<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 30ENVIRONMENTAL QUALITY
PART 1TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
CHAPTER 217DESIGN CRITERIA FOR DOMESTIC WASTEWATER SYSTEMS
SUBCHAPTER FACTIVATED SLUDGE SYSTEMS
RULE §217.157Membrane Bioreactor Systems

      (vi) chlorinated polyethylene (CPE).

    (C) The nominal pore size used in an MBR for microfiltration membranes must be at least 0.10 micrometers (microns) but not more than 0.4 microns.

    (D) The nominal pore size used in an MBR for ultrafiltration must be at least 0.02 microns but not more than 0.10 microns.

    (E) Any chemical used for cleaning must not adversely affect the membrane material.

  (7) Membrane Design Parameters.

    (A) MBRs must be designed for:

      (i) an average daily net flux rate equal to or less than 15 gallons per day per square-foot of membrane area;

      (ii) a peak daily net flux rate equal to or less than 1.25 times the average daily net flux rate; and

      (iii) a two-hour peak net flux rate equal to or less than 1.5 times the average daily net flux rate.

    (B) The executive director may approve larger net flux rates if the rates are substantiated to the executive director's satisfaction with a pilot study or data from a similar wastewater treatment facility.

    (C) An MBR system with a peak flow rate that is greater than 2.5 times the average daily flow must use an equalization basin, off-line storage, or reserve membrane capacity to accommodate the higher peak flow.

    (D) Hollow Fiber Transmembrane Pressure (TMP).

      (i) The operational TMP of a hollow fiber MBR system must be at least 2.0 pounds per square inch (psi) but not more than 10.0 psi.

      (ii) The TMP of a hollow fiber MBR system must not exceed 12.0 psi.

    (E) Flat Plate TMP.

      (i) The operational TMP of a flat plate MBR system must be at least 0.3 psi but not more than 3.0 psi.

      (ii) The TMP of a flat plate MBR system must never exceed 4.5 psi.

    (F) Tubular, Out of Basin TMP.

      (i) The operational TMP of a tubular, out of basin MBR system must be at least 0.5 psi but not more than 5.0 psi.

      (ii) The TMP of a tubular, out of basin MBR system must never exceed 10.0 psi.

  (8) Supporting Data. An owner must provide pilot study reports or data from a similar wastewater treatment facility for a wastewater treatment facility that is either:

    (A) required to meet stricter standards than in Table F.7. in Figure: 30 TAC §217.157(c)(1); or

    (B) designed to operate outside normal operating parameters defined within this section.

      (i) A pilot study must be conducted for at least 30 days after the initial start-up and acclimation period.

      (ii) A pilot study must be designed to evaluate the membrane performance under actual operational conditions, including flow variations and influent wastewater characteristics.

      (iii) The treatment and pretreatment processes evaluated in a pilot study or similar wastewater treatment facility must be equivalent to the processes that will be used in the wastewater treatment facility.

      (iv) The results of the pilot study must include the following recommendations:

        (I) net flux rates for design flow and peak flow;

        (II) average and maximum transmembrane pressure;

        (III) cleaning and backwash intervals;

        (IV) expected percent chemical recovery after chemical cleaning;

        (V) dissolved oxygen concentrations for reactors and membrane basins;

        (VI) MLSS concentrations for reactors and membrane basins;

        (VII) SRTs for reactors and membrane basins; and

        (VIII) expected effluent concentrations of conventional pollutants and nutrients, including the pollutants and nutrients that will be limited or monitored in the wastewater treatment facility's wastewater permit.

  (9) Redundancy.

    (A) A wastewater treatment facility must be able to operate at normal operating parameters and conditions for design flow with the largest MBR unit or train out of service.

    (B) Acceptable methods of providing redundancy are additional treatment trains, additional treatment units, or storage. The engineering report must include calculations that demonstrate adequate redundancy within the wastewater treatment facility.

  (10) Other Components.

    (A) Mixers.

      (i) Unaerated (deoxygenation, pre/post anoxic, and anaerobic) zones must have a submersible mixing system, or an alternative mixing system that has been approved in writing by the executive director.

      (ii) Coarse bubble air diffusers may be used for mixing in a pre-anoxic tank.

    (B) Scum and Foam Handling. An MBR must control scum and foam so that scum or foam does not interfere with treatment, and must prevent unauthorized discharge of scum or foam from a treatment unit.

    (C) Cranes and Hoists. A crane, hoist, or other process or mechanism approved in writing by the executive director must be provided for periodic cleaning and maintenance of the membranes.

  (11) Disinfection.

    (A) An owner may request and the executive director may approve, in writing, decreased ultraviolet light or chlorine dosing requirements for MBR effluent.

    (B) the design for ultraviolet light disinfection for MBR effluent that is based on greater than 75% transmissivity must be justified in the engineering report.

(e) MBR operation.

  (1) Membrane cleaning. The following methods may be used to clean membranes:

    (A) air scouring of at least 0.01 standard cubic feet per minute of air per square foot of membrane area, but not more than 0.04 standard cubic feet per minute of air per square foot of membrane area;

    (B) a mixture of air scouring as described in subparagraph (A) of this paragraph and mixed liquor jet feed;

    (C) back-flushing;

    (D) relaxation; or

    (E) chemical cleaning.

  (2) Operational Control Parameters.

    (A) In-line continuous turbidity monitoring of filtrate from each membrane train or cassette must be provided for operational control and indirect membrane integrity monitoring. An alarm must be provided to notify the wastewater treatment facility operator of turbidity greater than or equal to 1.0 nephelometric turbidity units (NTU).

    (B) An owner must follow the manufacturer's recommended frequency for MBR component inspection, testing, and maintenance. The manufacturer's recommended inspection, testing, and maintenance procedures and frequencies must be included in the wastewater treatment facility's operation and maintenance manual.

    (C) An owner must provide a wastewater treatment facility operator access to any specialized tool necessary for the operation or maintenance of an MBR system. A description of all specialized tools and instructions for their use must be included in the operation and maintenance manual for the wastewater treatment facility.

  (3) Control instrumentation. A wastewater treatment facility must have the ability to operate in full manual mode.

(f) Chemical Use and Disposal.

  (1) The chemicals used in treatment and maintenance must not harm the MBR system or interfere with treatment.

  (2) The chemicals used in treatment and maintenance, including concentrations of the chemicals and chemical disposal methods, must be identified in the engineering report.

(g) Training.

  (1) The individuals trained to operate an MBR system must be familiar with the sequencing and set points of all operations and actions typically controlled by automated systems and be able to identify and respond to irregularities.

  (2) The operation and maintenance manual must include instructions on how to operate the MBR in manual mode.

(h) Warranty and Bonds.

  (1) All membranes must have a warranty of at least five years.

  (2) The executive director may require a performance bond that meets the requirements of §217.7(b)(2)(E) of this title.


Source Note: The provisions of this §217.157 adopted to be effective August 28, 2008, 33 TexReg 6843; amended to be effective December 4, 2015, 40 TexReg 8254

Previous Page

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page