<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 26HEALTH AND HUMAN SERVICES
PART 1HEALTH AND HUMAN SERVICES COMMISSION
CHAPTER 510PRIVATE PSYCHIATRIC HOSPITALS AND CRISIS STABILIZATION UNITS
SUBCHAPTER GPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §510.122New Construction Requirements

        (I) Thermal duct insulation. Air ducts and casings with outside surface temperature below ambient dew point or temperature above 80 degrees Fahrenheit shall be provided with thermal insulation.

        (II) Insulation in air plenums and ducts. Linings in air ducts and equipment shall meet the Erosion Test Method described in Underwriters Laboratories, Inc., Standard Number 181 (relating to Factory-Made Duct Materials and Air Duct Connectors). This document may be obtained from the Underwriters Laboratories, Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

        (III) Insulation flame spread and smoke developed ratings. Interior and exterior insulation, including finishes and adhesives on the exterior surfaces of ducts and equipment, shall have a flame spread rating of 25 or less and a smoke developed rating of 50 or less as required by NFPA 90A, Chapters 2 and 3.

        (IV) Linings and acoustical traps. Duct lining and acoustical traps exposed to air movement shall not be used in ducts serving critical care areas. This requirement shall not apply to mixing boxes and acoustical traps that have approved nonabrasive coverings over such linings.

        (V) Frangible insulation. Insulation of soft and spray-on types shall not be used where it is subject to air currents or mechanical erosion or where loose particles may create a maintenance problem.

        (VI) Existing duct linings. Internal linings shall not be used in ducts, terminal boxes, or other air system components supplying operating rooms, delivery rooms, birthing rooms, labor rooms, recovery rooms, nurseries, trauma rooms, isolation rooms, and intensive care units unless terminal filters of at least 90% efficiency are installed downstream of linings.

      (iv) Fire damper requirements. Fire dampers shall be located and installed in all ducts at the point of penetration of a two-hour or higher fire rated wall or floor in accordance with the requirements of NFPA 101, §18-5.2.

      (v) Smoke damper requirements. Smoke dampers shall be located and installed in accordance with the requirements of NFPA 101, §18-3.7.3, and NFPA 90A, Chapter 3.

        (I) Fail-safe installation. Smoke dampers shall close on activation of the fire alarm system by smoke detectors installed and located as required by National Fire Protection Association 72, National Fire Alarm Code, 1999 edition (NFPA 72), Chapter 5; NFPA 90A, Chapter 4; and NFPA 101, §18-3.7; the fire sprinkler system; and upon loss of power. Smoke dampers shall not close by fan shut-down alone.

        (II) Interconnection of air handling fans and smoke dampers. Air handling fans and smoke damper controls may be interconnected so that closing of smoke dampers will not damage the ducts.

        (III) Frangible devices. Use of frangible devices for shutting smoke dampers is not permitted.

      (vi) Acceptable damper assemblies. Only fire damper and smoke damper assemblies integral with sleeves and listed for the intended purpose shall be acceptable.

      (vii) Duct access doors. Unobstructed access to duct openings in accordance with NFPA 90A, §2-3.4, shall be provided in ducts within reach and sight of every fire damper, smoke damper and smoke detector. Each opening shall be protected by an internally insulated door which shall be labeled externally to indicate the fire protection device located within.

      (viii) Restarting controls. Controls for restarting fans may be installed for convenient fire department use to assist in evacuation of smoke after a fire is controlled, provided that provisions are made to avoid possible damage to the system because of closed dampers. To accomplish this, smoke dampers shall be equipped with remote control devices.

      (ix) Make-up air. If air supply requirements in Table 3 of §134.131(c) of this title do not provide sufficient air for use by exhaust hoods and safety cabinets, filtered make-up air shall be ducted to maintain the required air flow direction in that room. Make-up systems for hoods shall be arranged to minimize short circuiting of air and to avoid reduction in air velocity at the point of contaminant capture.

  (4) General piping systems and plumbing fixture requirements. All piping systems and plumbing fixtures shall be designed and installed in accordance with the requirements of the National Standard Plumbing Code, published by the National Association of Plumbing-Heating-Cooling Contractors (PHCC), 2000 edition, and this paragraph. The National Standard Plumbing Code may be obtained by writing or calling the PHCC at the following address or telephone number: Plumbing-Heating-Cooling Contractors, P. O. Box 6808, Falls Church, VA 22040; telephone (800) 533-7694. The facility shall comply with the requirements of this paragraph and any specific piping systems and plumbing requirements for the particular unit or suite of the facility in accordance with §134.123 of this title.

    (A) Piping systems.

      (i) Water supply systems. Water service pipe to point of entrance to the building shall be brass pipe, copper tube (not less than type M when buried directly), copper pipe, cast iron water pipe, galvanized steel pipe, or approved plastic pipe. Water distribution system piping within buildings shall be brass pipe, copper pipe, copper tube, or galvanized steel pipe. Piping systems shall be designed to supply water at sufficient pressure to operate all fixtures and equipment during maximum demand.

        (I) Valves. Each water service main, branch main, riser, and branch to a group of fixtures shall be valved. Stop valves shall be provided at each fixture.

        (II) Backflow preventers. Backflow preventers (vacuum breakers) shall be installed on hose bibbs, laboratory sinks, janitor sinks, bedpan flushing attachments, and on all other fixtures to which hoses or tubing can be attached.

        (III) Flushing valves. Flush valves installed on plumbing fixtures shall be of a quiet operating type, equipped with silencers.

        (IV) Capacity of water heating equipment. Water heating equipment shall have sufficient capacity to supply water for clinical, dietary and laundry use at the temperatures and amounts specified in Table 5 of §134.131(e) of this title.

        (V) Water temperature measurements. Water temperatures shall be measured at hot water point of use or at the inlet to processing equipment.

        (VI) Water storage tanks. Water storage tank(s) shall be fabricated of corrosion-resistant metal or lined with noncorrosive material.

        (VII) Hot water distribution. Water distribution systems shall be arranged to provide hot water at each hot water outlet at all times.

        (VIII) Emergency water supply. Emergency potable water storage shall be provided. The storage capacity shall not be less than 500 gallons or 12 gallons per patient bed, whichever is greater. Capacity of hot water storage tanks may be included as part of the required emergency water capacity when valves and piping systems are arranged to make this water available at all times.

      (ii) Fire sprinkler systems. Fire sprinkler systems shall be provided in facilities as required by NFPA 101, §18-3.5. All fire sprinkler systems shall be designed, installed, and maintained in accordance with the requirements of NFPA13, and shall be certified as required by §134.127(d)(3)(C) of this title (relating to Preparation, Submittal, Review and Approval of Plans).

      (iii) Nonflammable medical gas and clinical vacuum systems. Nonflammable medical gas and clinical vacuum system installations shall be designed, installed and certified in accordance with the requirements of NFPA 99, §4-3 for Level I systems and the requirements of this clause.

        (I) Outlets. Nonflammable medical gas and clinical vacuum outlets shall be provided in accordance with Table 6 of §134.131(f) of this title.

        (II) Installer qualifications. All installations of the medical gas piping systems shall be done only by, or under the direct supervision of a holder of a master plumber license or a journeyman plumber license with a medical gas piping installation endorsement issued by the Texas State Board of Plumbing Examiners.

        (III) Installer tests. Prior to closing of walls, the installer shall perform an initial pressure test, a blowdown test, a secondary pressure test, a cross-connection test, and a purge of the piping system as required by NFPA 99.

        (IV) Qualifications for conducting verification tests and inspections. Verification tests and inspections by a party, other than the installer, shall be conducted by individuals who are technically competent and experienced in the field of piped medical gas systems.

Cont'd...

Next Page Previous Page

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page