<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 26HEALTH AND HUMAN SERVICES
PART 1HEALTH AND HUMAN SERVICES COMMISSION
CHAPTER 510PRIVATE PSYCHIATRIC HOSPITALS AND CRISIS STABILIZATION UNITS
SUBCHAPTER GPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §510.122New Construction Requirements

        (VI) Directional air flow. Ventilation systems shall be designed and balanced to provide directional flow as shown in Table 3 of §134.131(c) of this title. For reductions and shut down of ventilation systems when a room is unoccupied, the provisions in Note 4 of Table 3 of §134.131(c) of this title shall be followed.

        (VII) Areas requiring fully ducted systems. Fully ducted supply, return and exhaust air for HVAC systems shall be provided for all general patient care areas and where required for fire safety purposes. Combination systems, utilizing both ducts and plenums for movement of air in these areas shall not be permitted. Such areas include isolation rooms and food preparation areas.

        (VIII) Ventilation start-up requirements. Air handling systems shall not be started up and operated without the filters installed in place. This includes the 90% efficiency filters where required. Ducts shall be cleaned thoroughly by an air duct cleaning contractor when the air handling systems have been operating without the required filters in place.

        (IX) Humidifier location. When duct humidifiers are located upstream of the final filters, they shall be located at least 15 feet from the filters. Ductwork with duct-mounted humidifiers shall be provided with a means of removing water accumulation. An adjustable high-limit humidistat shall be located downstream of the humidifier to reduce the potential of condensation inside the duct. All duct take-offs should be sufficiently downstream of the humidifier to ensure complete moisture absorption. Reservoir-type water spray or evaporative pan humidifiers shall not be used.

      (ii) Filtration requirements. All central air handling systems serving patient care areas, including nursing unit corridors, shall be equipped with filters having efficiencies equal to, or greater than, those specified for those types of areas in Table 4 of §134.131(d) of this title. Filter efficiencies shall be average efficiencies tested in accordance with American Society of Heating, Refrigerating, and Air-conditioning Engineers (ASHRAE), Inc., Standard 52, 1999 edition, (relating to Gravimetric and Dust Spot Procedures for Testing Air Cleaning Devices Used in General Ventilation for Removing Particulate Matter). All joints between filter segments, and between filter segments and the enclosing ductwork, shall have gaskets and seals to provide a positive seal against air leakage. Air handlers serving more than one room shall be considered as central air handlers. All documents published by ASHRAE as referenced in this section may be obtained by writing or calling the ASHRAE, Inc. at the following address or telephone number: ASHRAE, Inc., 1791 Tullie Circle, N. E., Atlanta, GA 30329; telephone (404) 636-8400.

        (I) Filtration requirements for air handling units serving single rooms requiring asepsis control. Dedicated air handlers serving only one room where asepsis control is required, such as, but not limited to, operating rooms, delivery rooms, special procedure rooms, and nurseries shall be equipped with filters having efficiencies equal to, or greater than, those specified for patient care areas in Table 4 of §134.131(d) of this title.

        (II) Filtration requirements for air handling units serving other single rooms. Dedicated air handlers serving all other single rooms shall be equipped with nominal filters installed at the return air grille.

        (III) Location of multiple filters. Where two filter beds are required by Table 4 of §134.131(d) of this title, filter bed number one shall be located upstream of the air-conditioning equipment, and filter bed number two shall be downstream of the supply fan or blowers.

        (IV) Location of single filters. Where only one filter bed is required by Table 4 of §134.131(d) of this title, it shall be located upstream of the supply fan. Filter frames shall be durable and constructed to provide an airtight fit with the enclosing ductwork.

        (V) Pressure monitoring devices. A manometer or draft gauge shall be installed across each filter bed having a required efficiency of 75% or more including hoods requiring high efficiency particulate air (HEPA) filters.

      (iii) Thermal and acoustical insulation for air handling systems. Asbestos insulation shall not be used.

        (I) Thermal duct insulation. Air ducts and casings with outside surface temperature below ambient dew point or temperature above 80 degrees Fahrenheit shall be provided with thermal insulation.

        (II) Insulation in air plenums and ducts. Linings in air ducts and equipment shall meet the Erosion Test Method described in Underwriters Laboratories, Inc., Standard Number 181 (relating to Factory-Made Duct Materials and Air Duct Connectors). This document may be obtained from the Underwriters Laboratories, Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

        (III) Insulation flame spread and smoke developed ratings. Interior and exterior insulation, including finishes and adhesives on the exterior surfaces of ducts and equipment, shall have a flame spread rating of 25 or less and a smoke developed rating of 50 or less as required by NFPA 90A, Chapters 2 and 3.

        (IV) Linings and acoustical traps. Duct lining and acoustical traps exposed to air movement shall not be used in ducts serving critical care areas. This requirement shall not apply to mixing boxes and acoustical traps that have approved nonabrasive coverings over such linings.

        (V) Frangible insulation. Insulation of soft and spray-on types shall not be used where it is subject to air currents or mechanical erosion or where loose particles may create a maintenance problem.

        (VI) Existing duct linings. Internal linings shall not be used in ducts, terminal boxes, or other air system components supplying operating rooms, delivery rooms, birthing rooms, labor rooms, recovery rooms, nurseries, trauma rooms, isolation rooms, and intensive care units unless terminal filters of at least 90% efficiency are installed downstream of linings.

      (iv) Fire damper requirements. Fire dampers shall be located and installed in all ducts at the point of penetration of a two-hour or higher fire rated wall or floor in accordance with the requirements of NFPA 101, §18-5.2.

      (v) Smoke damper requirements. Smoke dampers shall be located and installed in accordance with the requirements of NFPA 101, §18-3.7.3, and NFPA 90A, Chapter 3.

        (I) Fail-safe installation. Smoke dampers shall close on activation of the fire alarm system by smoke detectors installed and located as required by National Fire Protection Association 72, National Fire Alarm Code, 1999 edition (NFPA 72), Chapter 5; NFPA 90A, Chapter 4; and NFPA 101, §18-3.7; the fire sprinkler system; and upon loss of power. Smoke dampers shall not close by fan shut-down alone.

        (II) Interconnection of air handling fans and smoke dampers. Air handling fans and smoke damper controls may be interconnected so that closing of smoke dampers will not damage the ducts.

        (III) Frangible devices. Use of frangible devices for shutting smoke dampers is not permitted.

      (vi) Acceptable damper assemblies. Only fire damper and smoke damper assemblies integral with sleeves and listed for the intended purpose shall be acceptable.

      (vii) Duct access doors. Unobstructed access to duct openings in accordance with NFPA 90A, §2-3.4, shall be provided in ducts within reach and sight of every fire damper, smoke damper and smoke detector. Each opening shall be protected by an internally insulated door which shall be labeled externally to indicate the fire protection device located within.

      (viii) Restarting controls. Controls for restarting fans may be installed for convenient fire department use to assist in evacuation of smoke after a fire is controlled, provided that provisions are made to avoid possible damage to the system because of closed dampers. To accomplish this, smoke dampers shall be equipped with remote control devices.

      (ix) Make-up air. If air supply requirements in Table 3 of §134.131(c) of this title do not provide sufficient air for use by exhaust hoods and safety cabinets, filtered make-up air shall be ducted to maintain the required air flow direction in that room. Make-up systems for hoods shall be arranged to minimize short circuiting of air and to avoid reduction in air velocity at the point of contaminant capture.

  (4) General piping systems and plumbing fixture requirements. All piping systems and plumbing fixtures shall be designed and installed in accordance with the requirements of the National Standard Plumbing Code, published by the National Association of Plumbing-Heating-Cooling Contractors (PHCC), 2000 edition, and this paragraph. The National Standard Plumbing Code may be obtained by writing or calling the PHCC at the following address or telephone number: Plumbing-Heating-Cooling Contractors, P. O. Box 6808, Falls Church, VA 22040; telephone (800) 533-7694. The facility shall comply with the requirements of this paragraph and any specific piping systems and plumbing requirements for the Cont'd...

Next Page Previous Page

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page