<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 26HEALTH AND HUMAN SERVICES
PART 1HEALTH AND HUMAN SERVICES COMMISSION
CHAPTER 506SPECIAL CARE FACILITIES
SUBCHAPTER HPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §506.91Construction Requirements

      (x) Wiring. When a SCF provides an essential electrical system all conductors for controls, equipment, lighting and power operating at 100 volts or higher shall be installed in metal or metallic raceways in accordance with the requirements of NFPA 70, Article 517. All surface mounted wiring operating at less than 100 volts shall be protected from mechanical injury with metal raceways to a height of seven feet above the floor. Conduits and cables shall be supported in accordance with NFPA 70, Article 300.

      (xi) Lighting.

        (I) In LCF lighting intensity for staff and patient needs shall comply with guidelines for health care facilities set forth in the Illuminating Engineering Society of North America (IES) Handbook published by the Illuminating Engineering Society of North America, 120 Wall Street, New York, NY 10025-4001.

          (-a-) Consideration should be given to controlling light intensity and wavelength to prevent harm to the patient's eyes.

          (-b-) Approaches to buildings and parking lots, and all spaces within buildings shall have fixtures that can be illuminated as necessary. All rooms including storerooms, electrical and mechanical equipment rooms, and all attics shall have sufficient artificial lighting so that all spaces shall be clearly visible.

        (II) Means of egress and exit sign lighting intensity shall comply with NFPA 101, §§5-8, 5-9 and 5-10.

        (III) Electric lamps which may be subject to breakage or which are installed in fixtures in confined locations when near woodwork, paper, clothing, or other combustible materials, shall be protected by wire guards, or plastic shields.

      (xii) Receptacles.

        (I) Appliances shall be grounded in accordance with NFPA 99, Chapter 9.

        (II) A minimum of one duplex receptacle in each wall shall be installed in each work area or room other than storage or lockers. Each examination and work table shall have access to a minimum of two duplex receptacles.

      (xiii) Grounding requirements. Fixed electrical equipment shall be grounded in accordance with the requirements of NFPA 99, §3-3.1.2, and NFPA 70, Article 517-13.

      (xiv) Nurses calling systems.

        (I) An audible voice two way communication nurse call system shall be provided in a SCF when it is classified as a LCF. The audible signal shall sound at a nurse station or similar control station.

        (II) Distinct visible and audible signals shall be activated in the nurse's duty station, lounge, and workroom, soiled workroom and clean workroom.

      (xv) Essential electrical system (EES). When SCF provides or requires an essential electrical system, the EES system shall comply with the requirements of NFPA 99, §3-5. A Type I EES shall be provided for LCF when patients require the use of life-support systems.

      (xvi) Fire alarm system. A fire alarm system which complies with the requirements of NFPA 101, §§12-6.3.4, 32.2.3.4.1, 32.3.3.4.1, NFPA 70, Article 760; and NFPA 72, Chapter 3, shall be provided in each facility.

        (I) Fire alarm system shall be installed by or under direct supervision of a fire alarm installer licensed by the State Fire Marshal.

        (II) The SCF shall submit a copy of the Fire Alarm Installation Certificate (State Fire Marshal's form FML 009 040392) to the department for all new installations and for any material changes to the existing systems.


Source Note: The provisions of this §506.91 adopted to be effective July 25, 2004, 29 TexReg 6911; transferred effective June 1, 2019, as published in the Texas Register May 17, 2019, 44 TexReg 2467

Previous Page

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page