TITLE 26HEALTH AND HUMAN SERVICES
PART 1HEALTH AND HUMAN SERVICES COMMISSION
CHAPTER 510PRIVATE PSYCHIATRIC HOSPITALS AND CRISIS STABILIZATION UNITS
SUBCHAPTER GPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §510.123Spatial Requirements for New Construction

      (xi) Sanitizing facilities. Storage areas and sanitizing facilities for garbage or refuse cans, carts, and mobile tray conveyors shall be provided. All containers for trash storage shall have tight-fitting lids.

      (xii) Housekeeping room. A housekeeping room shall be provided for the exclusive use of the dietary department. Where hot water or steam is used for general cleaning, additional space within the room shall be provided for the storage of hoses and nozzles.

      (xiii) Office spaces. An office shall be provided for the use of the food service manager or the dietary service manager. In smaller facilities, a designated alcove may be located in an area that is part of the food preparation area.

      (xiv) Toilets and locker spaces. A toilet room(s) shall be provided for the exclusive use of the dietary staff. Toilets shall not open directly into the food preparation areas, but must be in close proximity to them. For larger facilities, a locker room or space for lockers shall be provided for staff belongings.

    (C) Additional service areas, rooms and facilities. When an on-site food preparation system is used, in addition to the items required in subparagraph (B), the following service areas, rooms and facilities shall be provided.

      (i) Food preparation facilities. When food preparation systems are provided, there shall be space and equipment for preparing, cooking, and baking.

      (ii) Tray assembly line. A patient tray assembly and distribution area shall be located within close proximity to the food preparation and distribution areas.

      (iii) Food storage. The food storage room shall be adequate in size to accommodate food for a seven calendar day menu cycle.

      (iv) Additional storage area(s). Additional area(s) shall be provided for the storage of cooking wares, extra trays, flatware, plastic and paper products, and portable equipment.

      (v) Drying storage area. Provisions shall be made for drying and storage of pots and pans from the pot washing room.

    (D) Equipment. Equipment for use in the dietary suite shall meet the following requirements.

      (i) Mechanical devices shall be heavy duty, suitable for the use intended, and easily cleaned. Where equipment is movable, provide heavy duty locking casters. Equipment with fixed utility connections shall not be equipped with casters.

      (ii) Floor, wall, and top panels of walk-in coolers, refrigerators, and freezers shall be insulated. Coolers and refrigerators shall be capable of maintaining a temperature down to freezing. Freezers shall be capable of maintaining a temperature of 20 degrees below 0 degrees Fahrenheit. Coolers, refrigerators, and freezers shall be thermostatically controlled to maintain desired temperature settings in increments of two degrees or less. Interior temperatures shall be indicated digitally and visible from the exterior. Controls shall include audible and visible high and low temperature alarm. The time of alarm shall be automatically recorded.

      (iii) Walk-in units may be lockable from the outside but must have a release mechanism for exit from inside at all times. The interior shall be lighted. All shelving shall be corrosion resistant, easily cleaned, and constructed and anchored to support a loading of at least 100 pounds per linear foot.

      (iv) All cooking equipment shall be equipped with automatic shut-off devices to prevent excessive heat buildup.

    (E) Vending services. When vending machines are provided, a dedicated room or an alcove shall be located so that access is available at all times.

  (2) Details and finishes. Details and finishes shall be in accordance with §134.122(d)(2) of this title and this paragraph.

    (A) Details.

      (i) Food storage shelves shall not be less than six inches above the finished floor and the space below the bottom shelf shall be closed in and sealed tight for ease of cleaning.

      (ii) Operable windows and doors not equipped with automatic closing devices shall be equipped with insect screens.

      (iii) Food processing areas in the central dietary kitchen shall have ceiling heights not less than nine feet. Ceiling mounted equipment shall be supported from rigid structures located above the finished ceiling.

      (iv) Mirrors shall not be installed at hand washing fixtures in the food preparation areas.

    (B) Finishes.

      (i) Floors in areas used for food preparation, food assembly, soiled and clean ware cleaning shall be water-resistant and grease-proof. Floor surfaces, including tile joints, shall be resistant to food acids.

      (ii) Wall bases in food preparation, food assembly, soiled and clean ware cleaning and other areas which are frequently subject to wet cleaning methods shall be made integral and coved with the floor, tightly sealed to the wall, constructed without voids that can harbor insects, retain dirt particles, and be impervious to water.

      (iii) In the dietary and food preparation areas, the wall construction, finishes, and trim, including the joints between the walls and the floors, shall be free of voids, cracks, and crevices.

      (iv) The ceiling in food preparation and food assembly areas shall be washable as required by §134.122(d)(2)(B)(vi)(II).

      (v) The ceiling in the food storage room, and soiled and clean ware cleaning area shall be of the monolithic type as required by §134.122(d)(2)(B)(vi)(III).

  (3) Mechanical Requirements. Mechanical requirements shall be in accordance with §134.122(d)(3) of this title and this paragraph.

    (A) Exhaust hoods handling grease-laden vapors in food preparation centers shall comply with National Fire Protection Association 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, 1998 edition. All hoods over cooking ranges shall be equipped with grease filters, fire extinguishing systems, and heat-actuated fan controls. Clean out openings shall be provided every 20 feet and at any changes in direction in the horizontal exhaust duct systems serving these hoods. (Horizontal runs of ducts serving range hoods should be kept to a minimum.)

    (B) When air change standards in Table 3 of §134.131(c) of this title do not provide sufficient air for proper operation of exhaust hoods (when in use), supplementary filtered makeup air shall be provided in these rooms to maintain the required airflow direction and exhaust velocity. Makeup systems for hoods shall be arranged to minimize "short circuiting" of air and to avoid reduction in air velocity at the point of contaminant capture.

    (C) Air handling units serving the dietary suite shall be equipped with filters having efficiencies equal to, or greater than specified in Table 4 of §134.131(d) of this title.

  (4) Piping systems and plumbing fixtures. Piping systems and plumbing fixtures shall be in accordance with §134.122(d)(4) of this title and this paragraph.

    (A) The kitchen grease traps shall be located and arranged to permit easy access without the need to enter food preparation or storage areas. Grease traps shall be of capacity required and shall be accessible from outside of the building without need to interrupt any services.

    (B) Grease traps or grease interceptors shall be located outside the food preparation area and shall comply with the requirements in the National Association of Plumbing-Heating-Cooling Contractors (PHCC), National Standard Plumbing Code, 2000 edition. This publication may be obtained from the National Association of Plumbing-Heating-Cooling Contractors, 180 South Washington Street, Falls Church, VA 22046; telephone (703) 237-8100.

    (C) The material used for plumbing fixtures shall be non-absorptive and acid-resistant.

    (D) Water spouts used at lavatories and sinks shall have clearances adequate to avoid contaminating utensils and containers.

    (E) Hand washing fixtures used by food handlers shall be trimmed with valves that can be operated without hands. Single lever or wrist blade devices may be used. Blade handles used for this purpose shall not be less than four inches in length.

    (F) Drainage and waste piping shall not be installed in the space above the ceiling or installed in an exposed location in food preparation centers, food serving facilities and food storage areas unless special precautions are taken to protect the space below from leakage and condensation from necessary overhead piping.

    (G) No plumbing lines may be exposed overhead or on walls where possible leaks would create a potential for food contamination.

  (5) Electrical requirements. Electrical requirements shall be in accordance with §134.122(d)(5) of this title and this paragraph.

    (A) Exhaust hoods shall have an indicator light indicating that the exhaust fan is in operation.

Cont'd...