  (2) Any encapsulation must be performed within a containment.

  (3) Loose and hanging ACBM must be removed before encapsulation. Filler material applied to any gap in existing material must contain no asbestos, adhere well to the substrate, and provide an adequate base for the encapsulating agent.

  (4) Encapsulant must be applied using only airless spray equipment with the nozzle pressure and tip size set according to the manufacturer's recommendations.

  (5) Any encapsulated material must be specifically designated by sign, label, color coding, or other mechanism to warn any individual who may in the future be required to disturb the material.

(e) Requirements for the enclosure of ACBM.

  (1) Acceptable enclosure must be airtight and of permanent construction so that the material enclosed is inaccessible.

  (2) Any area of ACBM that can be reasonably anticipated to be disturbed during the installation of a hanger, bracket, or any other portion of the enclosure must be wetted within containment before such activity.

  (3) Before building the enclosure, loose and hanging ACBM that may be disturbed must be removed.

  (4) Any enclosure for ACBM must be specifically designated by sign, label, color coding, or other mechanism to warn any individual who may in the future be required to disturb the material.

(f) Safety requirements and prohibitions. The following safety requirements must be in effect for an abatement project:

  (1) Fire safety. A minimum of one fire extinguisher with a minimum National Fire Protection Association rating of 10BC (dry chemical) must be placed within each abatement project containment for every 3,000 square feet, or fraction thereof, of containment. One fire extinguisher must be placed at each entrance inside of the containment. Each fire extinguisher must be maintained in a fully charged and operable condition with a current annual inspection tag securely attached reflecting that maintenance was performed by an appropriately licensed individual. Where more than one fire extinguisher is required, they must be distributed proportionately throughout the containment and their locations clearly marked.

  (2) Electrical safety. An active electrical service line within a regulated area and containment must be connected through ground-fault circuit interrupter devices (GFCI). An electrical appliance must not be plugged into an outlet unless equipped with a GFCI.

  (3) Prohibitions. Use of any solvent with a flash point of 140 degrees Fahrenheit or below is prohibited.


Source Note: The provisions of this §296.212 adopted to be effective July 8, 2021, 46 TexReg 3880