RULE §334.50Release Detection

    (A) Manual tank gauging in accordance with this subparagraph may be used as the sole method of tank release detection only for petroleum substance tanks having a nominal capacity of 1,000 gallons or less.

    (B) The use of manual tank gauging shall not be considered an acceptable method for meeting the release detection requirements of this section for any tanks with a nominal capacity greater than 1,000 gallons.

    (C) When used for compliance with the release detection requirements of this section, the procedures and requirements in the following clauses shall be applicable.

      (i) For purposes of this subparagraph only, the following definitions are applicable.

        (I) Level measurement--The average of two consecutive liquid level readings from a tank gauge, measuring stick, or other measuring equipment.

        (II) Gauging period--A weekly period during which no substance is added to or removed from the tank. The duration of the gauging period is dependent upon tank volume and diameter, as specified in clause (v) of this subparagraph.

        (III) Weekly deviation--The variation between the level measurements taken at the beginning and the end of one gauging period, converted to and expressed as gallons.

        (IV) Monthly deviation--The arithmetic average of four consecutive weekly deviations, expressed as gallons.

      (ii) Any measuring equipment shall be capable of measuring the level of stored substance over the full range of the tank's height to the nearest 1/8 inch.

      (iii) Separate liquid level measurements in the tank shall be taken weekly at the beginning and the ending of the gauging period, and the weekly deviation shall be determined from such level measurements.

      (iv) Once each month, after four consecutive weekly deviations are determined, a monthly deviation shall be calculated.

      (v) For the purposes of the manual tank gauging method of release detection, a release shall be indicated when either the weekly deviation or the monthly deviation exceeds the maximum allowable standards indicated in the following subclauses:

        (I) for a tank with a capacity of 550 gallons or less (any tank diameter): minimum duration of gauging period = 36 hours; weekly standard = ten gallons; monthly standard = five gallons;

        (II) for a tank with a capacity of 551 gallons to 1,000 gallons (when tank diameter is 64 inches): minimum duration of gauging period = 44 hours; weekly standard = nine gallons; monthly standard = four gallons; and

        (III) for a tank with a capacity of 551 gallons to 1,000 gallons (when tank diameter is 48 inches): minimum duration of gauging period = 58 hours; weekly standard = 12 gallons; monthly standard = six gallons.

      (vi) When either the weekly standard or the monthly standard is exceeded and a suspected release is thereby indicated, the owner or operator shall comply with the applicable release reporting, investigation, and corrective action requirements of Subchapter D of this chapter.

  (3) Monthly (every 30 days) tank gauging. Monthly tank gauging may be used as a tank release detection method, subject to the following limitations and requirements.

    (A) Monthly tank gauging in accordance with this paragraph may be used as the sole method of tank release detection only for emergency generator tanks.

    (B) The use of monthly tank gauging shall not be considered an acceptable method for meeting the release detection requirements of this section for any tanks other than emergency generator tanks.

    (C) When used for compliance with the release detection requirements of this section, the procedures and requirements in the following clauses shall be applicable.

      (i) For purposes of this subparagraph only, the following definitions are applicable.

        (I) Level measurement--The average of two consecutive liquid level readings from a tank gauge, measuring stick, or other manual or automatic measuring equipment.

        (II) Gauging period--A period of at least 36 hours during which no substance is added to or removed from the tank.

        (III) Monthly deviation--The variation between the level measurements taken at the beginning and the end of one gauging 30-day period, converted to and expressed as gallons.

      (ii) Any measuring equipment (whether operated manually or automatically) shall be capable of measuring the level of a stored substance over the full range of the tank's height to the nearest 1/8 inch.

      (iii) Separate liquid level measurements in the tank shall be taken at least once every 30 days at the beginning and the ending of the gauging period, and the monthly deviation shall be determined from such level measurements.

      (iv) For the purposes of the 30-day tank gauging method of release detection, a release shall be indicated when the monthly deviation exceeds the maximum allowable standards indicated in the following subclauses:

        (I) for a tank with a capacity of 550 gallons or less: monthly standard = five gallons;

        (II) for a tank with a capacity of 551 gallons to 1,000 gallons: monthly standard = seven gallons;

        (III) for a tank with a capacity of 1,001 gallons to 2,000 gallons: monthly standard = 13 gallons; and

        (IV) for a tank with a capacity greater than 2,000 gallons: monthly standard = 1.0% of the total tank capacity.

      (v) When the monthly standard is exceeded and a suspected release is thereby indicated, the owner or operator shall comply with the applicable release reporting, investigation, and corrective action requirements of Subchapter D of this chapter.

  (4) Automatic tank gauging in combination with inventory control.

    (A) A combination of automatic tank gauging and inventory control may be used as a tank release detection method, subject to the following requirements.

      (i) Inventory control procedures shall be in compliance with paragraph (1)(B) of this subsection.

      (ii) The automatic tank gauging equipment shall be capable of:

        (I) automatically monitoring the in-tank liquid levels, conducting automatic tests for substance loss, and collecting data for inventory control purposes; and

        (II) performing an automatic test for substance loss that can detect a release of 0.2 gallon per hour from any portion of the tank which contains regulated substances.

      (iii) The automatic tank gauge testing must be performed with the system operating in one of the following modes:

        (I) in-tank static testing conducted at least once every 30 days; or

        (II) continuous in-tank leak detection operating on an uninterrupted basis or operating within a process that allows the system to gather incremental measurements to determine the leak status of the tank at least once every 30 days.

    (B) For emergency generator tanks and used oil tanks only, automatic tank gauging may be used as a tank release detection method without inventory control, provided that the automatic tank gauging equipment shall be capable of:

      (i) automatically monitoring the in-tank liquid levels;

      (ii) conducting continuous automatic tests for substance loss during the periods when the emergency generator engine is not in operation;

      (iii) performing an automatic test for substance loss that can detect a release of 0.2 gallon per hour from any portion of the tank which contains regulated substances; and

      (iv) measuring the water level at the bottom of the tank to the nearest 1/8 of an inch at least once every 30 days.

  (5) Vapor monitoring. Equipment and procedures designed to test or monitor for the presence of vapors from the regulated substance (or from a related tracer substance) in the soil gas of the backfilled excavation zone may be used, subject to the following limitations and requirements.

    (A) The bedding and backfill materials in the excavation zone shall be sufficiently porous to allow vapors from any released regulated substance (or related tracer substance) to rapidly diffuse through the excavation zone (e.g., gravel, sand, crushed rock).

    (B) The stored regulated substance, or any tracer substance placed in the tank system, shall be sufficiently volatile so that, in the event of a substance release from the UST system, vapors will develop to a level that can be readily detected by the monitoring devices located in the excavation zone.

    (C) The capability of the monitoring device to detect vapors from the stored regulated substance shall not be adversely affected by the presence of any groundwater, rainfall, and/or soil moisture in a manner that would allow a release to remain undetected for more than 30 days.

Cont'd...