RULE §133.163Spatial Requirements for New Construction

      (iii) When medical, surgical, and coronary critical care services are combined in one CCU suite, at least 50% of the beds shall be located in private rooms. (Note: Medical/surgical patients may utilize open areas or private critical care rooms as needed and available but, insofar as possible, coronary patients should not be accommodated in open ward areas.)

    (D) PCCU. When a PCCU is provided, the unit shall comply with the requirements contained in subparagraph (B) of this paragraph and the following.

      (i) The PCCU may be an open ward, private rooms, or combination of both. When an open ward plan is used, one private room is required for each 10 beds or fraction thereof.

      (ii) In a multiple-bassinet/crib (sleeping unit) room/ward the clearance between the side of the sleeping unit and a wall/partition shall be a minimum of five feet. The clearance between sides of sleeping units shall be a minimum of eight feet. The minimum distance at the foot of the bassinet shall not be less than ten feet for single load area/room or sixteen feet for double load area/room. Four feet of the passage space requirement at the foot of the bassinet may be shared between two bassinets. The fixed and moveable cabinets and shelves shall not encroach upon the bassinet/crib clear floor space/area. The requirements of this clause are illustrated in Table 8, Diagram K of §133.169(h) of this title.

      (iii) A sleeping space shall be provided for parents who spend long hours with the patient. This space may be within the patient room or separate from the patient area but shall be in communication with the PCCU staff.

      (iv) Hand washing fixtures with hands-free operable controls shall be provided in each room near the entrance of the room, and in open wards at a minimum ratio of one fixture to each three cribs, beds or bassinets. Hand washing fixtures shall be sized to contain splashing.

      (v) A room shall be provided for private discussions and shall be located within, or convenient to, the PCCU. The multipurpose room noted in subparagraph (F)(v) of this paragraph will meet this requirement if conveniently located.

      (vi) Storage space for infant formula shall be provided. This functional space may be outside the PCCU but shall be available for use at all times.

      (vii) Storage cabinets or closets for toys and games shall be provided within the unit.

      (viii) Storage area for cots, bed linens, and other items needed for overnight accommodation of parents shall be provided in the general location of sleeping accommodations.

      (ix) An examination/treatment room with a minimum of 120 square feet of clear floor area shall be located in or near the PCCU suite. The room shall contain a hand washing fixture with hands-free operable controls, storage facilities, counter, or shelf space for writing. This requirement does not apply when all patient rooms are private rooms.

    (E) Additional service spaces. The following additional service spaces shall be immediately available within each type of CCU(s). These may be shared by more than one CCU (unless otherwise noted) provided that direct access is available from each.

      (i) Securable closets. Securable closets or cabinet compartments for the personal effects of nursing personnel, located in or near the nurse station, shall be provided. At a minimum, these shall be large enough for purses and billfolds. Coats may be stored in closets or cabinets on each floor or in a central staff locker area.

      (ii) Charting and dictation area(s) for physicians. Space for recording, record storage and reviews shall be provided near cribs, beds or bassinets. Dictation space may be in a separate room or alcove. Suitable space shall be provided when computers are used for the clinical records.

      (iii) X-ray viewing area. Each type of CCU shall be provided with an X-ray viewing area and film illuminators for handling at least four films simultaneously. When the entire CCU suite is provided with digital imaging system capabilities, a minimum of two X-ray film illuminator viewers shall be provided. The film illuminators shall be mounted within the central area of the suite.

      (iv) Nourishment station. The nourishment station shall contain a sink with hands-free operable controls, work counter, refrigerator, cabinets, and not be located in the medication room or the clean workroom. Space shall be included for temporary holding of unused or soiled dietary trays.

      (v) Ice machine. The ice machine shall provide ice for treatment and patient use. Ice-making equipment for treatment may be in the clean workroom or the nourishment station.

      (vi) Equipment storage. In addition to above, twenty square feet of equipment storage shall be provided for each patient station. These storage areas shall be out of the way of the corridor traffic.

      (vii) Stretcher storage alcove. The alcove provided for stretcher or bassinet storage shall be located out of direct line of traffic.

      (viii) Clean workroom. The room shall contain a work counter, a hand washing fixture with hands-free operable controls, and storage facilities for clean and sterile supplies.

      (ix) Clean linen storage. There shall be a designated area for clean linen storage. This may be within a clean workroom, a separate closet, or an approved distribution system. If a closed cart system is used, storage of the cart may be in an alcove.

      (x) Soiled workroom. The soiled workroom shall contain a work counter, a clinical sink with hands-free operable controls or equivalent flushing rim type fixture with hot and cold mixing faucet, separate hand washing facilities, and separate waste and soiled linen receptacles.

      (xi) Soiled holding room. When provided, soiled holding rooms used only for temporary holding of soiled material may omit the clinical sink and work counter.

      (xii) Housekeeping room. A housekeeping room shall be provided within or immediately adjacent to the CCU. It shall not be shared with other nursing units or departments.

    (F) Other required areas/rooms. The following areas/rooms shall be provided and may be located outside the unit if conveniently accessible.

      (i) Waiting space. A visitors' waiting space shall be provided with toilet facility(ies), public telephone(s), and drinking fountain(s). One waiting space may serve other CCUs.

      (ii) Offices. Room(s) shall be provided for critical care medical and nursing management and administrative personnel. The offices shall be large enough to permit consulting with members of the critical care team and visitors. The offices shall be linked with the unit by telephone or an intercommunications system.

      (iii) Staff lounge. A staff lounge shall include toilet facilities with a hand washing fixture with hands-free operable controls. The lounge(s) shall be located so that staff may be recalled quickly to the patient area in emergencies. One lounge may serve multiple CCUs when the lounge is adjacent to the units. Toilet facilities may be shared as long as privacy is maintained for changing areas.

      (iv) On-call rooms. Physicians and other staff on 24-hour on-call work schedules shall be provided with sleeping rooms with access to a shower(s), toilet(s), and lavatory(ies). If on-call room(s) are not within the CCU served, a dedicated telephone or intercom system shall connect the on-call room(s) to the CCU(s).

      (v) Multipurpose room(s). A multipurpose room for staff, patients, and patients' families for patient conferences, reports, education, and training sessions shall be provided. This room(s) must be accessible to each nursing unit.

      (vi) A consultation room shall be provided, if not provided elsewhere in the unit.

  (2) Details and finishes. Details and finishes shall be in accordance with §133.162(d)(2) of this title and this paragraph.

    (A) Details.

      (i) At least one door to a CCU room shall be not less than four feet wide (41.5 inches clear width) and arranged to minimize interference with movement of beds and large equipment.

      (ii) Sliding doors in CCUs shall not have floor tracks at the latch side of the sliding panel, have hardware that minimizes jamming possibilities, and be in accordance with §133.162(d)(2)(A)(vi) of this title.

      (iii) Glazing in viewing panels shall be safety glass, wire glass, or clear plastic.

      (iv) Noise control and sound attenuation in an open ward environment shall be a design factor and meet the requirements contained in Table 1 of §133.169(a) of this title.

      (v) Recreation rooms, exercise rooms, equipment rooms, and similar spaces where impact noises may be generated shall not be located directly over CCU(s), unless special provisions are made to minimize such noise.

    (B) Finishes.

      (i) Flooring used in soiled workrooms shall be of the seamless type as required by §133.162(d)(2)(B)(iii)(III) of this title.

Cont'd...