RULE §559.42Safety

    (L) Portable fire extinguishers of appropriate type and placed in the appropriate location must be provided by the facility in accordance with NFPA 10.

    (M) The facility must inspect and maintain portable fire extinguishers.

      (i) Portable fire extinguishers must be visually inspected monthly by facility staff. Facility staff conducting the monthly visual inspection must assure portable fire extinguishers are protected from damage, kept on their mounting brackets or in cabinets at all times, and kept in proper condition and working order.

      (ii) Portable fire extinguishers must be inspected and maintained at least once every 12 months in accordance with NFPA 10 by a person licensed by the State Fire Marshal's office, to include hydrostatic testing as recommended by the manufacturer.

      (iii) A record of all fire extinguisher inspections and maintenance performed must be kept onsite by the facility.

    (N) Garbage, waste, or trash containers provided for kitchens, janitor closets, laundries, mechanical or boiler rooms, general storage, and similar places must be made of metal or any UL- or FM-approved material, having a close fitting cover. Disposable plastic liners may be used in these containers for sanitation.

  (2) General requirements.

    (A) All exterior site conditions must be designed, constructed, and maintained in the interest of clients' safety. Newly constructed ramps must not exceed 1:12 slope. Ramps, walks, and steps must be of slip-resistive texture and be smooth and uniform, without irregularities. Guard rails, fences, and hand rails must be provided as required.

    (B) All stairways must have substantial hand rails properly secured.

    (C) Tubs or showers for client use must have non-slip bottoms or floor surfaces, either built in or applied to the surface.

    (D) Elevators for client use must be in safe operating condition.

    (E) An adequate supply of hot water must be provided. The hot water system connected to all client-use fixtures must deliver warm water no hotter than 120 degrees Fahrenheit at the fixture. Hot water for other sanitary usages must be provided at the temperatures required for the appliance or fixture served, or for the operation involved.

    (F) There must be no occupancies or activities adversely affecting the safety of the clients in the buildings or on the premises of the facility.

    (G) Licensure capacity will be calculated at 40 square feet per client. This space may not include the kitchen/food service area, rest rooms, bath areas, office, corridors, stairways, storage areas, and outdoor space. Facilities licensed before October 1, 2000, will be allowed to meet the requirements in effect before October 1, 2000, of 35/50 square feet for ambulatory and semi- ambulatory clients. If a facility licensed before October 1, 2000, chooses to increase its capacity, changes ownership, or relocates, the facility will be required to meet the current standards for usable space, outdoor area, and rooms for privacy.

    (H) An office area must be provided in a central location to record and maintain files for each client.

    (I) An area for rest, other than the treatment and/or exam room, must be provided with a sufficient number of reclining lounge chairs or beds to accommodate the needs of clients.

    (J) The facility must provide a separate room or rooms with beds and with walls from floor to ceiling for those clients who prefer privacy. Facilities licensed on or after May 1, 1999, must ensure that the room(s) with beds provide space for a minimum 5% of the licensed capacity. The usable space in the room(s) must provide not less than 80 square feet per bed for a one-bed room and not less than 60 square feet per bed for multiple-bed rooms. A bedroom shall be not less than eight feet in its smallest dimension, unless otherwise approved by DADS.

    (K) The facility must have at least one room available as a treatment or examination room for use by the nursing staff or the client's physician. The client may not be treated or examined in an area other than the treatment room.

    (L) The facility must have a safe, secure, and suitable outdoor recreation or relaxation area for clients. This area must be connected to, be a part of, be controlled by, and be directly accessible from the facility. This area must be enclosed by a wall or a fence or located in a courtyard and supervised by staff to prevent wandering and large enough to conduct outdoor activities. A chain- link fence must provide protection on top to prevent injury from wire points. This area must be suitably furnished. A minimum of 20% of the required outdoor space must be shaded. The required outdoor space for facilities licensed on or after May 1, 1999 is:

      (i) 400 square feet for facilities up to 59 clients;

      (ii) 600 square feet for facilities up to 99 clients; and

      (iii) 800 square feet for facilities with 100 or more clients.


Source Note: The provisions of this §559.42 adopted to be effective May 1, 1999, 24 TexReg 3100; amended to be effective November 1, 2000, 25 TexReg 10753; amended to be effective April 1, 2007, 32 TexReg 1749; amended to be effective August 1, 2011, 36 TexReg 4677; transferred effective January 15, 2021, as published in the Texas Register December 18, 2020, 45 TexReg 9249