleaning of the distributor arms. A gate shall be provided in the wall to facilitate rodding of the distributor arms.

    (G) Flooding. Provisions shall be made to enable flooding of the trickling filter for filter fly control; however, consideration will be given by the commission to alternate methods of filter fly control provided that the effectiveness of the alternate method is verified at a full scale installation. This information shall be submitted with the plans and specifications.

    (H) Flow measurements. Means shall be provided to measure flow to the filter and recirculation flows.

(f) Rotating biological contactors (RBC).

  (1) General.

    (A) RBC units shall be covered and ample ventilation provided. Working clearance of approximately 30 inches should be provided within the cover unless the covers are removable, utilizing equipment normally available on site. Enclosures shall be constructed of a suitable corrosion-resistant material.

    (B) The design of the RBC media shall provide for self-cleaning action due to the flow of water and air through the media. Careful selection of media that will not entrap solids should be made.

    (C) The RBC tank should be designed to minimize zones in which solids will settle out.

    (D) RBC media should be selected which is compatible with the wastewater. Selection of media can be critical where the wastewater has an industrial waste portion which either significantly increases the wastewater temperature or contains a chemical constituent which may decrease the life of the RBC media.

  (2) Design.

    (A) Pretreatment. RBC units shall be preceded by pretreatment to remove any grit, debris, and excess oil and grease which may hinder the treatment process or damage the RBC units. The design engineer should consider primary clarifiers with scum and grease collecting devices, fine screens, and oil separators. For wastes with high hydrogen sulfide concentrations, preaeration shall be provided.

    (B) Organic loading. The organic loading for the design of RBC units shall be based on total BOD5 in the waste going to the RBC, including any side streams. The design engineer should consider a maximum loading rate of five pounds BOD5 per day per 1,000 square feet of media in any stage, depending on the character of the influent wastewater. The maximum loading rate shall not exceed eight pounds BOD5 per day per 1,000 square feet of media in any stage. The design engineer should also consider the ratio of soluble BOD5 to total BOD5 and its possible effect on required RBC media area. Allowable organic loading for the entire RBC system shall not exceed the following criteria.

Attached Graphic

    (C) Stages of treatment. The number of RBC units in series (stages) for BOD removal only shall be a minimum of three stages. For BOD removal and nitrification, there shall be a minimum of four stages. If the plant is designed with less stages than noted in the previous sentences of this subparagraph, the engineer must provide justification based on either full-scale operating facilities or pilot unit operational data. Any pilot unit data used in the justification must take into consideration an appropriate scale-up factor.

    (D) Drive system. The drive system for each RBC unit shall be selected for the maximum anticipated media load. A variable speed system should be considered to provide additional operator flexibility. The RBC units may be mechanically driven or air driven.

      (i) Mechanical drives.

        (I) Each RBC unit shall have a positively connected mechanical drive with motor and speed reduction unit to maintain the required rpm.

        (II) A fully assembled spare mechanical drive unit for each size shall be provided on-site.

        (III) Supplemental diffused air should be considered for mechanical drive systems to help remove excess biomass from the media and to help maintain the minimum dissolved oxygen concentration.

      (ii) Air drives.

        (I) Each RBC unit shall have air diffusers mounted below the media and off-center from the vertical axis of the RBC unit. Air cups mounted on the outside of the media shall collect the air to provide the driving force and maintain the required rpm.

        (II) Blowers shall provide enough air flow for each RBC unit plus additional capacity to double the air flow rate to any one unit while the others are running normally.

        (III) The blowers shall be capable of providing the required air flow with the largest unit out of service.

        (IV) The air diffuser line to each unit shall be mounted such that it can be removed without draining the tank or removing the RBC media.

        (V) An air control valve shall be installed on the air diffuser line to each RBC unit.

    (E) Dissolved oxygen. The RBC plant shall be designed to maintain a minimum dissolved oxygen concentration of one milligram per liter at all stages during the peak organic flow rate. Supplemental aeration may be required.

    (F) Nitrification. The design of an RBC plant to achieve nitrification is dependent upon a number of factors, including the concentration of ammonia in the influent, effluent ammonia concentration required, BOD5 removal required, minimum operational temperatures, and ratio of peak to design hydraulic flow. Each of these factors will impact the number of stages of treatment required and the allowable ammonia nitrogen loading (lb NH3 /day/1,000 ft2 media) required to achieve the desired levels of nitrification for a given facility. The engineer shall submit appropriate data supporting the design.

    (G) Design flexibility. The designer of an RBC plant should consider provisions to provide additional operational flexibility such as controlled flow to multiple first stages, alternate flow and staging arrangements, removable baffles between stages, and provision for step feed and supplemental aeration.

(g) Activated sludge facilities.

Cont'd...

Next Page Previous Page

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page