RULE §334.49Corrosion Protection

      (iii) The component may be inspected and/or tested by an alternative method which has been reviewed and determined by the agency to ascertain electrical isolation and to prevent the release or threatened release of any stored regulated substance in a manner that is no less protective of human health and safety and the environment than the methods described in clauses (i) and (ii) of this subparagraph, in accordance with the procedures in §334.43 of this title.

    (B) The inspections and tests required in subparagraph (A) of this paragraph shall be conducted within three to six months after installation of the metal component, and then once every three years thereafter for the remaining operational life of the UST system.

    (C) If the tests required in subparagraph (A) of this paragraph indicate that the metal component is no longer electrically isolated from the surrounding soil, backfill, groundwater or any other water, or from other metal components, a qualified corrosion specialist shall review the test results and thoroughly inspect the area of the metal component to ascertain the extent of electrical isolation and corrosion protection for the component.

    (D) If the qualified corrosion specialist determines that the metal component is no longer adequately protected from corrosion, the owner or operator shall assure that one or more of the following procedures are completed within 60 days of the date of such determination:

      (i) appropriate repairs or modifications shall be made to restore the electrical isolation of the protected component; or

      (ii) a field-installed cathodic protection system meeting the requirements of subsection (c)(2) of this section shall be installed.

  (2) Dual-protected tanks. If a steel/fiberglass-reinforced plastic composite tank, a steel tank with a bonded fiberglass-reinforced plastic external cladding or laminate, a steel tank with a bonded fiberglass reinforced polyurethane coating, or a steel tank with a bonded polyurethane coating is also equipped with a factory-installed cathodic protection system, then the normal inspection and testing requirements for cathodic protection systems in subsection (c)(4) of this section may be waived. This paragraph shall be applicable only to tanks meeting the design and construction requirements in §334.45(b)(1)(D) or (E) of this title, as applicable, and when such tanks are fitted with factory-installed cathodic protection systems meeting the requirements of subsection (c)(1) of this section.

(e) Corrosion protection records.

  (1) Owners and operators shall maintain all corrosion protection records required in this subsection in accordance with the requirements in §334.10(b) of this title.

  (2) Owners and operators shall maintain records adequate to demonstrate compliance with the corrosion protection requirements in this section, and in accordance with the following minimum requirements.

    (A) All appropriate installation records related to the corrosion protection system, as listed in §334.46(i) of this title, shall be maintained for as long as the corrosion protection system is used, including:

      (i) the name, address, telephone number, and corrosion protection credentials of either the company which designed the factory-installed cathodic protection system or the corrosion specialist who designed the field-installed cathodic protection system, as applicable;

      (ii) drawings or plans depicting the locations of all cathodic protection system components, including the locations of all test stations; and

      (iii) operating instructions and warranty information, maintenance schedules, and testing procedures for all operational components of the cathodic protection systems.

    (B) The following corrosion protection records shall be maintained for at least five years after the applicable test or inspection is conducted:

      (i) results of all tests and inspections of any impressed current cathodic protection system conducted in accordance with subsection (c)(2)(C) of this section; and

      (ii) results of all tests and inspections of the adequacy of any cathodic protection system conducted in accordance with subsection (c)(4) of this section; and

      (iii) results of all tests and inspections to assure corrosion protection for electrically isolated components in accordance with subsection (d)(1) of this section.


Source Note: The provisions of this §334.49 adopted to be effective September 29, 1989, 14 TexReg 4714; amended to be effective January 2, 1995, 19 TexReg 10104; amended to be effective November 23, 2000, 25 TexReg 11442; amended to be effective October 30, 2008, 33 TexReg 8790; amended to be effective March 17, 2011, 36 TexReg 1675; amended to be effective May 31, 2018, 43 TexReg 3390