TITLE 26HEALTH AND HUMAN SERVICES
PART 1HEALTH AND HUMAN SERVICES COMMISSION
CHAPTER 510PRIVATE PSYCHIATRIC HOSPITALS AND CRISIS STABILIZATION UNITS
SUBCHAPTER GPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §510.123Spatial Requirements for New Construction

    (B) Interior finishes, lighting, and furnishings shall present an atmosphere which is as noninstitutional as possible, consistent with applicable fire safety requirements. Security and safety devices should not be present in a manner to attract or challenge tampering by patients.

  (2) Architectural requirements. Architectural requirements shall be in accordance with §134.122(d)(1) of this title and this paragraph.

    (A) Handicapped accessibility requirements. At least 10% of patient room suites, bathing units and toilets, and all public and common use areas shall be designed and constructed to be handicapped accessible. These requirements shall apply in all new construction and when an existing nursing suite or a portion thereof is converted from one service to another.

    (B) Patient room suites. A patient room suite shall consist of the patient room and a toilet room or bathroom. Patient room suites shall comply with the following requirements.

      (i) Maximum patient room capacity. The maximum patient room capacity shall be two patients. In existing facilities where renovation work is undertaken and the present capacity is more than two patients, the maximum room capacity shall be no more than the present capacity with a maximum of four patients.

      (ii) Single-bed patient room. In a single-bed patient room, the minimum clear floor area shall be 100 square feet. The minimum clear floor area in an accessible private patient room shall be 120 square feet. The minimum room dimension shall be not less than 10 feet.

      (iii) Multi-bed patient room. In a multi-bed patient room, the minimum clear floor area shall be 80 square feet per bed. Minimum clear floor space in an accessible multi-bed room shall be 110 square feet per bed. Design of multi-bed patient rooms shall not restrict independent patient access to the corridor, lavatory, or bathroom.

      (iv) Arrangement of patient rooms. Minor encroachments including columns and wall hung lavatories that do not interfere with functions may be ignored when determining space requirements for patient rooms.

        (I) Required clear floor space in patient rooms shall be exclusive of toilet rooms, closets, lockers, built-in cabinets, wardrobes, alcoves, or vestibules.

        (II) A clearance of 3 feet 8 inches shall be available at the foot of each bed in multi-bed patient rooms to permit the passage of equipment and beds. A minimum distance of three feet between a wall and the side of a bed and four feet between beds shall be provided. A minimum distance of five feet between a wall and the side of a bed and four feet between beds shall be provided in an accessible semi-private room or one intended for rehabilitation patients. Arrangement of beds shall be such that sufficient space is provided for a bed and maneuvering space for a wheelchair.

        (III) Sleeping areas shall have doors for privacy. Design for visual privacy in multi-bed rooms shall not restrict patient access to the room, toilet, or observation by staff.

      (v) Patient bathroom. Each patient shall have access to a bathroom without having to enter the general corridor area. Each bathroom shall contain a toilet, hand washing fixtures, and storage shelf or cabinet and serve not more than four patient beds or two patient rooms. Hand washing fixtures may be located in the patient room.

      (vi) Bathing rooms. One bathtub or shower shall be provided for each four patient beds or space which is not otherwise served by bathing rooms within patients' rooms. Each tub or shower shall be in an individual room or enclosure which provides space for the private use of the bathing fixture and for drying and dressing.

      (vii) Patient storage. Each patient shall have a separate wardrobe, locker, or closet that is suitable for hanging full-length garments and for storing personal effects. A minimum of 12 lineal inches of hanging space shall be provided per patient.

    (C) Security rooms. When security rooms are provided by the treatment program narrative, the security rooms shall be single patient suite rooms designed to minimize potential for escape, hiding, injury to self or others, or suicide. Access to toilets, showers, and wardrobes shall be restricted. The patient room suite shall be in accordance with subparagraph (B)(ii) of this paragraph. Security rooms may be centralized on one unit or decentralized among units.

    (D) Seclusion suite. There shall be a seclusion suite in each nursing suite intended for short-term occupancy by a single person requiring security and protection from self or others. The seclusion suite shall consist of seclusion room(s), an anteroom or a vestibule, a toilet, and hand washing fixtures.

      (i) Each seclusion room shall be located and designed in a manner affording direct visual supervision by nursing staff and shall be constructed to prevent patient hiding, escape, injury, or suicide. There shall be a minimum of one seclusion room for each 24 beds or any portion thereof.

        (I) The floor area of each seclusion room shall be not less than 60 square feet. The minimum room dimension shall be six feet.

        (II) The seclusion room shall have a minimum ceiling height of nine feet.

        (III) The door to each seclusion room shall have no hardware on the room side and shall open out. A vision panel shall be provided in each door to permit staff observation of the entire room while maintaining privacy from the public and other patients. The seclusion room door shall swing out.

        (IV) Each seclusion room shall have natural light (skylight or window) in order to maintain a therapeutic environment. Skylight wells or windows shall be not less than 400 square inches in area.

      (ii) Access to the seclusion room from any public space such as a corridor shall be through an anteroom. When the seclusion suite is directly accessible from the nurse station, a vestibule may be provided in place of an anteroom. A cased opening to the vestibule in lieu of a door may be provided as long as the arrangement assures privacy from the public and other patients.

        (I) The minimum dimension of the anteroom or vestibule shall be eight feet.

        (II) The door to the anteroom shall swing in.

      (iii) There shall be at least one toilet room directly accessible from the anteroom or vestibule.

        (I) The toilet room shall be large enough to safely manage the patient.

        (II) The toilet room door shall swing out into the anteroom or vestibule.

        (III) A water closet and hand washing fixtures shall be provided in the toilet room. An unbreakable wall hung mirror may be provided.

        (IV) Doors for the seclusion room and anteroom shall be not less than 3 feet 8 inches in width.

        (V) When the interior of the seclusion room is padded, the padding shall be a Class "A." The flame spread rating shall be 0-25 and the smoke development rating shall be 0-450 in accordance with NFPA 101, Chapter 8.

    (E) Airborne infection isolation suites. When an isolation suite is provided, the suite may be located within a nursing suite or in a separate isolation unit. Each airborne infection isolation suite shall consist of a work area, a patient room, and a patient bathroom.

      (i) The work area may be a separately enclosed anteroom or a vestibule that is open to and is located immediately inside the door to the patient room. It shall have amenities for hand washing, gowning, and storage of clean and soiled materials. One enclosed anteroom may serve multiple isolation rooms.

      (ii) Each patient room shall have a clear floor area of 120 square feet exclusive of the work area and shall contain only one bed.

      (iii) Each bathroom shall be designed for the use of the handicapped and shall contain bathing fixtures, toilet fixtures and hand washing fixtures. Each bathroom shall be arranged to provide access from the patient room without entering or passing through the work area.

      (iv) At least one airborne infection isolation suite with an enclosed anteroom shall be provided.

      (v) Ventilation requirements for the isolation rooms shall be in accordance with Table 3 of §134.131(c) of this title.

      (vi) Doors to airborne infection isolation rooms shall be provided with self-closing devices.

    (F) Social spaces. A minimum of two separate social spaces, one appropriate for noisy activities and the other for quiet activities, shall be provided. The combined total area shall be not less than 40 square feet per bed space with not less than 160 square feet for each of the two spaces, whichever is greater. This space may be shared with the dining area or room.

    (G) Group therapy room. A room for group therapy shall be included. The room shall not be less than 250 square feet. The group therapy room may be combined with the quiet space required in subparagraph (F) of this paragraph provided that a space of not less than 370 square feet is available for both the quiet activity room and group therapy activities.

Cont'd...