<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 30ENVIRONMENTAL QUALITY
PART 1TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
CHAPTER 217DESIGN CRITERIA FOR DOMESTIC WASTEWATER SYSTEMS
SUBCHAPTER GFIXED FILM AND FILTRATION UNITS
RULE §217.182Trickling Filters--General Requirements

    (A) The design of a trickling filter must include a mechanism to maintain minimum recirculation during periods of low flow to ensure that the biological growth on the filter media remains active at all times.

    (B) For all trickling filters with continuous recirculation, the design must include the minimum recirculation rate in the evaluation of the efficiency of the filter.

    (C) Minimum flow to the filters must be equal to or greater than 1.0 million gallons per day per acre of filter aerial surface and must ensure the proper operation of the distribution nozzles.

    (D) The minimum flow rate for a trickling filter design using hydraulically driven distributors must keep rotary distributors turning at the minimum design rotational velocity.

    (E) For a wastewater treatment facility designed with a design flow equal to or greater than 0.4 million gallons per day and recirculation for BOD5 removal, the recirculation system must include variable speed pumps and a method of conveniently measuring the recycle flow rate.

  (2) Compensatory Recirculation.

    (A) The design of a trickling filter must provide compensatory recirculation to supplement influent flow if design and flushing dosing intensities are not achieved solely by the control of distributor operation.

    (B) Controls for the distributor speed and recycle pumping rate must provide optimum dosing intensity under all anticipated influent flow conditions.

  (3) Process Calculations. The engineering report must:

    (A) provide design details about removal of the remaining organic matter by recirculation;

    (B) identify the effect of dilution of the influent on the rate of diffusion of dissolved organic substrates into the biofilm; and

    (C) identify the effect of reduced influent concentrations on reaction rates in each section of a filter having first order kinetics.

  (4) Recirculation Rate. A recirculation rate may exceed four times the design flow if calculations to justify the higher rate are included in the engineering report.

  (5) Configuration.

    (A) In a wastewater treatment facility with influent that has constant organic loadings, direct recirculation of unsettled trickling filter effluent must be used.

    (B) A design must ensure that the distributor nozzles can handle the recirculated sloughed biofilm.

    (C) In a wastewater treatment facility with variable influent organic loadings, effluent must recirculate from a final clarifier to either a primary clarifier or a trickling filter to equalize organic loading.

(j) Average Hydraulic Surface Loading.

  (1) The engineering report must include calculations of the maximum, design, and minimum surface loadings on the trickling filters in terms of million gallons per acre of filter area per day for the flow expected in the initial year and at full capacity.

  (2) The average hydraulic surface loadings of a trickling filter with crushed rock, slag, or similar media:

    (A) must not exceed 40 million gallons per day per acre based on design flow, except in roughing applications;

    (B) must not be less than 1.0 million gallons per day per acre; and

    (C) must be within the ranges specified by the manufacturer.

(k) Underdrain System Design.

  (1) A trickling filter must include an underdrain with semicircular inverts that cover the entire floor of the trickling filter.

  (2) An underdrain must be constructed of vitrified clay or pre-cast reinforced concrete.

  (3) An underdrain constructed of half tile is prohibited.

  (4) Underdrain inlet openings must have a gross cross-sectional area greater than 15% of a trickling filter's surface area.

  (5) A modular synthetic media design must be supported above a trickling filter floor by beams and grating with support and clearances in accordance with the trickling filter media manufacturer's recommendations. The manufacturer's recommendations must be included in the engineering report.

(l) Underdrain Slopes.

  (1) An underdrain and trickling filter effluent channel floor must have a minimum slope of 1%.

  (2) An effluent channel must produce a minimum velocity of 2.0 feet per second at the design flow rate to a trickling filter.

  (3) The floor of a new trickling filter using stackable modular or synthetic media must slope toward a drainage channel at a slope of at least 1% and not more than 5%, based on filter size and hydraulic loading.

(m) Passive Ventilation.

  (1) The effluent channels and effluent pipes of an underdrain system or a synthetic media support structure must permit free passage of air.

  (2) Any drain, channel, or effluent pipe must have a cross-sectional area with not more than 50% of the area submerged at peak flow plus recirculation.

  (3) The effluent channels must accommodate the specified flushing hydraulic dosing intensity and allow the possibility of increased hydraulic loading.

  (4) A passive ventilation system may include an extension of an underdrain through a trickling filter sidewall, a ventilation opening through a sidewall, or an effluent discharge conduit designed as a partially full flow pipe or an open channel.

  (5) A vent opening through a trickling filter wall must include hydraulic closure to allow flooding of a trickling filter for nuisance organism control.

  (6) A passive ventilation design must provide at least 2.5 square feet of ventilating area per 1,000 pounds of primary effluent BOD5 per day.

  (7) An underdrain system for a rock media filter must provide at least 1.0 square foot of ventilating area for every 250 square feet of the trickling filter basin surface area.

  (8) The minimum required ventilating area for a synthetic media underdrain is the area recommended by the manufacturer. The manufacturer's recommendations must be included in the engineering report.

  (9) The ventilating area must be equal to the greater of 1.0 square foot per 175 square feet of synthetic media area or 2.6 square feet per 1,000 cubic feet of media volume.

(n) Forced Ventilation.

  (1) Forced ventilation is required for a trickling filter designed for:

    (A) nitrification;

    (B) a trickling filter design with a media depth in excess of 6.0 feet; and

    (C) a location where seasonal or diurnal temperatures do not provide sufficient difference between the ambient air and wastewater temperatures to sustain passive ventilation of one cubic foot of air per square foot of trickling filter area per minute.

  (2) A design must specify the minimum airflow for forced ventilation and optimized process performance, and the engineering report must include all calculations associated with this determination.

  (3) The design of a down-flow forced ventilation system must include a provision for:

    (A) the removal of entrained droplets; or

    (B) the return of air containing entrained moisture to the top of a trickling filter; and

    (C) a reversible fan or other mechanism to reverse the airflow when a wide temperature difference between the ambient air and wastewater creates strong updrafts.

  (4) A ventilation fan and the associated controls must withstand flooding of a trickling filter without sustaining damage.

  (5) The following equation and the values in Table G.3. in Figure: 30 TAC §217.182(n)(5) determine the minimum airflow rate for forced ventilation.

Attached Graphic

(o) Maintenance.

  (1) Cleaning and Sloughing.

    (A) A flow distribution device, an underdrain, a channel, and a pipe must allow for maintenance, flushing, and drainage.

    (B) A trickling filter system must hydraulically accommodate the specified flushing hydraulic dosing intensity and must facilitate cleaning and rodding of the distributor arms.

    (C) A trickling filter system must prevent recirculation of sloughed biomass in pieces larger than the distributor nozzle openings or the filter media voids.

  (2) Nuisance Organism Control. A trickling filter system must control nuisance organisms by operation of trickling filters at proper design dosing intensities, with periodic flushing at higher dosing intensities.

    (A) Filter Flies.

      (i) The structural and hydraulic design of a trickling filter must enable flooding of the trickling filter for fly control.

Cont'd...

Next Page Previous Page

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page